1SDA073138R1 ABB E4.2S 3200 Ekip Hi-Touch LSI 4p WMP Air Circuit Breaker 3200 A

1SDA073138R1 ABB E4.2S 3200 Ekip Hi-Touch LSI 4p WMP Air Circuit Breaker 3200 A

ABB 1SDA073138R1 E4.2S 3200 Ekip Hi-Touch LSI 4p WMP is a 3200 A four-pole withdrawable SACE Emax 2 air circuit breaker moving part with Ekip Hi-Touch LSI electronic protection and 85 kA breaking capacity at 400/415 V AC.

SKU: 1SDA073138R1MPN: 1SDA073138R1
Price
List Price £25,999.19 ex VAT
Your Price (ex VAT) Save 25%
£19,499.39 25% OFF
You save £6,499.80 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £19,499.39
Trade pricing is personalised to your account

Manufacturer Lead Time

£19,499.39

Why Choose the ABB E4.2S 3200 Ekip Hi-Touch LSI 4p WMP Air Circuit Breaker?

The ABB E4.2S 3200 Ekip Hi-Touch LSI 4p WMP, order code 1SDA073138R1, is a high-current four-pole air circuit breaker moving part from the ABB SACE Emax 2 range. Rated at 3200 A, it is designed for protection and switching in demanding low-voltage industrial, commercial, infrastructure and critical-power distribution systems.

This E4.2S breaker is equipped with an advanced Ekip Hi-Touch LSI solid-state electronic trip unit, providing long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection. The Hi-Touch platform extends the capabilities of ABB's electronic protection system with advanced measurement, monitoring and power-quality functionality, while the LSI protection configuration supports selective coordination throughout complex distribution networks.

The S performance level provides a rated ultimate short-circuit breaking capacity of 85 kA at 400/415 V AC and 66 kA at 690 V AC. The WMP configuration is the moving part of a withdrawable Emax 2 breaker system and is supplied with four auxiliary contacts plus breaker open/closed position indication, providing a service-friendly solution for high-availability switchboards.

Key Advantages

  • High-current 3200 A ABB SACE Emax 2 air circuit breaker.
  • Four-pole (4P) configuration for demanding low-voltage distribution systems.
  • 85 kA ultimate short-circuit breaking capacity at 400/415 V AC.
  • Advanced Ekip Hi-Touch LSI electronic trip unit.
  • Provides long-time, short-time and instantaneous overcurrent protection.
  • Short-time protection supports selective coordination between upstream and downstream devices.
  • Advanced Hi-Touch functionality supports detailed electrical measurement, monitoring and power-quality analysis.
  • Withdrawable moving-part construction supports efficient inspection, servicing and replacement.

Key Features

  • ABB SACE Emax 2 E4.2 frame.
  • E4.2S short-circuit performance level.
  • 3200 A rated uninterrupted current.
  • Four-pole (4P) configuration.
  • Ekip Hi-Touch LSI solid-state electronic release.
  • Long-time overload (L) protection.
  • Short-time short-circuit (S) protection.
  • Instantaneous short-circuit (I) protection.
  • Overload release adjustment from 1280–3200 A.
  • Short-time delayed short-circuit adjustment from 1920–32,000 A.
  • Instantaneous short-circuit adjustment from 4800–48,000 A.
  • 85 kA Icu at 400/415 V AC.
  • 66 kA Icu at 690 V AC.
  • Four auxiliary change-over contacts.
  • Breaker open/closed position indication.
  • IP30 degree of protection.

Advanced Hi-Touch Protection for High-Current Distribution

The ABB E4.2S 3200 combines high-current switching capability with the advanced functionality of the Ekip Hi-Touch electronic release. Its LSI protection functions provide coordinated response to sustained overloads, short-time faults and severe instantaneous short circuits, making the breaker suitable for distribution systems where selectivity and continuity of supply are important.

With an 85 kA breaking capacity at 400/415 V AC, a 3200 A current rating and withdrawable construction, the E4.2S provides a robust solution for demanding switchboards. The Hi-Touch platform adds sophisticated monitoring and measurement capabilities, while the moving-part architecture allows the breaker to be withdrawn from its compatible fixed part for inspection, servicing or replacement.

Typical Applications

  • Main incoming protection for high-current low-voltage switchboards.
  • Industrial power distribution systems.
  • High-current feeder and distribution protection.
  • Manufacturing and process plants.
  • Large commercial building electrical distribution.
  • Data centres and critical infrastructure.
  • Utility and infrastructure distribution systems.
  • Generator and transformer distribution switchboards.

Technical Specifications

Series SACE Emax 2
ABB order code 1SDA073138R1
Product group Emax2 Air Circuit Breaker
EAN 8015644769888
Product type Air circuit breaker moving part
Frame E4.2
Performance level S
Rated uninterrupted current (Iu) 3200 A
Rated voltage 690 V AC
Number of poles 4
Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC 85 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 66 kA
Trip unit Ekip Hi-Touch LSI
Release type Solid-state electronic
Protection functions Long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I)
Overload release adjustment range 1280–3200 A
Short-time delayed short-circuit adjustment range 1920–32,000 A
Instantaneous short-circuit adjustment range 4800–48,000 A
Integrated earth-fault protection No
Construction Withdrawable / draw-out moving part
Main-circuit connection Connection at separate chassis part
Control element Push button
Auxiliary change-over contacts 4
Open/closed position indication Yes
Optional motor drive Yes
Degree of protection IP30

Frequently Asked Questions

What is the ABB 1SDA073138R1 used for?

The ABB 1SDA073138R1 is a 3200 A four-pole SACE Emax 2 air circuit breaker moving part designed for switching and advanced protection in high-current low-voltage power distribution systems.

What protection unit is fitted to the ABB E4.2S 3200 1SDA073138R1?

It is fitted with an Ekip Hi-Touch LSI solid-state electronic trip unit, providing long-time overload, short-time short-circuit and instantaneous short-circuit protection together with advanced monitoring and measurement capabilities.

What is the breaking capacity of the ABB E4.2S 3200?

The E4.2S 3200 has a rated ultimate short-circuit breaking capacity of 85 kA at 400/415 V AC and 66 kA at 690 V AC.

What protection adjustment ranges are available on the Ekip Hi-Touch LSI release?

The overload release is adjustable from 1280–3200 A, the short-time delayed short-circuit release from 1920–32,000 A, and the instantaneous short-circuit release from 4800–48,000 A.

Is the ABB E4.2S 3200 Ekip Hi-Touch LSI 4p WMP withdrawable?

Yes. The 1SDA073138R1 is the moving part of a withdrawable Emax 2 air circuit breaker and connects through a compatible separate chassis part, supporting convenient inspection, servicing and replacement.

Trusted Advanced Protection from ABB SACE Emax 2

ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, sophisticated monitoring capabilities and service-friendly withdrawable construction for dependable high-current power distribution in demanding industrial, commercial and infrastructure installations.