Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA073048R1 is a four-pole SACE Emax 2 E2.2N 2500 A withdrawable air circuit breaker with an Ekip Hi-Touch LSI electronic trip unit for advanced low-voltage power distribution protection, measurement and monitoring.
£13,608.68
The ABB E2.2N 2500 Ekip Hi-Touch LSI 4p WMP, order code 1SDA073048R1, is a high-performance SACE Emax 2 air circuit breaker designed for protection, switching and control in demanding low-voltage electrical distribution systems. As part of the advanced ABB Emax 2 E2.2 series, this four-pole withdrawable circuit breaker combines a rated current of 2500 A with the advanced Ekip Hi-Touch LSI electronic trip unit.
The Ekip Hi-Touch LSI release provides comprehensive long-time, short-time and instantaneous protection against overload and short-circuit conditions. It also incorporates advanced measurement capabilities, including Ekip Measuring Pro and Network Analyzer functionality, making it well suited to modern power-distribution systems where accurate protection, monitoring and electrical network analysis are required.
With a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 66 kA across key industrial voltages, the E2.2N 2500 provides robust protection for high-current installations. Its withdrawable moving-part construction facilitates isolation and maintenance, while the breaker is supplied with four auxiliary change-over contacts and open/closed position indication for integration into switchgear control systems.
ABB SACE Emax 2 air circuit breakers are engineered to protect low-voltage electrical installations against overloads and short circuits while providing dependable switching for high-current distribution systems. The E2.2 platform combines robust interruption performance with intelligent electronic protection, making it suitable for installations where continuity of service, selective coordination and accurate fault protection are essential.
The Ekip Hi-Touch trip unit extends these capabilities with sophisticated protection, measurement and network-analysis functionality. Its LSI functions allow long-time overload, short-time delayed short-circuit and instantaneous short-circuit characteristics to be configured around the requirements of the installation, while integrated measurement capabilities provide valuable electrical data for monitoring and power-management applications.
| Series | SACE Emax 2 E2.2 |
|---|---|
| Order code / MPN | 1SDA073048R1 |
| Product type | Air circuit breaker |
| Rated current | 2500 A |
| Number of poles | 4 |
| Neutral pole current | 100% |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V AC |
| Rated impulse withstand voltage | 12 kV |
| Frequency | 50 / 60 Hz |
| Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Release unit | Ekip Hi-Touch |
| Protection functions | LSI |
| Overload release setting range | 1000–2500 A |
| Short-time delayed short-circuit setting range | 1500–25000 A |
| Instantaneous short-circuit setting range | 3750–37500 A |
| Configuration | Withdrawable moving part |
| Auxiliary contacts | 4 change-over contacts |
| Circuit-breaker position indication | Open / closed |
| Main circuit connection | Connection at separate fixed part |
| Motor drive integrated | No |
| Motor drive optional | Yes |
| Standard | IEC 60947-2 |
| Dimensions (H × W × D) | 425 × 407 × 383 mm |
| Weight | 55 kg |
| EAN | 8015644768980 |
The ABB 1SDA073048R1 is a SACE Emax 2 air circuit breaker designed for switching and protecting high-current low-voltage electrical distribution systems, including transformer, generator, industrial and general installation applications.
The E2.2N 2500 has a rated current of 2500 A, with adjustable long-time overload protection from 1000–2500 A.
The Ekip Hi-Touch LSI release provides long-time, short-time and instantaneous protection, protecting electrical circuits against overload and short-circuit conditions.
The E2.2N 2500 provides an ultimate short-circuit breaking capacity of 66 kA at 400/415 V AC, with the same 66 kA Icu rating specified at 440 V AC, 500/525 V AC and 690 V AC.
This model is supplied as a withdrawable moving part for a compatible ABB SACE Emax 2 fixed part, facilitating circuit isolation, inspection and maintenance within the switchgear assembly.
ABB SACE Emax 2 air circuit breakers combine high-current switching, advanced electronic protection, measurement and power-management capabilities for dependable operation in demanding industrial, commercial and infrastructure electrical distribution systems.
We use cookies