ABB 1SDA073062R1 is a SACE Emax 2 E2.2H 2500 A four-pole withdrawable air circuit breaker moving part with an Ekip Dip LSI electronic trip unit providing long-time, short-time and instantaneous protection for demanding low-voltage power distribution systems.
£13,097.04
The ABB 1SDA073062R1 is a high-performance SACE Emax 2 E2.2H air circuit breaker moving part designed for protection and switching in demanding low-voltage power distribution systems. This four-pole withdrawable unit has a rated uninterrupted current of 2500 A and incorporates an Ekip Dip LSI solid-state electronic trip unit providing long-time overload, short-time short-circuit and instantaneous short-circuit protection.
As part of the ABB SACE Emax 2 range, the E2.2H combines high short-circuit performance with configurable electronic protection and service-friendly withdrawable construction. The Ekip Dip LSI release provides adjustable protection through straightforward DIP-switch settings, while its short-time protection function supports selective coordination between upstream and downstream protective devices.
With a rated operational voltage of 690 V AC, an ultimate short-circuit breaking capacity of 100 kA at 400/415 V AC and a rated short-time withstand current of 85 kA for 1 s, the E2.2H 2500 provides robust protection for high-current distribution networks. Its four-pole configuration and withdrawable design make it suitable for industrial, commercial and infrastructure switchboards requiring high fault-interruption capability and maintainability.
Air circuit breakers such as the ABB SACE Emax 2 protect low-voltage distribution systems against damaging overloads and short circuits while providing dependable high-current switching and isolation. The Ekip Dip LSI release combines long-time overload protection with short-time delayed and instantaneous short-circuit protection, enabling coordinated protection across complex electrical distribution networks.
The E2.2H platform is engineered for installations with demanding prospective fault levels. Its 100 kA breaking capacity at 400/415 V AC and 85 kA short-time withstand capability for 1 s support robust and selective system protection, while the withdrawable architecture allows the moving part to be removed from the corresponding fixed section for maintenance or replacement.
| Series | SACE Emax 2 |
|---|---|
| ABB order code | 1SDA073062R1 |
| Product type | Air circuit breaker moving part |
| Frame | E2.2 |
| Performance level | H |
| Rated uninterrupted current (Iu) | 2500 A |
| Rated current (In) | 2500 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 4 |
| Current type | AC |
| Trip unit | Ekip Dip LSI |
| Release type | Solid-state electronic |
| Protection functions | Long-time, short-time and instantaneous |
| Rated ultimate short-circuit breaking capacity (Icu) | 100 kA at 400 V AC |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw) | 85 kA for 1 s |
| Construction | Withdrawable / moving part |
| Auxiliary contacts | 4 |
| Circuit-breaker position indication | Open / closed |
| EAN | 8015644769123 |
| Standard | IEC 60947-2 |
The ABB 1SDA073062R1 is a SACE Emax 2 E2.2H four-pole withdrawable air circuit breaker moving part rated at 2500 A and fitted with an Ekip Dip LSI solid-state electronic trip unit.
The circuit breaker has a rated uninterrupted current of 2500 A and a rated operational voltage of 690 V AC.
The Ekip Dip LSI release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.
The E2.2H 2500 has a rated ultimate short-circuit breaking capacity of 100 kA at 400/415 V AC and 85 kA at 690 V AC.
The breaker has a rated short-time withstand current of 85 kA for 1 s and 66 kA for 3 s, supporting selective coordination in high-current distribution systems.
No. The Ekip Dip LSI configuration provides long-time, short-time and instantaneous overcurrent protection; integrated ground-fault protection is associated with LSIG configurations.
The 1SDA073062R1 is the withdrawable moving part of the circuit breaker and is intended for use with the corresponding ABB SACE Emax 2 fixed part.
ABB SACE Emax 2 air circuit breakers are engineered for demanding industrial, commercial and infrastructure power-distribution systems, combining high short-circuit performance, configurable electronic protection and service-friendly modular construction.