ABB 1SDA073004R1 E2.2B 2000 Ekip Touch LI 4p WMP is a 2000 A four-pole withdrawable Emax 2 air circuit breaker moving part with adjustable long-time and instantaneous electronic protection for high-current low-voltage power distribution systems.
£8,054.11
The ABB E2.2B 2000 Ekip Touch LI 4p WMP, order code 1SDA073004R1, is a four-pole air circuit breaker (ACB) moving part designed for protection, switching and isolation in high-current low-voltage electrical distribution systems. Part of the ABB SACE Emax 2 series, it combines a 2000 A rated current with electronic protection for industrial, commercial and infrastructure power distribution applications.
This Emax 2 circuit breaker is equipped with the Ekip Touch LI electronic trip unit, providing adjustable long-time overload and instantaneous short-circuit protection. The Ekip Touch interface uses a touch-sensitive display for configuration, combining straightforward operation with adjustable electronic protection for power distribution circuits.
The E2.2B 2000 provides a rated ultimate short-circuit breaking capacity of 42 kA from 380–690 V AC, a rated operational voltage of 690 V AC and a rated insulation voltage of 1000 V AC. Its four-pole withdrawable moving-part (WMP) construction is designed for use with the corresponding Emax 2 fixed part, supporting convenient isolation, inspection, servicing and replacement within maintainable switchgear assemblies.
Air circuit breakers such as the ABB Emax 2 E2.2B provide switching, isolation and electronic overcurrent protection for high-current low-voltage distribution circuits. With a 2000 A rated current and 42 kA ultimate short-circuit breaking capacity from 380–690 V AC, this E2.2B model is suited to main switchboards, feeders and other demanding power distribution applications.
The Ekip Touch LI trip unit combines adjustable long-time protection against sustained overloads with instantaneous protection against severe short circuits. Its touch-sensitive interface facilitates protection configuration, while the withdrawable Emax 2 architecture supports maintenance and isolation strategies in installations where serviceability and system availability are important.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA073004R1 |
| EAN | 8015644768546 |
| Product type | Air circuit breaker moving part |
| Product group | Emax2 Air Circuit Breaker |
| Frame | E2.2 |
| Performance level | B |
| Rated current | 2000 A |
| Number of poles | 4 |
| Trip unit | Ekip Touch LI |
| Release type | Electronic |
| Protection functions | Long-time (L), instantaneous (I) |
| Long-time overload protection setting | 0.4–1 × In |
| Long-time overload adjustment range | 800–2000 A |
| Instantaneous protection setting | 1.5–15 × In |
| Instantaneous short-circuit adjustment range | 3000–30000 A |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 42 kA |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50/60 Hz |
| Current type | AC |
| Interface | Touch-sensitive display |
| Installation | Withdrawable |
| Configuration | Moving part of withdrawable circuit breaker (WMP) |
| Terminal arrangement | Rear terminals |
| Standard | IEC 60947-2 |
The ABB 1SDA073004R1 is a 2000 A four-pole air circuit breaker moving part used for protection, switching and isolation in high-current low-voltage industrial, commercial and infrastructure power distribution systems.
The ABB E2.2B 2000 has a rated current of 2000 A.
The Ekip Touch LI electronic trip unit provides adjustable long-time overload protection from 0.4–1 × In and instantaneous short-circuit protection from 1.5–15 × In.
The E2.2B 2000 provides a rated ultimate short-circuit breaking capacity of 42 kA at 380, 400/415, 440, 500/525 and 690 V AC.
Yes. The 1SDA073004R1 is the four-pole withdrawable moving part (WMP) of an ABB SACE Emax 2 E2.2B 2000 air circuit breaker and is designed for use with the corresponding withdrawable fixed part.
ABB SACE Emax 2 air circuit breakers combine dependable high-current low-voltage circuit protection with advanced electronic trip technology, while the Ekip Touch platform provides configurable protection and intuitive operation for demanding electrical distribution systems.