1SDA073413R1 ABB E2.2H/MS 2000 3p F HR Switch Disconnector

1SDA073413R1 ABB E2.2H/MS 2000 3p F HR Switch Disconnector

ABB 1SDA073413R1 SACE Emax 2 E2.2H/MS 2000 three-pole fixed switch disconnector with horizontal rear terminals, a 2000 A rated uninterrupted current, 690 V AC operational voltage and 85 kA short-time withstand capability for high-current low-voltage switching and isolation.

SKU: 1SDA073413R1MPN: 1SDA073413R1
Price
List Price £7,932.31 ex VAT
Your Price (ex VAT) Save 25%
£5,949.23 25% OFF
You save £1,983.08 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £5,949.23
Trade pricing is personalised to your account

Manufacturer Lead Time

£5,949.23

Why Choose the ABB E2.2H/MS 2000 3p F HR Switch Disconnector?

The ABB E2.2H/MS 2000 3p F HR, order code 1SDA073413R1, is a high-performance SACE Emax 2 switch disconnector designed for reliable switching and isolation in high-current low-voltage electrical distribution systems. Built on ABB's E2.2 platform, this fixed three-pole device provides a 2000 A rated uninterrupted current and is suitable for industrial, commercial and infrastructure switchboards where robust isolation is required without an integral overcurrent protection trip unit.

The E2.2H/MS configuration is derived from the Emax 2 air circuit breaker platform but operates as a switch disconnector, providing switching and isolation while circuit protection is handled separately within the installation. Its fixed construction and horizontal rear terminals make it particularly suitable for switchboard designs requiring rear busbar or cable connections.

Rated for operation at up to 690 V AC, the E2.2H/MS 2000 provides a rated short-time withstand current of 85 kA for 1 s and 66 kA for 3 s. It is rated for AC-23A switching duty and combines high current-carrying capability with the mechanical platform and accessory flexibility of the ABB SACE Emax 2 range.

Key Advantages

  • High 2000 A rated uninterrupted current for demanding low-voltage distribution systems.
  • Three-pole switch disconnector for three-phase switching and isolation applications.
  • 85 kA short-time withstand current for 1 s for high fault-level electrical networks.
  • 66 kA short-time withstand current for 3 s supports demanding coordination requirements.
  • Rated for operation at up to 690 V AC.
  • Horizontal rear terminals support efficient busbar integration within switchboards.
  • Fixed installation provides a robust and straightforward switchboard arrangement.
  • Optional motor operation and voltage releases support remote and electrically controlled switching applications.

Key Features

  • ABB SACE Emax 2 E2.2H/MS switch disconnector.
  • 2000 A rated uninterrupted current.
  • Three-pole configuration.
  • Fixed installation.
  • Horizontal rear terminals (HR).
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 85 kA rated short-time withstand current for 1 s.
  • 66 kA rated short-time withstand current for 3 s.
  • 2000 A AC-23 switching capability.
  • Utilisation category AC-23A.
  • Optional motor operator.
  • Optional voltage release.
  • Based on ABB's modular Emax 2 air circuit breaker platform.

High-Performance Switching and Isolation for Power Distribution

Switch disconnectors provide a reliable means of making, carrying and isolating electrical circuits while overcurrent and short-circuit protection is provided separately. Devices based on air circuit breaker platforms are particularly useful in high-current switchboards because they combine robust switching mechanisms with high short-time withstand capability and flexible installation options.

The ABB E2.2H/MS 2000 combines a 2000 A continuous-current rating with an 85 kA short-time withstand rating for 1 s. Its fixed three-pole construction and horizontal rear terminals make it well suited to main isolation, busbar switching and high-current feeder applications where dependable isolation and efficient switchboard integration are priorities.

Typical Applications

  • Main switchboard switching and isolation.
  • Industrial low-voltage power distribution systems.
  • High-current feeder switching and isolation.
  • Busbar and bus-section isolation.
  • Manufacturing and process plant switchboards.
  • Commercial buildings and critical infrastructure.

Technical Specifications

Series SACE Emax 2
Order code / MPN 1SDA073413R1
EAN / GTIN 8015644772635
Product type Switch disconnector
Product group Emax 2 Air Circuit Breaker
Frame E2.2
Performance level H/MS
Rated uninterrupted current (Iu) 2000 A
Number of poles 3
Current type AC
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Frequency 50/60 Hz
Rated short-time withstand current (Icw), 1 s 85 kA
Rated short-time withstand current (Icw), 3 s 66 kA
Rated current, AC-21 at 400 V 2000 A
Rated current, AC-23 at 400 V 2000 A
Utilisation category AC-23A
Motor drive Optional
Motor drive integrated No
Voltage release Optional
Main-circuit connection Bolted connection
Installation Fixed
Terminal configuration Horizontal rear terminals (HR)
Dimensions (W × H × D) 276 × 371 × 270 mm
Net weight 41 kg
Standard IEC 60947-3

Frequently Asked Questions

What is the ABB 1SDA073413R1?

The ABB 1SDA073413R1 is an Emax 2 E2.2H/MS 2000 three-pole switch disconnector with fixed installation and horizontal rear terminals, designed for high-current low-voltage switching and isolation.

What is the rated current of the ABB E2.2H/MS 2000?

The E2.2H/MS 2000 has a rated uninterrupted current of 2000 A and is rated for operation at up to 690 V AC.

Is the ABB E2.2H/MS 2000 a circuit breaker or switch disconnector?

The 1SDA073413R1 is a switch disconnector. It is based on the Emax 2 platform but is intended for switching and isolation rather than providing the integral overcurrent protection of an air circuit breaker equipped with an electronic trip unit.

What is the short-time withstand current of the ABB 1SDA073413R1?

The E2.2H/MS 2000 has a rated short-time withstand current of 85 kA for 1 s and 66 kA for 3 s.

What does F HR mean on the ABB E2.2H/MS 2000?

The F designation identifies the fixed installation configuration, while HR identifies the horizontal rear terminal arrangement used to connect the device within the switchboard.

Trusted High-Current Switching from ABB

ABB SACE Emax 2 switch disconnectors combine high continuous-current capability, strong short-time withstand performance and flexible switchboard integration for demanding industrial, commercial and infrastructure power distribution systems.