Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA073335R1 E6.2H/f 5000 Ekip Touch LSI 4p WMP is a 5000 A four-pole withdrawable Emax 2 air circuit breaker moving part with Ekip Touch long-time, short-time and instantaneous electronic protection for demanding low-voltage power distribution systems.
£34,730.53
The ABB E6.2H/f 5000 Ekip Touch LSI 4p WMP, order code 1SDA073335R1, is a high-performance four-pole withdrawable air circuit breaker moving part from the ABB SACE Emax 2 range. Designed for demanding high-current low-voltage distribution systems, it combines a rated current of 5000 A with an advanced Ekip Touch LSI electronic trip unit for long-time overload, short-time selective short-circuit and instantaneous short-circuit protection.
The E6.2H/f full-size platform is engineered for major switchboards where high current capacity, fault-clearing performance and protection selectivity are essential. Its Ekip Touch release provides a colour touchscreen interface for intuitive configuration and access to operating information, while optional communication capabilities allow integration into modern power-management and automation architectures.
With a rated operational voltage of 690 V AC, rated insulation voltage of 1000 V AC and rated impulse withstand voltage of 12 kV, the breaker is designed for robust industrial service. The H performance level provides a rated ultimate and service short-circuit breaking capacity of 100 kA across key operating voltages, together with a rated short-time withstand current of 100 kA for 1 s and 3 s.
Air circuit breakers such as the ABB Emax 2 E6.2H/f provide switching, isolation and protection for major low-voltage electrical distribution systems. The combination of a 5000 A current rating, 100 kA short-circuit breaking capacity and 100 kA short-time withstand capability makes this breaker well suited to main incomers, transformer secondary circuits, bus couplers and major feeders in high-power switchboards.
The Ekip Touch LSI trip unit adds adjustable short-time protection to long-time overload and instantaneous short-circuit protection, supporting selective coordination with downstream protective devices. Its touchscreen interface provides convenient access to protection parameters and operating information, while the withdrawable Emax 2 architecture supports maintainability in critical installations where continuity of service is important.
| Series | SACE Emax 2 |
|---|---|
| Frame / type | E6.2H/f |
| Order code / MPN | 1SDA073335R1 |
| EAN / GTIN | 8015644771850 |
| Product type | Air circuit breaker moving part |
| Construction | Full-size |
| Rated current (In) | 5000 A |
| Rated uninterrupted current (Iu) | 5000 A |
| Number of poles | 4P |
| Current type | AC |
| Trip unit | Ekip Touch LSI |
| Release type | Electronic |
| Protection functions | L (long-time), S (short-time), I (instantaneous) |
| Rated operational voltage (Ue) | 690 V AC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu), 400–690 V AC | 100 kA |
| Rated service short-circuit breaking capacity (Ics), 220–690 V AC | 100 kA |
| Ics as percentage of Icu | 100% |
| Rated short-time withstand current (Icw), 1 s | 100 kA |
| Rated short-time withstand current (Icw), 3 s | 100 kA |
| Short-circuit performance level | H |
| Neutral pole current | 100% of Iu |
| Mechanical durability | 12,000 operating cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Electrical durability at up to 440 V AC | 3,000 operating cycles |
| Electrical durability at 500–690 V AC | 2,000 operating cycles |
| Electrical operating frequency | 10 cycles per hour |
| Power loss | 850 W |
| Installation | Withdrawable |
| Configuration | Moving part (WMP) |
| Standard | IEC 60947-2 |
| Product net weight | 148 kg |
The ABB 1SDA073335R1 is a 5000 A four-pole Emax 2 air circuit breaker moving part designed for protection, switching and isolation in demanding high-current low-voltage electrical distribution systems.
The Ekip Touch LSI electronic trip unit provides long-time overload (L), short-time selective short-circuit (S) and instantaneous short-circuit (I) protection.
The E6.2H/f 5000 provides a rated ultimate short-circuit breaking capacity of 100 kA at operating voltages from 400–690 V AC, with a rated service short-circuit breaking capacity equal to 100% of Icu.
The four-pole 1SDA073335R1 has a neutral pole current rating of 100% of Iu, corresponding to the breaker's 5000 A rated uninterrupted current.
Yes. The 1SDA073335R1 is the moving part of a withdrawable ABB Emax 2 air circuit breaker and is designed for use with the appropriate compatible Emax 2 fixed part.
ABB SACE Emax 2 air circuit breakers combine high current capability, advanced electronic protection, strong short-circuit performance and a maintainable withdrawable architecture for demanding industrial, commercial and critical low-voltage power distribution applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.