1SDA073000R1 ABB Emax 2 E2.2H 1600 Ekip G Hi-Touch LSIG 4-Pole Air Circuit Breaker

1SDA073000R1 ABB Emax 2 E2.2H 1600 Ekip G Hi-Touch LSIG 4-Pole Air Circuit Breaker

ABB 1SDA073000R1 is an Emax 2 E2.2H 1600 A four-pole withdrawable air circuit breaker moving part with an Ekip G Hi-Touch LSIG electronic trip unit for advanced generator, overload, short-circuit and earth-fault protection in demanding low-voltage power systems.

SKU: 1SDA073000R1MPN: 1SDA073000R1
Price
List Price £15,630.70 ex VAT
Your Price (ex VAT) Save 25%
£11,723.03 25% OFF
You save £3,907.68 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £11,723.03
Trade pricing is personalised to your account

Manufacturer Lead Time

£11,723.03

Why Choose the ABB 1SDA073000R1 Emax 2 Air Circuit Breaker?

The ABB 1SDA073000R1 is a high-performance Emax 2 E2.2H 1600 A four-pole air circuit breaker moving part engineered for advanced generator and low-voltage power-distribution protection. Part of the ABB SACE Emax 2 range, it combines the high breaking performance of the E2.2H frame with withdrawable construction and the sophisticated Ekip G Hi-Touch LSIG electronic trip unit.

The Ekip G Hi-Touch LSIG release provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection. Designed specifically for advanced generator protection, the G Hi-Touch platform also incorporates sophisticated measurement and network-analysis functionality, including Ekip Measuring Pro and Network Analyzer capabilities.

With a rated uninterrupted current of 1600 A, a four-pole configuration and an ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC and 85 kA at 500–690 V AC, the 1SDA073000R1 provides exceptional fault-interruption performance. Its withdrawable moving-part design enables integration with a compatible Emax 2 E2.2 fixed part and supports efficient inspection, servicing and replacement within switchgear assemblies.

Key Advantages

  • High-performance ABB Emax 2 generator-protection air circuit breaker moving part.
  • 1600 A rated uninterrupted current for demanding generator and power-distribution applications.
  • Four-pole configuration with the neutral pole rated at 100% of rated current.
  • 100 kA ultimate short-circuit breaking capacity at 400–440 V AC.
  • 85 kA ultimate short-circuit breaking capacity at 500–690 V AC.
  • 85 kA rated short-time withstand current for 1 s.
  • Advanced Ekip G Hi-Touch LSIG electronic trip unit with generator-specific protection functionality.
  • Comprehensive overload, selective short-circuit, instantaneous short-circuit and earth-fault protection.
  • Integrated advanced measurement and network-analysis functionality.
  • Withdrawable construction supports efficient switchboard inspection, maintenance and servicing.

Key Features

  • ABB SACE Emax 2 E2.2H series.
  • 1600 A rated current.
  • Four-pole air circuit breaker moving part.
  • Ekip G Hi-Touch LSIG solid-state electronic protection release.
  • Long-time overload (L) protection adjustable from 0.4–1 × In.
  • Short-time selective short-circuit (S) protection.
  • Instantaneous short-circuit (I) protection adjustable from 1.5–15 × In.
  • Earth-fault (G) protection adjustable from 0.1–1 × In.
  • Generator-specific protection functionality.
  • Integrated Ekip Measuring Pro measurement functionality.
  • Integrated Network Analyzer functionality.
  • Touch-sensitive display interface for protection configuration and monitoring.
  • 100 kA Icu at 400–440 V AC.
  • 85 kA Icu at 500–690 V AC.
  • 85 kA Icw for 1 s and 66 kA Icw for 3 s.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • Suitable for IT networks up to 690 V.

Advanced Generator and LSIG Protection for Critical Power Systems

The ABB Emax 2 E2.2H is engineered for high-current low-voltage systems where substantial fault-interruption capability and protection selectivity are essential. Its H performance level provides 100 kA ultimate short-circuit breaking capacity at 400–440 V AC, 85 kA at 500–690 V AC and a rated short-time withstand current of 85 kA for 1 s, making the 1SDA073000R1 particularly suitable for demanding generator and power-distribution installations.

The Ekip G Hi-Touch LSIG trip unit combines comprehensive overload, selective short-circuit, instantaneous short-circuit and earth-fault protection with generator-specific functionality, advanced electrical measurement and network analysis. Together with the E2.2H frame and withdrawable architecture, the 1SDA073000R1 provides a sophisticated protection solution for critical systems requiring high breaking performance, detailed system supervision and convenient switchgear maintenance.

Typical Applications

  • Generator protection and power-generation systems.
  • Main low-voltage electrical distribution switchboards.
  • Generator-fed and transformer-fed distribution networks.
  • Industrial power distribution systems.
  • Critical power and high-availability installations.
  • Manufacturing and process plants.
  • Infrastructure and large commercial electrical systems.
  • Power distribution systems requiring advanced measurement and network analysis.

Technical Specifications

Series SACE Emax 2
Frame E2.2
Performance level H
ABB order code / MPN 1SDA073000R1
Product type Air circuit breaker moving part
Rated current (In) 1600 A
Rated uninterrupted current (Iu) 1600 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Frequency 50/60 Hz
Number of poles 4
Neutral pole current 100% of rated current
Trip unit Ekip G Hi-Touch LSIG
Trip unit type Solid-state electronic release
Protection functions LSIG – long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection
Overload protection adjustment 0.4–1 × In
Instantaneous protection adjustment 1.5–15 × In
Earth-fault protection adjustment 0.1–1 × In
Generator-specific protection Yes
Measurement module Ekip Measuring Pro
Network analysis Integrated Network Analyzer functionality
Ultimate short-circuit breaking capacity (Icu) at 400 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 500 V AC 85 kA
Ultimate short-circuit breaking capacity (Icu) at 525 V AC 85 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 85 kA
Rated service short-circuit breaking capacity (Ics) 100% of Icu
Rated short-time withstand current (Icw, 1 s) 85 kA
Rated short-time withstand current (Icw, 3 s) 66 kA
Current type AC
Execution Withdrawable moving part (WMP)
Connecting capacity 1200 mm²
Suitable for IT networks Yes, up to 690 V
Power loss 288 W
Mechanical durability 25,000 operating cycles
Electrical durability at ≤440 V 12,000 operating cycles
Electrical durability at 500–690 V 10,000 operating cycles
Dimensions (W × H × D) 407 × 425 × 383 mm
Weight 55 kg
Standard IEC 60947-2
EAN 8015644768508
Customs tariff number 85362090
Product group Emax2 Air Circuit Breaker

Frequently Asked Questions

What is the ABB 1SDA073000R1 used for?

The ABB 1SDA073000R1 is an Emax 2 E2.2H air circuit breaker moving part designed for advanced protection of generators and high-current low-voltage power-distribution circuits in demanding industrial, infrastructure and critical-power installations.

What is the current rating of the ABB 1SDA073000R1?

The E2.2H 1600 has a rated uninterrupted current of 1600 A and is supplied in a four-pole configuration with the neutral pole rated at 100% of rated current.

What protection functions does the Ekip G Hi-Touch LSIG trip unit provide?

The Ekip G Hi-Touch LSIG electronic trip unit provides long-time overload protection (L), short-time selective short-circuit protection (S), instantaneous short-circuit protection (I) and earth-fault protection (G), together with generator-specific protection, advanced measurement and network-analysis functionality.

What is the breaking capacity of the E2.2H 1600?

The E2.2H 1600 provides an ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC and 85 kA at 500–690 V AC. Its rated short-time withstand current is 85 kA for 1 s and 66 kA for 3 s.

Is the ABB 1SDA073000R1 a fixed or withdrawable circuit breaker?

The 1SDA073000R1 is the withdrawable moving part (WMP) of an ABB Emax 2 circuit-breaker system. It is designed for integration with a compatible E2.2 fixed part, allowing the breaker to be withdrawn for inspection, maintenance or replacement.

Trusted Generator and Low-Voltage Protection from ABB

ABB SACE Emax 2 air circuit breakers combine high short-circuit performance, sophisticated electronic protection, advanced measurement and flexible withdrawable construction for demanding generator and low-voltage power-distribution systems.