Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA073154R1 E4.2V 3200 Ekip Touch LI 4p WMP is a 3200 A four-pole withdrawable SACE Emax 2 air circuit breaker moving part with adjustable Ekip Touch LI electronic protection and 150 kA breaking capacity at 380–440 V AC.
£21,078.07
The ABB E4.2V 3200 Ekip Touch LI 4p WMP, order code 1SDA073154R1, is a high-performance four-pole air circuit breaker (ACB) from the ABB SACE Emax 2 range, designed for protection and switching in demanding low-voltage power distribution systems. Rated at 3200 A, this withdrawable moving part combines the E4.2 frame with ABB's V short-circuit performance level and an advanced Ekip Touch LI electronic trip unit.
The Ekip Touch LI release provides long-time overload (L) and instantaneous short-circuit (I) protection. Long-time protection is adjustable from 0.4–1 × In, while instantaneous protection is adjustable from 1.5–15 × In. A touch-sensitive display provides an intuitive interface for configuring protection settings and accessing operating information.
With a rated operational voltage of 690 V AC, rated insulation voltage of 1000 V AC and an ultimate short-circuit breaking capacity of 150 kA at 380–440 V AC, the E4.2V 3200 is engineered for networks with very high prospective fault currents. Its four-pole withdrawable moving-part construction supports efficient inspection, servicing and replacement when installed with the corresponding ABB SACE Emax 2 fixed chassis.
Air circuit breakers such as the ABB SACE Emax 2 provide switching, isolation and protection for high-current low-voltage electrical networks. The E4.2V platform combines a substantial 3200 A continuous-current rating with very high short-circuit breaking performance, making it suitable for main distribution systems where prospective fault currents demand robust circuit protection.
The Ekip Touch LI trip unit provides adjustable long-time overload and instantaneous short-circuit protection through an intuitive touch-sensitive interface. Combined with the E4.2V platform's 150 kA breaking capability at 380–440 V AC, this configuration is well suited to high-current feeders, transformer circuits and main distribution applications in appropriately engineered electrical networks.
| Series | SACE Emax 2 |
|---|---|
| Product group | Emax2 Air Circuit Breaker |
| Order code / SKU | 1SDA073154R1 |
| Product type | Air circuit breaker moving part |
| Frame | E4.2 |
| Short-circuit performance level | V |
| Rated current | 3200 A |
| Rated uninterrupted current (Iu) | 3200 A |
| Number of poles | 4 |
| Trip unit | Ekip Touch LI |
| Trip-unit type | Electronic |
| Protection functions | L, I |
| Overload protection setting | 0.4–1 × In |
| Overload protection adjustment range | 1280–3200 A |
| Instantaneous protection setting | 1.5–15 × In |
| Instantaneous short-circuit adjustment range | 4800–48000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50 / 60 Hz |
| Ultimate short-circuit breaking capacity (Icu) at 380 V AC | 150 kA |
| Ultimate short-circuit breaking capacity (Icu) at 400 / 415 V AC | 150 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 150 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 / 525 V AC | 100 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 100 kA |
| Short-time withstand current (Icw) | 100 kA for 1 s |
| Installation | Withdrawable |
| Construction | Moving part for separate fixed chassis |
| Interface | Touch-sensitive display |
| Standard | IEC 60947-2 |
The ABB 1SDA073154R1 is a 3200 A four-pole withdrawable air circuit breaker moving part designed for switching and protection of high-current low-voltage power distribution systems.
The circuit breaker is fitted with an Ekip Touch LI electronic trip unit, providing adjustable long-time overload and instantaneous short-circuit protection through a touch-sensitive interface.
The E4.2V 3200 has a rated current of 3200 A, with long-time overload protection adjustable from 1280–3200 A.
The E4.2V 3200 provides an ultimate short-circuit breaking capacity of 150 kA at 380–440 V AC and 100 kA at 500–690 V AC.