1SDA073135R1 ABB E4.2S 3200 Ekip Touch LSI 4p WMP Air Circuit Breaker

1SDA073135R1 ABB E4.2S 3200 Ekip Touch LSI 4p WMP Air Circuit Breaker

ABB 1SDA073135R1 E4.2S 3200 Ekip Touch LSI 4p WMP is a 3200 A four-pole SACE Emax 2 withdrawable air circuit breaker moving part with Ekip Touch LSI electronic protection and an 85 kA ultimate breaking capacity at 400/415/440 V AC.

SKU: 1SDA073135R1MPN: 1SDA073135R1
Price
List Price £22,666.44 ex VAT
Your Price (ex VAT) Save 25%
£16,999.83 25% OFF
You save £5,666.61 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £16,999.83
Trade pricing is personalised to your account

Manufacturer Lead Time

£16,999.83

Why Choose the ABB E4.2S 3200 Ekip Touch LSI 4p WMP Air Circuit Breaker?

The ABB E4.2S 3200 Ekip Touch LSI 4p WMP, order code 1SDA073135R1, is a high-performance four-pole air circuit breaker moving part designed for protection, control and monitoring in demanding low-voltage power distribution systems. As part of the advanced ABB SACE Emax 2 series, it combines a 3200 A rated uninterrupted current with the intelligent Ekip Touch LSI electronic trip unit.

The Ekip Touch LSI release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. Its touch-sensitive display enables straightforward configuration of protection parameters, while adjustable electronic protection supports effective selectivity and coordination throughout industrial, commercial and infrastructure electrical networks.

This E4.2S configuration features a 3200 A rated uninterrupted current, four-pole construction and a rated operational voltage up to 690 V AC. The S performance level provides an ultimate short-circuit breaking capacity of 85 kA at 400/415/440 V AC and 66 kA at 500–690 V AC, while the withdrawable moving-part construction supports efficient inspection and maintenance.

Key Advantages

  • High-performance ABB SACE Emax 2 air circuit breaker for demanding power distribution systems.
  • 3200 A rated uninterrupted current for high-current electrical installations.
  • Four-pole configuration with a 100% rated neutral pole.
  • Advanced Ekip Touch LSI electronic trip unit with touch-sensitive interface.
  • LSI protection covers overload, selective short-circuit and instantaneous short-circuit conditions.
  • 85 kA ultimate short-circuit breaking capacity at 400/415/440 V AC.
  • 66 kA rated short-time withstand current for 1 s.
  • Withdrawable moving-part design supports convenient maintenance and switchboard servicing.

Key Features

  • ABB SACE Emax 2 E4.2S frame.
  • 3200 A rated uninterrupted current.
  • Four-pole construction.
  • Ekip Touch LSI electronic protection release.
  • Long-time overload protection (L).
  • Short-time selective short-circuit protection (S).
  • Instantaneous short-circuit protection (I).
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 85 kA Icu at 400/415/440 V AC.
  • Withdrawable moving part for compatible Emax 2 switchgear installations.

Advanced LSI Protection for High-Current Distribution

The ABB Ekip Touch LSI electronic trip unit provides adjustable protection against overload and both delayed and instantaneous short-circuit conditions. Long-time protection safeguards conductors and equipment against sustained overcurrent, while short-time and instantaneous functions enable coordinated interruption of higher fault currents within the distribution network.

The E4.2S frame is engineered for high-current installations requiring dependable fault interruption, selectivity and continuity of service. Its combination of 85 kA breaking capacity at 400/415/440 V AC, 66 kA short-time withstand capability and withdrawable construction makes it well suited to maintainable industrial and infrastructure switchboards.

Typical Applications

  • High-current industrial power distribution switchboards.
  • Main incoming and outgoing feeder protection.
  • Transformer secondary distribution systems.
  • Manufacturing and process industry installations.
  • Data centres and critical power infrastructure.
  • Commercial buildings and large infrastructure projects.
  • Utility and energy distribution installations.
  • Low-voltage networks requiring selective electronic short-circuit protection.

Technical Specifications

Series SACE Emax 2
Order code 1SDA073135R1
Product type Air circuit breaker moving part
Frame E4.2S
Short-circuit performance level S
Rated uninterrupted current (Iu) 3200 A
Rated current (In) 3200 A
Number of poles 4
Neutral pole current 100% of Iu
Trip unit Ekip Touch LSI
Release type Electronic
Protection functions L, S, I
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Frequency 50 / 60 Hz
Ultimate short-circuit breaking capacity (Icu) at 400/415/440 V AC 85 kA
Ultimate short-circuit breaking capacity (Icu) at 500/525/690 V AC 66 kA
Service short-circuit breaking capacity (Ics) 100% of Icu
Rated short-time withstand current (Icw), 1 s 66 kA
Rated short-time withstand current (Icw), 3 s 66 kA
Overload protection adjustment range 1280–3200 A
Short-time protection adjustment range 1920–32000 A
Instantaneous protection adjustment range 4800–48000 A
Installation Withdrawable moving part
Main circuit connection Connection through separate fixed part
Power loss 743 W
Mechanical endurance 20,000 cycles
Electrical endurance 7,000 cycles
Dimensions (W × H × D) 551 × 425 × 383 mm
Net weight 74 kg
Standard IEC 60947-2
EAN 8015644769857

Frequently Asked Questions

What is the ABB 1SDA073135R1?

The ABB 1SDA073135R1 is an E4.2S 3200 Ekip Touch LSI four-pole withdrawable air circuit breaker moving part from the SACE Emax 2 range.

What is the rated current of the E4.2S 3200 Ekip Touch LSI?

The breaker has a rated uninterrupted current of 3200 A, with an adjustable overload protection range of 1280–3200 A.

What protection functions does the Ekip Touch LSI provide?

The Ekip Touch LSI provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection.

What is the breaking capacity of the ABB E4.2S 3200?

The E4.2S 3200 provides an ultimate short-circuit breaking capacity of 85 kA at 400/415/440 V AC and 66 kA at 500–690 V AC.

Is the ABB 1SDA073135R1 a withdrawable circuit breaker?

Yes. The 1SDA073135R1 is a withdrawable moving part designed for installation with the appropriate compatible SACE Emax 2 fixed part.

Trusted for High-Current Power Distribution

ABB SACE Emax 2 air circuit breakers combine high-current switching capability, advanced electronic protection and maintainable withdrawable construction to provide dependable protection and control for demanding industrial and infrastructure power distribution systems.