ABB 1SDA073055R1 is a four-pole SACE Emax 2 E2.2S 2500 A withdrawable air circuit breaker with an Ekip Touch LSI electronic trip unit for advanced low-voltage power distribution protection.
£12,512.36
The ABB E2.2S 2500 Ekip Touch LSI 4p WMP, order code 1SDA073055R1, is a high-performance SACE Emax 2 air circuit breaker designed for protection, switching and control in demanding low-voltage electrical distribution systems. As part of the advanced ABB Emax 2 E2.2 series, this four-pole withdrawable circuit breaker combines a rated current of 2500 A with the intelligent Ekip Touch LSI solid-state electronic trip unit.
The Ekip Touch LSI release provides comprehensive long-time, short-time and instantaneous protection, protecting electrical installations against overload and short-circuit conditions. Its electronic protection platform offers adjustable protection settings for effective coordination with other protective devices, making the breaker suitable for sophisticated industrial, commercial and infrastructure power-distribution systems.
With a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 85 kA at 400 V AC, the E2.2S 2500 is engineered for demanding high-current installations. Its withdrawable moving-part construction facilitates isolation and maintenance, while the four-pole configuration and fitted auxiliary contacts support integration into modern low-voltage switchgear assemblies.
ABB SACE Emax 2 air circuit breakers are engineered to protect low-voltage electrical installations against overloads and short circuits while providing dependable switching for high-current distribution systems. The E2.2 platform combines robust interruption performance with intelligent electronic protection, making it suitable for installations where continuity of service, selective coordination and accurate fault protection are essential.
The Ekip Touch LSI trip unit provides configurable long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. This flexibility allows protection characteristics to be matched to the electrical installation and coordinated with upstream and downstream protective devices, helping isolate faults while maintaining reliable operation throughout the wider distribution system.
| Series | SACE Emax 2 E2.2 |
|---|---|
| Order code / MPN | 1SDA073055R1 |
| Product type | Air circuit breaker |
| Rated current | 2500 A |
| Number of poles | 4 |
| Rated operational voltage | 690 V AC |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 85 kA |
| Short-time withstand current (Icw), 1 s | 66 kA |
| Release unit | Ekip Touch |
| Protection functions | LSI |
| Long-time protection | Overload protection |
| Short-time protection | Short-circuit protection with time delay |
| Instantaneous protection | Instantaneous short-circuit protection |
| Overload release setting range | 1000–2500 A |
| Short-time delayed short-circuit setting range | 1500–25000 A |
| Instantaneous short-circuit setting range | 3750–37500 A |
| Configuration | Withdrawable moving part |
| Auxiliary contacts | 4 change-over contacts |
| Circuit-breaker position indication | Open / closed |
| Main circuit connection | Connection through separate fixed part |
| Motor drive integrated | No |
| Motor drive optional | Yes |
| Protection rating | IP30 |
| Dimensions (H × W × D) | 425 × 407 × 383 mm |
| Weight | 55 kg |
| EAN | 8015644769055 |
The ABB 1SDA073055R1 is a SACE Emax 2 air circuit breaker designed for switching and protecting high-current low-voltage electrical distribution systems in industrial, commercial and infrastructure applications.
The E2.2S 2500 has a rated current of 2500 A, with adjustable long-time overload protection from 1000–2500 A.
The Ekip Touch LSI release provides long-time, short-time and instantaneous protection, protecting electrical circuits against overload and short-circuit conditions.
The E2.2S 2500 provides an ultimate short-circuit breaking capacity of 85 kA at 400 V AC and a short-time withstand current of 66 kA for 1 s.
This model is supplied as a withdrawable moving part for a compatible ABB SACE Emax 2 fixed part, facilitating circuit isolation, inspection and maintenance within the switchgear assembly.
ABB SACE Emax 2 air circuit breakers combine high-current switching, intelligent electronic protection and flexible power-management capabilities for dependable operation in demanding industrial, commercial and infrastructure electrical distribution systems.
We use cookies