ABB 1SDA073015R1 is an Emax 2 E2.2N 2000 A four-pole withdrawable air circuit breaker moving part with an Ekip Touch LSI electronic trip unit providing long-time overload, short-time selective short-circuit and instantaneous short-circuit protection for high-current low-voltage power distribution systems.
£8,814.19
The ABB 1SDA073015R1 is an Emax 2 E2.2N 2000 A four-pole air circuit breaker moving part designed for reliable protection, switching and isolation in high-current low-voltage electrical distribution systems. Part of the ABB SACE Emax 2 range, it combines robust withdrawable construction with the advanced Ekip Touch LSI electronic trip unit.
The Ekip Touch LSI release provides long-time overload (L), short-time selective short-circuit (S) and instantaneous short-circuit (I) protection. Protection settings are configured through the touch-sensitive display, providing intuitive adjustment and detailed control for distribution systems requiring dependable electronic protection and selective coordination.
With a rated uninterrupted current of 2000 A, a four-pole configuration and an ultimate short-circuit breaking capacity of 66 kA from 380–690 V AC, the 1SDA073015R1 provides consistent fault-interruption performance across a broad operating-voltage range. Its withdrawable moving-part construction enables integration with a compatible Emax 2 E2.2 fixed part and supports efficient inspection, servicing and replacement within switchgear assemblies.
The ABB Emax 2 E2.2N provides switching, isolation and electronic protection for high-current low-voltage distribution circuits. The 1SDA073015R1 delivers an ultimate short-circuit breaking capacity of 66 kA across 380–690 V AC, making it suitable for main switchboards and distribution systems where consistent fault-interruption performance is required across a wide operating-voltage range.
The Ekip Touch LSI trip unit combines adjustable long-time overload protection with short-time selective and instantaneous short-circuit protection. The short-time function supports coordination between upstream and downstream protective devices, while the touch-sensitive interface simplifies configuration. Combined with the E2.2N frame and withdrawable architecture, the 1SDA073015R1 provides a flexible solution for demanding 2000 A distribution applications.
| Series | SACE Emax 2 |
|---|---|
| Frame | E2.2 |
| Performance level | N |
| ABB order code / MPN | 1SDA073015R1 |
| Product type | Air circuit breaker moving part |
| Rated current | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Number of poles | 4 |
| Trip unit | Ekip Touch LSI |
| Trip unit type | Solid-state electronic protection release |
| Protection functions | LSI – long-time overload, short-time selective short-circuit and instantaneous short-circuit protection |
| Overload protection adjustment | 0.4–1 × In |
| Instantaneous protection adjustment | 1.5–15 × In |
| Integrated earth-fault protection | No |
| Protection interface | Touch-sensitive display |
| Ultimate short-circuit breaking capacity (Icu) at 380 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50/60 Hz |
| Current type | AC |
| Execution | Withdrawable moving part (WMP) |
| Main-circuit connection | Connection via separate compatible E2.2 chassis part |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Motor drive | Optional |
| Integrated motor drive | No |
| Integrated undervoltage release | No |
| Degree of protection | IP30 |
| Power loss | 450 W |
| Mechanical durability | 25,000 operating cycles |
| Electrical durability at ≤440 V | 10,000 operating cycles |
| Electrical durability at 500–690 V | 8,000 operating cycles |
| Dimensions (W × H × D) | 407 × 425 × 383 mm |
| Weight | 49 kg |
| Standard | IEC 60947-2 |
| EAN | 8015644768652 |
| Customs tariff number | 85362090 |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA073015R1 is an Emax 2 E2.2N air circuit breaker moving part designed for switching, isolation and electronic protection of high-current low-voltage electrical distribution circuits in industrial, commercial and infrastructure installations.
The E2.2N 2000 has a rated uninterrupted current of 2000 A and is supplied in a four-pole configuration.
The Ekip Touch LSI electronic trip unit provides long-time overload protection (L), short-time selective short-circuit protection (S) and instantaneous short-circuit protection (I). Protection parameters can be configured through the touch-sensitive display.
The E2.2N 2000 provides an ultimate short-circuit breaking capacity of 66 kA at 380 V, 400/415 V, 440 V, 500/525 V and 690 V AC, providing consistent fault-interruption capability across its operating-voltage range.
The 1SDA073015R1 is the withdrawable moving part (WMP) of an ABB Emax 2 circuit-breaker system. It connects to a separate compatible E2.2 fixed chassis part, allowing the breaker to be withdrawn for inspection, servicing or replacement.
ABB SACE Emax 2 air circuit breakers provide advanced protection and control for modern low-voltage power distribution systems, combining high short-circuit performance, intelligent electronic protection and flexible withdrawable switchgear integration.