Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA073019R1 Emax 2 E2.2N 2000 Ekip Hi-Touch LSIG four-pole withdrawable air circuit breaker moving part rated at 2000 A with advanced LSIG protection, integrated measurement, power-quality monitoring and 66 kA short-circuit breaking capacity.
£11,898.45
The ABB E2.2N 2000 Ekip Hi-Touch LSIG 4p WMP, order code 1SDA073019R1, is a high-performance four-pole withdrawable air circuit breaker moving part from the ABB SACE Emax 2 range. Rated at 2000 A, it combines the E2.2N frame with the advanced Ekip Hi-Touch LSIG electronic trip unit for protection, measurement and supervision of demanding low-voltage power distribution systems.
The Ekip Hi-Touch LSIG release provides adjustable long-time (L), selective short-time (S), instantaneous (I) and earth-fault (G) protection. Its overload protection is adjustable from 0.4–1 × In, selective short-time protection from 0.6–10 × In, instantaneous protection from 1.5–15 × In and earth-fault protection from 0.1–1 × In, providing extensive flexibility for coordinated power-distribution protection.
The E2.2N frame provides an ultimate short-circuit breaking capacity of 66 kA up to 690 V AC. The Hi-Touch release incorporates Ekip Measuring Pro and Network Analyzer functionality for advanced electrical measurement and real-time power-quality supervision, while the withdrawable construction supports efficient inspection, servicing and breaker replacement within compatible Emax 2 switchboards.
The ABB SACE Emax 2 platform is engineered to protect and manage high-current low-voltage electrical distribution systems. The Ekip Hi-Touch LSIG release combines adjustable overload, selective short-time, instantaneous and earth-fault functions, enabling coordinated protection against the principal electrical fault conditions encountered in industrial, commercial and infrastructure networks.
Beyond circuit protection, Ekip Measuring Pro and the integrated Network Analyzer provide advanced electrical measurement and real-time power-quality supervision. Combined with the E2.2N frame's 66 kA breaking performance up to 690 V AC and service-friendly withdrawable construction, the 1SDA073019R1 provides a comprehensive solution where protection, selectivity, monitoring and maintainability are key requirements.
| Series | SACE Emax 2 |
|---|---|
| Order code | 1SDA073019R1 |
| EAN | 8015644768690 |
| Product group | Emax 2 Air Circuit Breaker |
| Product type | Air circuit breaker moving part |
| Frame | E2.2 |
| Performance level | N |
| Rated current | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Number of poles | 4P |
| Current type | AC |
| Installation | Withdrawable, moving part |
| Main-circuit connection | Via separate fixed chassis |
| Trip unit | Ekip Hi-Touch LSIG |
| Release type | Solid-state electronic |
| Protection functions | L, S, I and G |
| Long-time protection setting | 0.4–1 × In |
| Selective short-time protection setting | 0.6–10 × In |
| Instantaneous protection setting | 1.5–15 × In |
| Earth-fault protection setting | 0.1–1 × In |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated frequency | 50 / 60 Hz |
| Icu at 380 V AC | 66 kA |
| Icu at 400 / 415 V AC | 66 kA |
| Icu at 440 V AC | 66 kA |
| Icu at 500 / 525 V AC | 66 kA |
| Icu at 690 V AC | 66 kA |
| Integrated earth-fault protection | Yes |
| Measurement module | Ekip Measuring Pro |
| Power-quality monitoring | Network Analyzer |
| Auxiliary contacts | 4 |
| Breaker position indication | Open / closed |
| Electrical durability | 10,000 cycles at ≤440 V; 8,000 cycles at 500–690 V |
| Maximum electrical operating frequency | 30 cycles per hour |
| Mechanical durability | 25,000 cycles |
| Dimensions (W × H × D) | 407 × 425 × 383 mm |
| Standard | IEC 60947-2 |
The ABB 1SDA073019R1 is an Emax 2 E2.2N four-pole withdrawable air circuit breaker moving part rated at 2000 A and equipped with an Ekip Hi-Touch LSIG electronic trip unit.
The Ekip Hi-Touch LSIG provides long-time overload (L), selective short-time (S), instantaneous short-circuit (I) and earth-fault (G) protection together with advanced electrical measurement and power-quality monitoring.
Long-time protection is adjustable from 0.4–1 × In, selective short-time protection from 0.6–10 × In, instantaneous protection from 1.5–15 × In and earth-fault protection from 0.1–1 × In.
The E2.2N 2000 provides an ultimate short-circuit breaking capacity of 66 kA at 380 V, 400 / 415 V, 440 V, 500 / 525 V and 690 V AC.
Yes. The Ekip Hi-Touch release incorporates Ekip Measuring Pro and Network Analyzer functionality for advanced electrical measurement and real-time power-quality monitoring.
ABB SACE Emax 2 air circuit breakers combine advanced electronic LSIG protection, electrical measurement, power-quality monitoring and service-friendly withdrawable construction for dependable management of demanding low-voltage power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.