ABB 1SDA073044R1 E2.2N 2500 Ekip Touch LI 4p WMP is a 2500 A four-pole withdrawable SACE Emax 2 air circuit breaker moving part with Ekip Touch LI electronic protection and 66 kA breaking capacity at 400/415 V AC.
£10,641.33
The ABB E2.2N 2500 Ekip Touch LI 4p WMP, order code 1SDA073044R1, is a high-performance four-pole air circuit breaker (ACB) from the ABB SACE Emax 2 range, designed for protection and switching in demanding low-voltage power distribution systems. With a rated current of 2500 A, it provides dependable protection for high-current industrial, commercial and infrastructure installations.
This E2.2N breaker is equipped with the advanced Ekip Touch LI electronic trip unit, providing long-time overload (L) and instantaneous short-circuit (I) protection. The Ekip Touch platform incorporates an intuitive touchscreen interface for protection configuration and monitoring, combining precise electronic protection with straightforward operation for modern electrical distribution systems.
The N performance level provides a rated ultimate short-circuit breaking capacity of 66 kA at 400/415 V AC, while the breaker is rated for operation up to 690 V AC. Its four-pole WMP configuration is the moving part of a withdrawable Emax 2 system, enabling connection through a separate fixed chassis and supporting efficient inspection, servicing and replacement in critical switchboards.
Air circuit breakers such as the ABB E2.2N protect high-current electrical distribution circuits against damaging overload and short-circuit conditions. The Ekip Touch LI release monitors circuit current and provides adjustable long-time and instantaneous protection, enabling the breaker to disconnect the circuit when operating conditions exceed the configured protection thresholds.
The Ekip Touch interface provides an accessible platform for protection configuration and monitoring, while the withdrawable Emax 2 architecture supports efficient switchboard maintenance. The combination of high current capacity, strong short-circuit performance and advanced electronic protection makes this breaker well suited to critical industrial and commercial distribution systems.
| Series | SACE Emax 2 |
|---|---|
| ABB order code | 1SDA073044R1 |
| Product type | Air circuit breaker moving part |
| Frame | E2.2 |
| Performance level | N |
| Rated current | 2500 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Number of poles | 4 |
| Frequency | 50 / 60 Hz |
| Trip unit | Ekip Touch LI |
| Protection functions | Long-time overload (L) and instantaneous short-circuit (I) |
| Overload protection adjustment | 0.4–1 × In |
| Instantaneous protection adjustment | 1.5–15 × In |
| Protection configuration | Touchscreen interface |
| Construction | Withdrawable / draw-out moving part |
| Main-circuit connection | Connection through separate chassis |
| Operating control | Push-button |
| Auxiliary change-over contacts | 4 |
| Open/closed indication | Yes |
| Motor operator | Optional |
| Degree of protection | IP30 |
| Standard | IEC 60947-2 |
| Net weight | 60 kg |
| Power loss | 550 W |
| EAN | 8015644768942 |
The ABB 1SDA073044R1 is a 2500 A four-pole Emax 2 air circuit breaker moving part designed for switching and protection in high-current low-voltage power distribution systems.
It is fitted with an Ekip Touch LI electronic trip unit, providing adjustable long-time overload and instantaneous short-circuit protection.
The E2.2N 2500 has a rated ultimate short-circuit breaking capacity of 66 kA at 400/415 V AC, with 66 kA Icu also specified across several other rated AC operating voltages up to 690 V.
The Ekip Touch LI trip unit provides long-time overload (L) and instantaneous short-circuit (I) protection together with a touchscreen interface for configuring and monitoring the electronic protection functions.
Yes. This WMP version is the withdrawable moving part of the Emax 2 breaker system and connects through a separate chassis, supporting convenient inspection, servicing and replacement.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, high-current switching capability and service-friendly withdrawable construction for dependable low-voltage power distribution in industrial, commercial and infrastructure installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.