1SDA073045R1 ABB E2.2N 2500 Ekip Touch LSI 4p WMP Air Circuit Breaker

1SDA073045R1 ABB E2.2N 2500 Ekip Touch LSI 4p WMP Air Circuit Breaker

ABB 1SDA073045R1 SACE Emax 2 E2.2N 2500 A four-pole withdrawable air circuit breaker moving part with Ekip Touch LSI electronic protection for selective high-current low-voltage power distribution.

SKU: 1SDA073045R1MPN: 1SDA073045R1
Price
List Price £14,636.71 ex VAT
Your Price (ex VAT) Save 25%
£10,977.53 25% OFF
You save £3,659.18 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £10,977.53
Trade pricing is personalised to your account

Manufacturer Lead Time

£10,977.53

Why Choose the ABB E2.2N 2500 Ekip Touch LSI 4p WMP Air Circuit Breaker?

The ABB 1SDA073045R1 is a high-current SACE Emax 2 E2.2N air circuit breaker moving part rated at 2500 A, designed for protection, switching and isolation in demanding low-voltage power distribution systems. This four-pole withdrawable model incorporates the Ekip Touch LSI electronic trip unit, providing long-time, short-time and instantaneous protection.

The Ekip Touch platform combines configurable electronic protection with an intuitive touchscreen interface for convenient adjustment and access to electrical information. Its LSI protection functions support selective coordination between upstream and downstream devices, making the breaker well suited to main incomers, high-current feeders and other critical distribution circuits.

With a rated uninterrupted current of 2500 A, a four-pole configuration and rated operational voltage of 690 V AC, the E2.2N provides an ultimate short-circuit breaking capacity of 66 kA at 400 V AC. The withdrawable moving-part design connects to a separate chassis part and facilitates inspection, maintenance and replacement in serviceable switchboard installations.

Key Advantages

  • High-current ABB SACE Emax 2 E2.2N air circuit breaker for demanding low-voltage networks.
  • 2500 A rated uninterrupted current for substantial industrial and commercial loads.
  • Four-pole configuration for three-phase distribution systems requiring neutral switching.
  • Ekip Touch LSI electronic trip unit provides long-time, short-time and instantaneous protection.
  • 66 kA ultimate breaking capacity at 400 V AC for robust short-circuit protection.
  • Withdrawable moving-part construction supports efficient inspection, servicing and breaker replacement.

Key Features

  • ABB SACE Emax 2 E2.2N frame.
  • 2500 A rated current.
  • 4-pole configuration.
  • Ekip Touch LSI solid-state electronic protection release.
  • Long-time, short-time and instantaneous protection functions.
  • Overload protection adjustable from 1000–2500 A.
  • Short-time delayed short-circuit protection adjustable from 1500–25000 A.
  • Instantaneous short-circuit protection adjustable from 3750–37500 A.
  • Four change-over auxiliary contacts.
  • Breaker open/closed position indication.

Advanced Touchscreen LSI Protection for High-Current Distribution

The Ekip Touch LSI release provides adjustable long-time protection against sustained overload conditions, short-time protection for selective fault coordination and instantaneous protection against severe short circuits. These functions allow protection settings to be coordinated throughout the distribution network, helping isolate faults close to their source while maintaining service to unaffected circuits.

Combined with the 2500 A E2.2N frame and touchscreen-based Ekip Touch interface, the 1SDA073045R1 provides a flexible solution for high-current distribution systems requiring configurable electronic protection and straightforward system supervision. Its withdrawable construction further supports maintainability and reduced switchboard downtime.

Typical Applications

  • Main low-voltage switchboards and distribution boards.
  • Industrial power distribution systems.
  • Manufacturing plants and process facilities.
  • Large commercial buildings and infrastructure installations.
  • Transformer secondary and main incoming protection.
  • High-current feeders requiring selective overload and short-circuit protection.

Technical Specifications

Series SACE Emax 2
ABB order code 1SDA073045R1
EAN 8015644768959
Product type Air circuit breaker moving part
Frame E2.2N
Rated uninterrupted current 2500 A
Number of poles 4
Current type AC
Trip unit Ekip Touch LSI
Release type Solid-state electronic
Protection functions Long-time (L), short-time (S), instantaneous (I)
Overload release adjustment 1000–2500 A
Short-time delayed short-circuit adjustment 1500–25000 A
Instantaneous short-circuit adjustment 3750–37500 A
Rated operational voltage 690 V AC
Ultimate breaking capacity (Icu) at 400 V AC 66 kA
Installation Withdrawable
Configuration Moving part
Main-circuit connection Connection at separate chassis part
Auxiliary contacts 4 change-over contacts
Breaker open/closed indication Yes
Integrated ground-fault protection No
Degree of protection IP30
Motor drive Optional
Power loss 550 W
Electrical durability 8,000 cycles at Ue ≤ 440 V; 7,000 cycles at 500–690 V
Mechanical durability 20,000 cycles
Dimensions (W × H × D) 407 × 425 × 383 mm
Product net weight 64 kg
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA073045R1 used for?

The ABB 1SDA073045R1 is a 2500 A four-pole air circuit breaker moving part designed for protection, switching and isolation of high-current low-voltage power distribution systems.

What protection unit is fitted to the ABB 1SDA073045R1?

The breaker incorporates an Ekip Touch LSI electronic trip unit, providing adjustable long-time, short-time and instantaneous protection through an intuitive touchscreen interface.

What is the breaking capacity of the E2.2N 2500?

The E2.2N 2500 provides an ultimate short-circuit breaking capacity of 66 kA at 400 V AC, supporting dependable protection in demanding high-current distribution systems.

Does the ABB 1SDA073045R1 provide ground-fault protection?

No. This model uses the Ekip Touch LSI release, which provides long-time, short-time and instantaneous protection. Emax 2 variants fitted with LSIG releases add integrated ground-fault protection.

Is the ABB 1SDA073045R1 fixed or withdrawable?

The 1SDA073045R1 is a withdrawable moving part for the SACE Emax 2 E2.2N platform and connects to a corresponding separate chassis part, allowing convenient removal for inspection, servicing or replacement.

Trusted Power Protection from ABB

ABB SACE Emax 2 air circuit breakers combine high-current switching capability, advanced electronic protection and maintainable withdrawable construction for dependable modern low-voltage power distribution systems.