ABB 1SDA073378R1 E6.2V/f 6300 Ekip Hi-Touch LSI 4p WMP is a 6300 A four-pole full-size withdrawable Emax 2 air circuit breaker moving part with advanced long-time, short-time and instantaneous electronic protection for high-fault-level low-voltage power distribution systems.
£57,094.89
The ABB E6.2V/f 6300 Ekip Hi-Touch LSI 4p WMP, order code 1SDA073378R1, is a high-performance four-pole withdrawable air circuit breaker moving part from the ABB SACE Emax 2 range. Designed for very high-current low-voltage distribution systems, it combines a rated uninterrupted current of 6300 A with the advanced Ekip Hi-Touch LSI electronic trip unit for long-time overload, short-time selective short-circuit and instantaneous short-circuit protection.
The E6.2V/f full-size platform is engineered for critical switchboards requiring exceptionally high fault-clearing performance. Its V performance level provides a rated ultimate short-circuit breaking capacity of 150 kA at 440 V AC, while a rated short-time withstand current of 100 kA for 1 s supports selective coordination in complex industrial and infrastructure power networks.
The Ekip Hi-Touch release provides advanced protection, measurement and monitoring functionality through an intuitive interface, giving operators greater visibility and control over critical electrical systems. The withdrawable moving-part architecture enables the breaker to be used with the appropriate ABB Emax 2 fixed part, supporting efficient inspection, servicing and replacement where continuity of service is important.
The ABB Emax 2 E6.2V/f platform is designed for electrical systems where exceptionally high continuous current and fault-clearing performance are required. Combining a 6300 A current rating, 150 kA ultimate short-circuit breaking capacity at 440 V AC and 100 kA short-time withstand capability, this breaker is particularly suited to main incomers, transformer secondary circuits, bus couplers and other critical high-current circuits.
The Ekip Hi-Touch LSI electronic release combines adjustable long-time overload, short-time selective and instantaneous short-circuit protection with advanced monitoring functionality. Together with the Emax 2 withdrawable architecture, this provides a powerful protection solution for installations where electrical selectivity, system visibility, high availability and maintainability are key requirements.
| Series | SACE Emax 2 |
|---|---|
| Product group | Emax2 Air Circuit Breaker |
| Frame / type | E6.2V/f |
| Order code / MPN | 1SDA073378R1 |
| EAN / GTIN | 8015644772284 |
| Product type | Air circuit breaker moving part |
| Construction | Full-size, withdrawable |
| Rated uninterrupted current (Iu) | 6300 A |
| Number of poles | 4P |
| Neutral configuration | Full-size neutral |
| Current type | AC |
| Trip unit | Ekip Hi-Touch LSI |
| Release type | Solid-state electronic |
| Protection functions | L (long-time), S (short-time), I (instantaneous) |
| Overload release setting range | 2520–6300 A |
| Short-time delayed short-circuit setting range | 3780–63000 A |
| Instantaneous short-circuit setting range | 9450–94500 A |
| Rated voltage | 690 V AC |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 150 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 150 kA |
| Rated short-time withstand current (Icw), 1 s | 100 kA |
| Short-circuit performance level | V |
| Integrated earth-fault protection | No |
| Auxiliary contacts | 4 change-over contacts |
| Circuit breaker indication | Open/closed position |
| Integrated motor drive | No |
| Optional motor drive | Yes |
| Main circuit connection | Connection via separate fixed chassis part |
| Installation | Withdrawable |
| Configuration | Moving part (WMP) |
The ABB 1SDA073378R1 is a 6300 A four-pole Emax 2 air circuit breaker moving part designed for protection, switching and isolation in very high-current, high-fault-level low-voltage electrical distribution systems.
The Ekip Hi-Touch LSI electronic trip unit provides long-time overload (L), short-time selective short-circuit (S) and instantaneous short-circuit (I) protection, together with advanced monitoring and measurement functionality.
The E6.2V/f 6300 provides a rated ultimate short-circuit breaking capacity of 150 kA at 400 V AC and 440 V AC, making it suitable for demanding installations with very high prospective fault currents.
No. The Ekip Hi-Touch LSI release provides long-time, short-time and instantaneous overcurrent protection. An LSIG-equipped Emax 2 version should be selected where integrated earth-fault protection is required.
Yes. The 1SDA073378R1 is the moving part of a withdrawable ABB Emax 2 air circuit breaker and is designed for use with the appropriate compatible Emax 2 fixed part.
ABB SACE Emax 2 air circuit breakers combine very high current capability, advanced electronic protection, exceptional short-circuit performance and maintainable withdrawable architecture for demanding industrial, commercial and critical low-voltage power distribution applications.