Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA073413R1 SACE Emax 2 E2.2H/MS 2000 three-pole fixed switch disconnector with horizontal rear terminals, a 2000 A rated uninterrupted current, 690 V AC operational voltage and 85 kA short-time withstand capability for high-current low-voltage switching and isolation.
£5,949.23
The ABB E2.2H/MS 2000 3p F HR, order code 1SDA073413R1, is a high-performance SACE Emax 2 switch disconnector designed for reliable switching and isolation in high-current low-voltage electrical distribution systems. Built on ABB's E2.2 platform, this fixed three-pole device provides a 2000 A rated uninterrupted current and is suitable for industrial, commercial and infrastructure switchboards where robust isolation is required without an integral overcurrent protection trip unit.
The E2.2H/MS configuration is derived from the Emax 2 air circuit breaker platform but operates as a switch disconnector, providing switching and isolation while circuit protection is handled separately within the installation. Its fixed construction and horizontal rear terminals make it particularly suitable for switchboard designs requiring rear busbar or cable connections.
Rated for operation at up to 690 V AC, the E2.2H/MS 2000 provides a rated short-time withstand current of 85 kA for 1 s and 66 kA for 3 s. It is rated for AC-23A switching duty and combines high current-carrying capability with the mechanical platform and accessory flexibility of the ABB SACE Emax 2 range.
Switch disconnectors provide a reliable means of making, carrying and isolating electrical circuits while overcurrent and short-circuit protection is provided separately. Devices based on air circuit breaker platforms are particularly useful in high-current switchboards because they combine robust switching mechanisms with high short-time withstand capability and flexible installation options.
The ABB E2.2H/MS 2000 combines a 2000 A continuous-current rating with an 85 kA short-time withstand rating for 1 s. Its fixed three-pole construction and horizontal rear terminals make it well suited to main isolation, busbar switching and high-current feeder applications where dependable isolation and efficient switchboard integration are priorities.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA073413R1 |
| EAN / GTIN | 8015644772635 |
| Product type | Switch disconnector |
| Product group | Emax 2 Air Circuit Breaker |
| Frame | E2.2 |
| Performance level | H/MS |
| Rated uninterrupted current (Iu) | 2000 A |
| Number of poles | 3 |
| Current type | AC |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50/60 Hz |
| Rated short-time withstand current (Icw), 1 s | 85 kA |
| Rated short-time withstand current (Icw), 3 s | 66 kA |
| Rated current, AC-21 at 400 V | 2000 A |
| Rated current, AC-23 at 400 V | 2000 A |
| Utilisation category | AC-23A |
| Motor drive | Optional |
| Motor drive integrated | No |
| Voltage release | Optional |
| Main-circuit connection | Bolted connection |
| Installation | Fixed |
| Terminal configuration | Horizontal rear terminals (HR) |
| Dimensions (W × H × D) | 276 × 371 × 270 mm |
| Net weight | 41 kg |
| Standard | IEC 60947-3 |
The ABB 1SDA073413R1 is an Emax 2 E2.2H/MS 2000 three-pole switch disconnector with fixed installation and horizontal rear terminals, designed for high-current low-voltage switching and isolation.
The E2.2H/MS 2000 has a rated uninterrupted current of 2000 A and is rated for operation at up to 690 V AC.
The 1SDA073413R1 is a switch disconnector. It is based on the Emax 2 platform but is intended for switching and isolation rather than providing the integral overcurrent protection of an air circuit breaker equipped with an electronic trip unit.
The E2.2H/MS 2000 has a rated short-time withstand current of 85 kA for 1 s and 66 kA for 3 s.
The F designation identifies the fixed installation configuration, while HR identifies the horizontal rear terminal arrangement used to connect the device within the switchboard.
ABB SACE Emax 2 switch disconnectors combine high continuous-current capability, strong short-time withstand performance and flexible switchboard integration for demanding industrial, commercial and infrastructure power distribution systems.