Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA073374R1 Emax 2 E6.2V/f 6300 is a 6300 A four-pole withdrawable air circuit breaker moving part with Ekip Touch LI electronic overload and instantaneous short-circuit protection.
£53,820.64
The ABB E6.2V/f 6300 Ekip Touch LI 4p WMP, order code 1SDA073374R1, is a high-current SACE Emax 2 withdrawable air circuit breaker moving part engineered for protection and switching in demanding low-voltage power-distribution systems. Part of the ABB Emax 2 E6.2 full-size range, this four-pole breaker combines a 6300 A rated uninterrupted current, V-level short-circuit performance and an Ekip Touch LI electronic protection release.
The integrated Ekip Touch LI trip unit provides long-time overload (L) and instantaneous short-circuit (I) protection. Its touchscreen-based interface supports convenient protection configuration and access to operating information, making the breaker well suited to high-current installations requiring straightforward overload and instantaneous fault protection together with the capabilities of ABB's Ekip Touch platform.
The E6.2V/f 6300 delivers an ultimate short-circuit breaking capacity of 150 kA at 400/415/440 V AC, 130 kA at 500/525 V AC and 100 kA at 690 V AC. It also provides a rated short-time withstand current of 100 kA for both 1 s and 3 s. Its withdrawable moving-part construction is designed for use with the corresponding Emax 2 fixed part, supporting efficient isolation, inspection and maintenance in critical high-current switchboards.
Air circuit breakers such as the ABB Emax 2 E6.2V/f protect major low-voltage distribution circuits against overload and severe short-circuit conditions. The Ekip Touch LI release combines long-time overload protection with instantaneous short-circuit protection, providing a straightforward protection arrangement for high-current circuits where selective short-time or integrated earth-fault functions are not required.
The combination of a 6300 A continuous-current rating, 150 kA breaking capacity at 400/415/440 V AC and 100 kA short-time withstand capability makes the 1SDA073374R1 suitable for major switchboards with substantial prospective fault currents. Its withdrawable architecture allows the moving breaker assembly to be isolated from the separately installed fixed part, supporting inspection, servicing and maintainability in critical electrical installations.
| Series | SACE Emax 2 E6.2 |
|---|---|
| ABB order code | 1SDA073374R1 |
| Product type | Air circuit breaker moving part |
| Frame configuration | E6.2V/f full size |
| Performance level | V |
| Rated uninterrupted current (Iu) | 6300 A |
| Number of poles | 4 |
| Current type | AC |
| Trip unit | Ekip Touch LI |
| Release type | Electronic |
| Protection functions | Long-time and instantaneous (LI) |
| Rated operational voltage | 690 V AC |
| Ultimate breaking capacity (Icu) at 400 V AC | 150 kA |
| Ultimate breaking capacity (Icu) at 415 V AC | 150 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 150 kA |
| Ultimate breaking capacity (Icu) at 500 V AC | 130 kA |
| Ultimate breaking capacity (Icu) at 525 V AC | 130 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 100 kA |
| Service breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw), 1 s | 100 kA |
| Rated short-time withstand current (Icw), 3 s | 100 kA |
| Installation | Withdrawable |
| Construction | Moving part (WMP) |
| Fixed part | Ordered separately |
| Suitable for IT networks | Yes, up to 690 V |
| Product weight | 148 kg |
| Applicable standard | IEC 60947 |
The ABB 1SDA073374R1 is an Emax 2 E6.2V/f full-size withdrawable air circuit breaker moving part rated at 6300 A, with four poles and an Ekip Touch LI electronic protection release.
The Ekip Touch LI provides long-time overload (L) and instantaneous short-circuit (I) protection, providing protection against sustained overcurrent and severe short-circuit faults.
The E6.2V/f 6300 provides an ultimate short-circuit breaking capacity of 150 kA at 400/415/440 V AC, 130 kA at 500/525 V AC and 100 kA at 690 V AC.
No. This configuration uses an Ekip Touch LI release providing long-time overload and instantaneous short-circuit protection. Ekip Touch LSIG configurations are available within the E6.2 range where integrated earth-fault protection is required.
It is a withdrawable moving part (WMP) designed for use with the corresponding ABB SACE Emax 2 fixed part, supporting convenient isolation, inspection and maintenance.
ABB SACE Emax 2 air circuit breakers combine high-current switching, configurable electronic protection and maintainable withdrawable construction to provide dependable protection for demanding low-voltage power-distribution systems.