ABB 1SDA073250R1 E6.2H 5000 Ekip G Hi-Touch LSIG 4p WMP is a 5000 A four-pole withdrawable SACE Emax 2 air circuit breaker moving part with generator-specific LSIG protection, Ekip Measuring Pro, Network Analyzer functionality and 100 kA breaking capacity at 380–690 V AC.
£35,095.94
The ABB E6.2H 5000 Ekip G Hi-Touch LSIG 4p WMP, order code 1SDA073250R1, is a high-performance four-pole air circuit breaker (ACB) from the ABB SACE Emax 2 range, specifically configured for generator protection and demanding high-current low-voltage power distribution systems. Rated at 5000 A, this withdrawable moving part combines the E6.2 frame, ABB's H short-circuit performance level and the advanced Ekip G Hi-Touch LSIG electronic trip unit.
The Ekip G Hi-Touch LSIG release provides long-time overload (L), short-time selective short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection. The long-time protection is adjustable from 2000–5000 A, short-time protection from 3000–50000 A and instantaneous protection from 7500–75000 A. Generator-specific protection is complemented by Ekip Measuring Pro and integrated Network Analyzer functionality for advanced electrical measurement and power-quality supervision.
The E6.2H 5000 has a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 100 kA across the principal 380–690 V AC operating voltages. Its rated short-time withstand current is 100 kA for 1 s, while the four-pole withdrawable construction allows the moving part to be used with the corresponding fixed chassis for maintainable high-capacity switchboard installations.
Generator circuits can present different fault characteristics and operating requirements from conventional utility-fed distribution systems. The Ekip G Hi-Touch LSIG release is specifically oriented towards generator applications, combining adjustable overload, selective short-circuit, instantaneous short-circuit and earth-fault protection with generator-specific functions and advanced electrical measurement.
Combined with the E6.2H platform's 5000 A continuous-current capability, 100 kA short-circuit breaking performance and 100 kA 1-second short-time withstand current, this configuration provides a robust solution for generator incomers, generation switchboards and critical high-current distribution systems. Ekip Measuring Pro and Network Analyzer functionality further support detailed supervision of electrical quantities and network performance.
| Series | SACE Emax 2 |
|---|---|
| Product group | Emax2 Air Circuit Breaker |
| Order code / SKU | 1SDA073250R1 |
| Product type | Air circuit breaker moving part |
| Frame | E6.2 |
| Short-circuit performance level | H |
| Installation | Withdrawable moving part |
| Current type | AC |
| Rated uninterrupted current (Iu) | 5000 A |
| Number of poles | 4 |
| Trip unit | Ekip G Hi-Touch LSIG |
| Trip-unit type | Electronic |
| Protection functions | L, S, I, G |
| Overload protection adjustment range | 2000–5000 A |
| Short-time delayed short-circuit adjustment range | 3000–50000 A |
| Instantaneous short-circuit adjustment range | 7500–75000 A |
| Integrated earth-fault protection | Yes |
| Generator-specific protection | Yes |
| Measurement | Ekip Measuring Pro |
| Network analysis | Integrated Network Analyzer |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50/60 Hz |
| Ultimate short-circuit breaking capacity (Icu) at 380 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 100 kA |
| Rated short-time withstand current (Icw) | 100 kA for 1 s |
| Main-circuit connection | Connection at separate chassis part |
| Auxiliary contacts | 4 change-over contacts |
| Open/closed position indication | Yes |
| Control element | Push button |
| Motor drive | Optional |
| Degree of protection | IP30 |
| Product net weight | 134 kg |
| Standard | IEC 60947-2 |
The ABB 1SDA073250R1 is a 5000 A four-pole withdrawable air circuit breaker moving part specifically configured for generator protection and demanding high-current low-voltage power distribution systems.
The circuit breaker is fitted with an Ekip G Hi-Touch LSIG electronic trip unit, providing long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection together with generator-specific protection functions.
The ABB E6.2H 5000 has a rated uninterrupted current of 5000 A, with its long-time overload protection adjustable from 2000–5000 A.
The E6.2H 5000 provides an ultimate short-circuit breaking capacity of 100 kA at 380, 400/415, 440, 500/525 and 690 V AC, together with a rated short-time withstand current of 100 kA for 1 s.
Yes. The Ekip G Hi-Touch LSIG release provides generator-specific protection together with LSIG protection, Ekip Measuring Pro and Network Analyzer functionality, making the breaker specifically suited to generator and critical-power applications.
ABB SACE Emax 2 air circuit breakers combine very high continuous-current capability, strong short-circuit performance and advanced generator-oriented electronic protection for dependable control, monitoring and protection of generation, industrial and critical low-voltage power systems.