ABB 1SDA073222R1 is a four-pole SACE Emax 2 E6.2V 4000 A withdrawable air circuit breaker moving part with an Ekip Dip LSI electronic trip unit and up to 150 kA short-circuit breaking capacity for selective protection in demanding low-voltage power distribution systems.
£31,374.57
The ABB E6.2V 4000 Ekip Dip LSI 4p WMP, order code 1SDA073222R1, is a high-performance SACE Emax 2 air circuit breaker designed for protection and switching in demanding low-voltage electrical distribution systems. This four-pole withdrawable moving part combines a rated current of 4000 A with ABB's Ekip Dip LSI electronic trip unit.
The Ekip Dip LSI release provides long-time, short-time and instantaneous protection, helping protect electrical installations against sustained overloads and short-circuit faults. Protection settings are configured using DIP switches, providing straightforward adjustment for applications requiring selective short-circuit protection without integrated earth-fault protection.
The E6.2V is the high-breaking-capacity V performance version of the Emax 2 E6.2 platform, providing an ultimate short-circuit breaking capacity of 150 kA at 400/415–440 V AC, 130 kA at 500/525 V AC and 100 kA at 690 V AC. Its four-pole withdrawable construction and high fault-current performance make it particularly suitable for major industrial, infrastructure and critical power-distribution switchboards.
ABB SACE Emax 2 E6.2 air circuit breakers are engineered for major low-voltage installations requiring high continuous-current capability and exceptional short-circuit performance. The E6.2V 4000 combines a substantial 4000 A current rating with 150 kA ultimate short-circuit breaking capacity at 400/415–440 V AC and 100 kA at 690 V AC, making it well suited to networks with very high prospective fault currents.
The Ekip Dip LSI electronic trip unit combines long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. Adjustable ranges of 1600–4000 A for overload protection, 2400–40000 A for short-time protection and 6000–60000 A for instantaneous protection provide flexibility for coordinating the breaker with other protective devices in the installation.
| Series | SACE Emax 2 E6.2 |
|---|---|
| Order code / MPN | 1SDA073222R1 |
| Product type | Air circuit breaker moving part |
| Rated current (In) | 4000 A |
| Rated uninterrupted current (Iu) | 4000 A |
| Number of poles | 4 |
| Neutral pole current | 50% |
| Performance level | V |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Frequency | 50/60 Hz |
| Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 150 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 150 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 130 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 100 kA |
| Release unit | Ekip Dip |
| Release type | Electronic |
| Protection functions | LSI |
| Long-time protection | Adjustable overload protection |
| Short-time protection | Adjustable selective short-circuit protection |
| Instantaneous protection | Adjustable instantaneous short-circuit protection |
| Integrated earth-fault protection | No |
| Overload protection setting range | 1600–4000 A |
| Short-time delayed short-circuit setting range | 2400–40000 A |
| Instantaneous short-circuit setting range | 6000–60000 A |
| Protection adjustment | DIP switches |
| Configuration | Withdrawable moving part |
| Main circuit connection | Connection at separate chassis part |
| Auxiliary change-over contacts | 4 |
| Switched-off indication | Yes |
| Control element | Push button |
| Complete device with protection unit | Yes |
| Integrated undervoltage release | No |
| Motor drive integrated | No |
| Motor drive optional | Yes |
| Protection rating | IP30 |
| Power loss | 544 W |
| Electrical durability at ≤440 V | 4000 cycles |
| Electrical durability at 500–690 V | 4000 cycles |
| Mechanical durability | 12000 cycles |
| Dimensions (W × H × D) | 929 × 425 × 383 mm |
| Weight | approx. 134 kg |
| GTIN / EAN | 8015644770716 |
| Standard | IEC 60947-2 |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA073222R1 is a SACE Emax 2 E6.2V air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution systems, particularly installations requiring selective protection and very high short-circuit breaking performance.
The ABB E6.2V 4000 has a rated current of 4000 A, making it suitable for high-current main distribution, industrial, infrastructure and critical power applications.
The Ekip Dip LSI electronic trip unit provides long-time, short-time and instantaneous protection. It protects against sustained overloads and both delayed and high-level short-circuit faults, while this LSI configuration does not include integrated earth-fault protection.
The E6.2V 4000 provides an ultimate short-circuit breaking capacity of 150 kA at 400/415–440 V AC, 130 kA at 500/525 V AC and 100 kA at 690 V AC.
This model is supplied as a four-pole withdrawable moving part with its main circuit connection through a separate compatible ABB SACE Emax 2 chassis part, allowing the breaker to be isolated and withdrawn for inspection or maintenance.
ABB SACE Emax 2 air circuit breakers combine high-current switching, configurable electronic protection and exceptional short-circuit performance for demanding industrial, commercial, infrastructure and critical power-distribution systems.
We use cookies