ABB 1SDA073205R1 is a SACE Emax 2 E4.2V 4000 A four-pole withdrawable air circuit breaker moving part with an Ekip Touch LSI electronic trip unit providing long-time, short-time and instantaneous protection for demanding low-voltage power-distribution systems.
£29,146.76
The ABB 1SDA073205R1 is a high-performance SACE Emax 2 E4.2V air circuit breaker moving part engineered for protection and switching in demanding low-voltage power-distribution systems. This four-pole withdrawable unit is rated at 4000 A and incorporates an Ekip Touch LSI solid-state electronic trip unit, providing long-time overload, short-time selective short-circuit and instantaneous short-circuit protection.
The Ekip Touch release combines configurable electronic protection with an intuitive touch interface, allowing protection parameters and operating information to be accessed directly from the trip unit. The LSI protection profile is particularly suitable for distribution systems requiring coordinated overload and short-circuit protection without integrated ground-fault protection.
The E4.2V performance level provides exceptional fault-interruption capability, with an ultimate short-circuit breaking capacity of 150 kA at 440 V AC and a rated short-time withstand current of 100 kA for 1 s. Combined with its 4000 A rating and withdrawable architecture, this makes the breaker suitable for major incomers and high-current feeders in installations with very high prospective fault levels.
Air circuit breakers such as the ABB SACE Emax 2 protect major low-voltage distribution circuits against damaging overloads and short circuits while providing dependable high-current switching and isolation. The Ekip Touch LSI release combines long-time overload protection, short-time delayed protection for selective coordination and instantaneous protection against severe short circuits.
The E4.2V platform is designed for installations with exceptionally high prospective fault currents. Its combination of a 4000 A current rating, 150 kA Icu at 440 V AC and 100 kA Icw for 1 s provides substantial interruption and withstand capability, while the withdrawable architecture allows the moving part to be removed from its corresponding fixed chassis for inspection, maintenance or replacement.
| Series | SACE Emax 2 |
|---|---|
| ABB order code | 1SDA073205R1 |
| EAN | 8015644770556 |
| Product type | Air circuit breaker moving part |
| Frame | E4.2 |
| Performance level | V |
| Rated uninterrupted current (Iu) | 4000 A |
| Rated voltage | 690 V AC |
| Number of poles | 4 |
| Current type | AC |
| Trip unit | Ekip Touch LSI |
| Release type | Solid-state electronic |
| Protection functions | Long-time, short-time and instantaneous |
| Overload release adjustment range | 1600–4000 A |
| Short-time delayed short-circuit adjustment range | 2400–40000 A |
| Instantaneous short-circuit adjustment range | 6000–60000 A |
| Integrated ground-fault protection | No |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 150 kA |
| Rated short-time withstand current (Icw) for 1 s | 100 kA |
| Construction | Withdrawable / moving part |
| Main-circuit connection | Connection through separate chassis part |
| Auxiliary contacts | 4 change-over contacts |
| Circuit-breaker indication | Open / closed |
| Control element | Push button |
| Integrated motor drive | No |
| Optional motor drive | Yes |
| Degree of protection | IP30 |
The ABB 1SDA073205R1 is a SACE Emax 2 E4.2V four-pole withdrawable air circuit breaker moving part rated at 4000 A and equipped with an Ekip Touch LSI solid-state electronic trip unit.
The ABB 1SDA073205R1 has a rated uninterrupted current of 4000 A.
The Ekip Touch LSI release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.
The E4.2V 4000 has a rated ultimate short-circuit breaking capacity of 150 kA at 440 V AC, making it suitable for installations with very high prospective fault levels.
The E4.2V frame has a rated short-time withstand current of 100 kA for 1 s.
No. The LSI configuration provides long-time, short-time and instantaneous protection. Integrated ground-fault protection is provided by LSIG configurations.
The overload release is adjustable from 1600–4000 A, the short-time delayed release from 2400–40000 A, and the instantaneous short-circuit release from 6000–60000 A.
The 1SDA073205R1 is the withdrawable moving part of the circuit breaker and connects to the main circuit through the corresponding separate ABB SACE Emax 2 fixed chassis part.
ABB SACE Emax 2 air circuit breakers are engineered for demanding industrial, commercial and infrastructure power-distribution systems, combining high short-circuit performance, advanced electronic protection and service-friendly modular construction.