ABB 1SDA073009R1 Emax 2 E2.2B 2000 Ekip Hi-Touch LSIG four-pole withdrawable air circuit breaker moving part rated at 2000 A with advanced LSIG protection, power-quality monitoring and 42 kA short-circuit performance.
£11,299.13
The ABB E2.2B 2000 Ekip Hi-Touch LSIG 4p WMP, order code 1SDA073009R1, is a four-pole withdrawable air circuit breaker moving part from the ABB SACE Emax 2 range. Rated at 2000 A, it combines the E2.2B frame with the advanced Ekip Hi-Touch LSIG solid-state electronic trip unit for protection and management of high-current low-voltage distribution systems.
The Ekip Hi-Touch LSIG release provides comprehensive long-time (L), selective short-time (S), instantaneous (I) and earth-fault (G) protection. Hi-Touch functionality extends conventional circuit protection with advanced electrical measurement and integrated Network Analyzer capabilities, enabling detailed supervision of electrical parameters and power quality within demanding installations.
The E2.2B frame provides a rated ultimate short-circuit breaking capacity of 42 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s. Its withdrawable moving-part construction is designed for use with the corresponding Emax 2 fixed part, supporting efficient inspection, maintenance and breaker replacement in industrial and commercial switchboards.
The ABB SACE Emax 2 platform is designed to protect and manage high-current low-voltage electrical distribution systems. The Ekip Hi-Touch LSIG release combines long-time overload, selective short-time, instantaneous and earth-fault protection, enabling comprehensive protection against the principal electrical fault conditions encountered in industrial and commercial distribution networks.
Beyond circuit protection, the Hi-Touch platform provides advanced measurement and Network Analyzer functionality for monitoring power quality in real time. Combined with the E2.2B frame's 42 kA short-circuit performance and service-friendly withdrawable architecture, the 1SDA073009R1 provides an effective solution where protection, selectivity, electrical supervision and maintainability are important requirements.
| Series | SACE Emax 2 |
|---|---|
| Order code | 1SDA073009R1 |
| EAN | 8015644768591 |
| Product group | Emax 2 Air Circuit Breaker |
| Product type | Air circuit breaker moving part |
| Frame | E2.2 |
| Performance level | B |
| Rated current | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Number of poles | 4P |
| Current type | AC |
| Installation | Withdrawable, moving part |
| Trip unit | Ekip Hi-Touch LSIG |
| Release type | Solid-state electronic |
| Protection functions | L, S, I and G |
| Rated operational voltage | 690 V AC |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 42 kA |
| Rated short-time withstand current (Icw) | 42 kA for 1 s |
| Integrated earth-fault protection | Yes |
| Power-quality monitoring | Integrated Network Analyzer |
| Auxiliary contacts | 4 |
| Breaker position indication | Open / closed |
| Electrical durability | 10,000 cycles at ≤440 V; 8,000 cycles at 500–690 V |
| Maximum electrical operating frequency | 30 cycles per hour |
| Mechanical durability | 25,000 cycles |
| Dimensions (W × H × D) | 407 × 425 × 383 mm |
| Product net weight | 49 kg |
| Standards / approvals | IEC |
| Country of origin | Italy |
The ABB 1SDA073009R1 is an Emax 2 E2.2B four-pole withdrawable air circuit breaker moving part rated at 2000 A and equipped with an Ekip Hi-Touch LSIG solid-state electronic trip unit.
The Ekip Hi-Touch LSIG provides long-time overload (L), selective short-time (S), instantaneous short-circuit (I) and earth-fault (G) protection together with advanced electrical measurement and power-quality analysis functionality.
The E2.2B 2000 has an ultimate short-circuit breaking capacity of 42 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s.
Yes. The G function of the Ekip Hi-Touch LSIG trip unit provides integrated earth-fault protection alongside long-time, selective short-time and instantaneous short-circuit protection.
Yes. The Ekip Hi-Touch platform includes advanced measurement capabilities and an integrated Network Analyzer for monitoring electrical power quality and supporting detailed supervision of the low-voltage distribution system.
ABB SACE Emax 2 air circuit breakers combine advanced electronic LSIG protection, electrical measurement, power-quality monitoring and service-friendly withdrawable construction for dependable management of demanding low-voltage power distribution systems.