ABB 1SDA073185R1 E4.2S 4000 Ekip Touch LSI 4p WMP is a 4000 A four-pole withdrawable SACE Emax 2 air circuit breaker moving part with Ekip Touch LSI electronic protection and 85 kA breaking capacity at 400/415 V AC.
£24,659.25
The ABB E4.2S 4000 Ekip Touch LSI 4p WMP, order code 1SDA073185R1, is a high-current four-pole air circuit breaker moving part from the ABB SACE Emax 2 range. Rated at 4000 A, it is designed for protection and switching in demanding low-voltage industrial, commercial, infrastructure and critical-power distribution systems.
This E4.2S breaker incorporates an advanced Ekip Touch LSI solid-state electronic trip unit, providing long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection. Protection settings are accessible through the touchscreen interface, with adjustable long-time, selective short-time and instantaneous thresholds supporting effective coordination within complex electrical distribution networks.
The S performance level provides a rated ultimate short-circuit breaking capacity of 85 kA at 400/415 V AC, remaining at 85 kA at 440 V AC and reducing to 66 kA at 500/525 V AC and 690 V AC. Its WMP configuration is the moving part of a withdrawable Emax 2 breaker system, providing a service-friendly solution for high-current switchboards.
The ABB E4.2S 4000 combines high-current switching capability with the advanced configuration interface of the Ekip Touch LSI electronic release. Long-time protection responds to sustained overload conditions, short-time protection provides a configurable delayed response that supports selective coordination, and instantaneous protection rapidly disconnects severe short-circuit faults.
With a 4000 A current rating, 85 kA breaking capacity at 400/415 V AC and a rated operational voltage up to 690 V AC, the E4.2S is well suited to demanding main-distribution and high-current feeder applications. Its withdrawable architecture allows the moving breaker portion to be removed from its compatible fixed part for inspection or servicing, supporting maintainability in critical switchboards.
| Series | SACE Emax 2 |
|---|---|
| ABB order code | 1SDA073185R1 |
| Product group | Emax2 Air Circuit Breaker |
| EAN / GTIN | 8015644770358 |
| Product type | Air circuit breaker moving part |
| Frame | E4.2 |
| Performance level | S |
| Rated current (In) | 4000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Frequency | 50 / 60 Hz |
| Icu at 380 V AC | 85 kA |
| Icu at 400/415 V AC | 85 kA |
| Icu at 440 V AC | 85 kA |
| Icu at 500/525 V AC | 66 kA |
| Icu at 690 V AC | 66 kA |
| Number of poles | 4 |
| Neutral pole current | 100% of Iu |
| Current type | AC |
| Trip unit | Ekip Touch LSI |
| Release type | Solid-state electronic |
| Protection functions | Long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) |
| Overload protection adjustment | 0.4–1 × In / 1600–4000 A |
| Short-time protection adjustment | 0.6–10 × In / 2400–40,000 A |
| Instantaneous protection adjustment | 1.5–15 × In / 6000–60,000 A |
| Protection interface | Touchscreen display |
| Integrated earth-fault protection | No |
| Construction | Withdrawable / draw-out moving part |
| Auxiliary contacts | 4 |
| Breaker position indication | Open / closed |
| Electrical durability | 5000 cycles at Ue ≤ 440 V; 4000 cycles at 500–690 V |
| Mechanical durability | 15,000 cycles |
| Power loss | 900 W |
| Dimensions (W × H × D) | 551 × 425 × 383 mm |
| Product net weight | 64 kg |
| Standard | IEC 60947-2 |
The ABB 1SDA073185R1 is a 4000 A four-pole SACE Emax 2 air circuit breaker moving part designed for switching and selective protection in demanding high-current low-voltage power distribution systems.
It is fitted with an Ekip Touch LSI solid-state electronic trip unit, providing adjustable long-time overload, short-time short-circuit and instantaneous short-circuit protection through a touchscreen interface.
The E4.2S 4000 has a rated ultimate short-circuit breaking capacity of 85 kA at 400/415 V AC. Its Icu is also 85 kA at 380 V and 440 V AC, and 66 kA at 500/525 V and 690 V AC.
The long-time overload protection is adjustable from 0.4–1 × In, the selective short-time protection from 0.6–10 × In, and the instantaneous short-circuit protection from 1.5–15 × In.
Yes. The 1SDA073185R1 is the moving part of a withdrawable Emax 2 air circuit breaker and is designed to operate with a compatible fixed part, supporting efficient inspection, servicing and replacement.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, intuitive touchscreen configuration and service-friendly withdrawable construction for dependable high-current power distribution in demanding industrial, commercial and infrastructure installations.