ABB 1SDA072988R1 is an Emax 2 E2.2S 1600 A four-pole withdrawable air circuit breaker moving part with an Ekip Hi-Touch LSI electronic trip unit for advanced overload and short-circuit protection in demanding low-voltage power distribution systems.
£10,305.16
The ABB 1SDA072988R1 is a high-performance Emax 2 E2.2S 1600 A four-pole air circuit breaker moving part designed for advanced protection, switching and isolation in demanding low-voltage electrical distribution systems. Part of the ABB SACE Emax 2 range, it combines robust withdrawable construction with the sophisticated Ekip Hi-Touch LSI electronic trip unit.
The Ekip Hi-Touch LSI release provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection. ABB's Hi-Touch platform provides advanced protection, measurement and monitoring capabilities, making this configuration well suited to sophisticated distribution systems where selectivity, system visibility and dependable fault protection are important.
With a rated uninterrupted current of 1600 A, a four-pole configuration and an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC, the 1SDA072988R1 provides robust fault-interruption performance for high-current installations. Its withdrawable moving-part design enables integration with the appropriate Emax 2 E2.2 fixed part and supports efficient inspection, servicing and replacement within switchgear assemblies.
Air circuit breakers such as the ABB Emax 2 E2.2S provide switching, isolation and protection for high-current low-voltage distribution circuits. The E2.2S performance level combines an ultimate short-circuit breaking capacity of 85 kA at 440 V AC with a rated short-time withstand current of 66 kA for 1 s, making the 1SDA072988R1 suitable for main switchboards and demanding distribution systems where high fault levels and protection selectivity must be considered.
The Ekip Hi-Touch LSI trip unit combines long-time overload, short-time short-circuit and instantaneous short-circuit protection with advanced measurement and monitoring capabilities. Together with the E2.2S frame and withdrawable architecture, the 1SDA072988R1 provides a flexible solution for sophisticated low-voltage distribution systems requiring high breaking performance, selective electronic protection and convenient switchgear maintenance.
| Series | SACE Emax 2 |
|---|---|
| Frame | E2.2 |
| Performance level | S |
| ABB order code / MPN | 1SDA072988R1 |
| Product type | Air circuit breaker moving part |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated operational voltage | 690 V AC |
| Number of poles | 4 |
| Trip unit | Ekip Hi-Touch LSI |
| Trip unit type | Solid-state electronic protection release |
| Protection functions | LSI – long-time overload, short-time short-circuit and instantaneous short-circuit protection |
| Overload release adjustment range | 640–1600 A |
| Short-time delayed short-circuit release adjustment range | 960–16000 A |
| Integrated earth-fault protection | No |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 85 kA |
| Rated short-time withstand current (Icw, 1 s) | 66 kA |
| Current type | AC |
| Execution | Withdrawable moving part (WMP) |
| Main-circuit connection | Connection at separate chassis part |
| Auxiliary contacts | 4 changeover contacts |
| Control element | Push button |
| Motor drive | Optional |
| Integrated motor drive | No |
| Integrated undervoltage release | No |
| Degree of protection | IP30 |
| Power loss | 288 W |
| Dimensions (W × H × D) | 407 × 425 × 383 mm |
| Weight | 55 kg |
| Standard | IEC 60947-2 |
| EAN | 8015644768386 |
| Customs tariff number | 85362090 |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA072988R1 is an Emax 2 E2.2S air circuit breaker moving part designed for switching, isolation and protection of high-current low-voltage electrical distribution circuits in demanding industrial, commercial and infrastructure installations.
The E2.2S 1600 has a rated uninterrupted current of 1600 A and is supplied in a four-pole configuration.
The Ekip Hi-Touch LSI electronic trip unit provides long-time overload protection (L), short-time short-circuit protection (S) and instantaneous short-circuit protection (I), together with advanced measurement and monitoring capabilities. This LSI configuration does not include integrated earth-fault protection.
The E2.2S 1600 has an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and a rated short-time withstand current of 66 kA for 1 s, providing robust fault-interruption performance for demanding low-voltage systems.
The 1SDA072988R1 is the withdrawable moving part (WMP) of an ABB Emax 2 circuit-breaker system. It connects to a separate compatible E2.2 fixed chassis part, allowing the breaker to be withdrawn for inspection, servicing or replacement.
ABB SACE Emax 2 air circuit breakers provide advanced protection and control for modern low-voltage power distribution systems, combining high short-circuit performance, sophisticated electronic protection and flexible withdrawable switchgear integration.