ABB 1SDA073018R1 E2.2N 2000 Ekip Hi-Touch LSI 4p WMP is a 2000 A four-pole withdrawable Emax 2 air circuit breaker moving part with advanced LSI protection, Ekip Measuring Pro and Network Analyzer functionality for demanding low-voltage power distribution systems.
£11,430.68
The ABB E2.2N 2000 Ekip Hi-Touch LSI 4p WMP, order code 1SDA073018R1, is a four-pole air circuit breaker (ACB) moving part designed for advanced protection, switching and isolation in high-current low-voltage electrical distribution systems. Part of the ABB SACE Emax 2 series, it combines a 2000 A rated uninterrupted current with the E2.2N short-circuit performance level for demanding industrial, commercial and infrastructure applications.
This Emax 2 circuit breaker is equipped with the Ekip Hi-Touch LSI electronic trip unit, providing long-time overload, short-time selective and instantaneous short-circuit protection. The Hi-Touch platform also integrates Ekip Measuring Pro and Network Analyzer functionality, combining configurable circuit protection with advanced electrical measurement and power-quality monitoring capabilities.
The E2.2N 2000 provides a rated ultimate short-circuit breaking capacity of 66 kA at 400–690 V AC, together with a rated short-time withstand current of 66 kA for 1 s. Its four-pole withdrawable moving-part (WMP) construction is designed for use with the corresponding Emax 2 fixed part, supporting convenient isolation, inspection, servicing and replacement within maintainable switchgear assemblies.
The ABB Emax 2 E2.2N platform provides switching, isolation and advanced electronic protection for high-current low-voltage distribution circuits. With a 2000 A rated uninterrupted current, 66 kA ultimate short-circuit breaking capacity at 400–690 V AC and 66 kA short-time withstand current for 1 s, this model is suited to demanding main switchboards and distribution systems.
The Ekip Hi-Touch LSI trip unit combines long-time overload protection with short-time selective protection and instantaneous short-circuit protection. Integrated Ekip Measuring Pro and Network Analyzer functionality adds advanced electrical measurement and power-quality monitoring capabilities, while the withdrawable Emax 2 architecture supports convenient isolation, maintenance and continuity strategies.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA073018R1 |
| EAN | 8015644768683 |
| Product type | Air circuit breaker moving part |
| Product group | Emax2 Air Circuit Breaker |
| Frame | E2.2 |
| Performance level | N |
| Rated current (In) | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Number of poles | 4 |
| Neutral pole current | 100% Iu |
| Trip unit | Ekip Hi-Touch LSI |
| Release type | Electronic |
| Protection functions | Long-time (L), short-time (S), instantaneous (I) |
| Long-time protection setting | 0.4–1 × In |
| Long-time overload adjustment range | 800–2000 A |
| Short-time protection setting | 0.6–10 × In |
| Instantaneous protection setting | 1.5–15 × In |
| Instantaneous short-circuit adjustment range | 3000–30000 A |
| Integrated earth-fault protection | No |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 525 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw), 1 s | 66 kA |
| Rated short-time withstand current (Icw), 3 s | 50 kA |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Frequency | 50/60 Hz |
| Current type | AC |
| Measurement module | Ekip Measuring Pro |
| Network analysis | Integrated Network Analyzer |
| Interface | Touch-sensitive display |
| Auxiliary changeover contacts | 4 |
| Circuit-breaker position indication | Open/closed |
| Integrated undervoltage release | No |
| Integrated motor drive | No |
| Optional motor drive | Yes |
| Power loss | 450 W |
| Electrical durability at Ue ≤ 440 V | 10,000 cycles |
| Electrical durability at Ue 500–690 V | 8,000 cycles |
| Mechanical durability | 25,000 cycles |
| Degree of protection | IP30 |
| Main circuit connection | Connection at separate chassis part |
| Standard | IEC 60947-2 |
| Execution | Withdrawable |
| Configuration | Moving part of withdrawable circuit breaker (WMP) |
| Product net width | 407 mm |
| Product net height | 425 mm |
| Product net depth | 383 mm |
| Product net weight | 55 kg |
The ABB 1SDA073018R1 is a 2000 A four-pole air circuit breaker moving part used for advanced protection, switching, isolation and electrical monitoring in high-current low-voltage industrial, commercial and infrastructure power distribution systems.
The ABB E2.2N 2000 has a rated uninterrupted current of 2000 A.
The Ekip Hi-Touch LSI electronic trip unit provides long-time overload protection, short-time selective short-circuit protection and instantaneous short-circuit protection, together with advanced measurement and Network Analyzer functionality.
The E2.2N 2000 provides a rated ultimate short-circuit breaking capacity of 66 kA at 400–690 V AC, with a rated short-time withstand current of 66 kA for 1 s and 50 kA for 3 s.
Yes. The 1SDA073018R1 is the four-pole withdrawable moving part (WMP) of an ABB SACE Emax 2 E2.2N 2000 air circuit breaker and is designed for use with the corresponding withdrawable fixed part.
ABB SACE Emax 2 air circuit breakers combine dependable high-current circuit protection with advanced electronic trip, measurement and monitoring technology, while the Ekip Hi-Touch LSI platform provides configurable protection and power-quality analysis for demanding low-voltage electrical distribution systems.