1SDA073401R1 ABB E1.2N/MS 1600 3p F F Switch-Disconnector

1SDA073401R1 ABB E1.2N/MS 1600 3p F F Switch-Disconnector

ABB 1SDA073401R1 E1.2N/MS 1600 is a 1600 A three-pole fixed SACE Emax 2 switch-disconnector with front terminals for reliable switching and isolation in demanding low-voltage power distribution systems.

SKU: 1SDA073401R1MPN: 1SDA073401R1
Price
List Price £5,028.35 ex VAT
Your Price (ex VAT) Save 25%
£3,771.26 25% OFF
You save £1,257.09 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £3,771.26
Trade pricing is personalised to your account

Manufacturer Lead Time

£3,771.26

Why Choose the ABB E1.2N/MS 1600 3p F F Switch-Disconnector?

The ABB E1.2N/MS 1600 3p F F, order code 1SDA073401R1, is a 1600 A three-pole fixed switch-disconnector from the ABB SACE Emax 2 range, designed for reliable isolation and switching in demanding low-voltage power distribution systems.

Unlike an Emax 2 circuit breaker fitted with an Ekip protection trip unit, the E1.2N/MS is a switch-disconnector configuration intended primarily for switching and isolation rather than automatic overcurrent protection. This makes it suitable for installations where circuit protection is provided by separate upstream or downstream protective devices.

The unit features a compact E1.2 frame, 1600 A rated uninterrupted current, three-pole construction and a fixed installation arrangement with front terminals. Its N performance configuration provides a rated short-time withstand current of 50 kA for 1 s, supporting dependable operation in high-current distribution assemblies.

Key Advantages

  • High-capacity 1600 A switch-disconnector for low-voltage power distribution.
  • Provides dependable switching and circuit isolation.
  • Three-pole configuration for three-phase AC systems.
  • Compact ABB SACE Emax 2 E1.2 frame.
  • 50 kA short-time withstand current for 1 s.
  • 36 kA short-time withstand current for 3 s.
  • Fixed construction simplifies permanent switchboard installation.
  • Front terminals provide a practical main-circuit connection arrangement.

Key Features

  • ABB SACE Emax 2 E1.2N/MS series.
  • 1600 A rated uninterrupted current.
  • Three-pole configuration.
  • Switch-disconnector functionality without an integrated protection trip unit.
  • 690 V AC rated operational voltage.
  • 50 kA Icw for 1 s.
  • 36 kA Icw for 3 s.
  • Fixed mounting arrangement.
  • Front main-circuit terminals.
  • Compact 210 × 296 × 183 mm dimensions.
  • Approximately 14 kg net weight.

Reliable High-Current Switching and Isolation

The ABB SACE Emax 2 E1.2N/MS platform provides switch-disconnector functionality in the same compact architecture used throughout the Emax 2 family. Its 1600 A current rating and substantial short-time withstand capability make it suitable for high-current switchboards where dependable isolation and switching are required.

Because this MS configuration is a switch-disconnector rather than an automatically tripping protective circuit breaker, overcurrent and fault protection should be provided by suitable external protective devices within the electrical system. The fixed construction and front terminals make the unit particularly appropriate for permanent switchboard installations.

Typical Applications

  • Low-voltage main distribution switchboards.
  • High-current circuit isolation and switching.
  • Industrial power distribution systems.
  • Commercial and infrastructure electrical installations.
  • Switchboards using separate overcurrent protection devices.
  • Power distribution systems requiring fixed front-connected switching devices.

Technical Specifications

Series SACE Emax 2
Order code 1SDA073401R1
GTIN / EAN 8015644772512
Product type Switch-disconnector
Frame E1.2
Performance level N
Rated uninterrupted current (Iu) 1600 A
Number of poles 3
Rated operational voltage 690 V AC
Rated short-time withstand current (Icw), 1 s 50 kA
Rated short-time withstand current (Icw), 3 s 36 kA
Mounting Fixed
Terminal arrangement Front terminals
Product net width 210 mm
Product net height 296 mm
Product net depth 183 mm
Product net weight 14 kg
Current type AC

Frequently Asked Questions

What is the ABB 1SDA073401R1?

The ABB 1SDA073401R1 is a 1600 A three-pole fixed SACE Emax 2 switch-disconnector designed for switching and isolation in low-voltage power distribution systems.

What is the rated current of the ABB E1.2N/MS 1600?

The E1.2N/MS 1600 has a rated uninterrupted current of 1600 A.

Does the ABB E1.2N/MS 1600 provide automatic overcurrent protection?

No. The E1.2N/MS is a switch-disconnector configuration intended for switching and isolation, so suitable circuit protection must be provided elsewhere in the electrical system.

What is the short-time withstand current of the E1.2N/MS 1600?

The unit has a rated short-time withstand current of 50 kA for 1 s and 36 kA for 3 s.

Is the ABB 1SDA073401R1 fixed or withdrawable?

The ABB 1SDA073401R1 is a fixed switch-disconnector with front terminals for the main-circuit connections.

Trusted Switching for Low-Voltage Distribution