Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA073272R1 E6.2H 6300 Ekip Dip LSI 4p WMP is a 6300 A four-pole withdrawable Emax 2 air circuit breaker moving part with long-time, short-time and instantaneous electronic protection for high-current low-voltage distribution systems.
£41,586.01
The ABB E6.2H 6300 Ekip Dip LSI 4p WMP, order code 1SDA073272R1, is a high-performance four-pole air circuit breaker moving part from the ABB SACE Emax 2 range, designed for protection, switching and isolation in high-current low-voltage electrical distribution systems. With a rated current of 6300 A and an Ekip Dip LSI electronic trip unit, it provides long-time overload, short-time selective short-circuit and instantaneous short-circuit protection for demanding industrial, commercial and infrastructure installations.
As part of the ABB Emax 2 E6.2H series, this breaker combines very high current capability with robust short-circuit performance and a withdrawable architecture. The moving-part configuration is designed for use with the appropriate Emax 2 fixed part, supporting efficient inspection, servicing and replacement in critical switchboards where maintainability and continuity of operation are important.
The E6.2H 6300 has a rated uninterrupted current of 6300 A, a 690 V AC rated operational voltage and a 1000 V AC rated insulation voltage. Its H performance class provides a rated ultimate and service short-circuit breaking capacity of 100 kA across key industrial voltages, together with a 100 kA short-time withstand current for 1 s and 3 s.
Air circuit breakers such as the ABB Emax 2 E6.2H provide switching, isolation and electrical protection for high-current low-voltage distribution systems. The combination of a 6300 A current rating, 100 kA breaking capacity and high short-time withstand capability makes this breaker particularly suitable for main incomers, transformer secondary circuits, bus couplers and major outgoing feeders in large switchboards.
The Ekip Dip LSI electronic trip unit adds short-time protection to the long-time and instantaneous functions, allowing improved selectivity and coordination with downstream circuit breakers. Adjustable protection thresholds enable the breaker to be configured around the requirements of the electrical installation, helping isolate faults while maintaining supply to unaffected parts of the distribution network where the protection scheme permits.
| Series | SACE Emax 2 |
|---|---|
| Frame / type | E6.2H |
| Order code / MPN | 1SDA073272R1 |
| EAN | 8015644771225 |
| Product type | Air circuit breaker moving part |
| Rated current (In) | 6300 A |
| Rated uninterrupted current (Iu) | 6300 A |
| Number of poles | 4P |
| Current type | AC |
| Trip unit | Ekip Dip LSI |
| Release type | Electronic |
| Protection functions | L (long-time), S (short-time), I (instantaneous) |
| Overload release setting range | 2520–6300 A |
| Short-time short-circuit release setting range | 3780–63000 A |
| Instantaneous short-circuit release setting range | 9450–94500 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu), 400–690 V AC | 100 kA |
| Rated service short-circuit breaking capacity (Ics), 220–690 V AC | 100 kA |
| Ics as percentage of Icu | 100% |
| Rated short-time withstand current (Icw), 1 s | 100 kA |
| Rated short-time withstand current (Icw), 3 s | 100 kA |
| Short-circuit performance level | H |
| Neutral pole current | 50% of Iu |
| Mechanical durability | 12,000 operating cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Electrical durability | 2,000 operating cycles |
| Electrical operating frequency | 10 cycles per hour |
| Power loss | 1550 W |
| Connecting capacity | 6000 mm² |
| Auxiliary contacts | 4 change-over contacts |
| Motor drive | Optional |
| Integrated earth-fault protection | No |
| Suitable for IT networks | Yes, up to 690 V |
| Installation | Withdrawable |
| Configuration | Moving part (WMP) |
| Standard | IEC 60947-2 |
| Product net weight | 134 kg |
The ABB 1SDA073272R1 is a 6300 A four-pole Emax 2 air circuit breaker moving part designed for protection, switching and isolation in high-current low-voltage electrical distribution systems.
The circuit breaker has a rated current of 6300 A, making it suitable for very high-current industrial, commercial and infrastructure power distribution applications.
The Ekip Dip LSI electronic trip unit provides long-time overload (L), short-time selective short-circuit (S) and instantaneous short-circuit (I) protection.
The E6.2H version provides a rated ultimate short-circuit breaking capacity of 100 kA at key operating voltages up to 690 V AC, with its rated service short-circuit breaking capacity equal to 100% of Icu.
Yes. The 1SDA073272R1 is the moving part of a withdrawable ABB Emax 2 air circuit breaker and is designed for use with the appropriate compatible Emax 2 fixed part.
ABB SACE Emax 2 air circuit breakers combine high current capability, configurable electronic protection and a maintainable withdrawable architecture for demanding industrial, commercial and critical low-voltage power distribution applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.