Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072961R1 SACE Emax 2 E2.2B 1600 A four-pole withdrawable air circuit breaker with Ekip Dip LI electronic protection for reliable low-voltage power distribution.
£6,416.99
The ABB 1SDA072961R1 is a SACE Emax 2 E2.2B air circuit breaker rated at 1600 A, designed for reliable protection, switching and isolation in low-voltage electrical distribution systems. This four-pole withdrawable moving-part breaker incorporates the Ekip Dip LI electronic trip unit, providing long-time overload and instantaneous short-circuit protection.
As part of the ABB SACE Emax 2 range, the E2.2B combines dependable electronic protection with robust mechanical construction and straightforward switchboard integration. The Ekip Dip LI release provides essential adjustable protection functions without unnecessary complexity, making this breaker well suited to industrial, commercial and infrastructure power-distribution applications.
With a rated uninterrupted current of 1600 A, a four-pole configuration and rated operational voltage up to 690 V AC, this E2.2B breaker provides an ultimate short-circuit breaking capacity of 42 kA across its specified AC voltage range. Its withdrawable moving-part construction enables convenient inspection, servicing and replacement while supporting maintainable switchboard installations.
Air circuit breakers such as the ABB SACE Emax 2 protect low-voltage electrical networks against overloads and short circuits while providing dependable switching and isolation of high-current circuits. The E2.2B platform combines electronic protection with robust short-circuit withstand performance for main distribution and feeder applications.
The Ekip Dip LI release provides long-time protection against sustained overload conditions together with instantaneous protection for severe short circuits. This focused protection arrangement makes the 1SDA072961R1 suitable for installations requiring dependable electronic circuit protection without integrated short-time or ground-fault protection functions.
| Series | SACE Emax 2 |
|---|---|
| ABB order code | 1SDA072961R1 |
| EAN | 8015644768119 |
| Product type | Air circuit breaker |
| Frame | E2.2B |
| Rated uninterrupted current | 1600 A |
| Number of poles | 4 |
| Neutral pole current | 100% Iu |
| Current type | AC |
| Trip unit | Ekip Dip LI |
| Release type | Electronic / solid-state |
| Protection functions | Long-time (L), instantaneous (I) |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Ultimate breaking capacity (Icu) at 400 V AC | 42 kA |
| Ultimate breaking capacity (Icu) at 415 V AC | 42 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 42 kA |
| Ultimate breaking capacity (Icu) at 500/525 V AC | 42 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 42 kA |
| Service breaking capacity (Ics) | 100% of Icu |
| Short-time withstand current (Icw), 1 s | 42 kA |
| Short-time withstand current (Icw), 3 s | 42 kA |
| Installation | Withdrawable |
| Configuration | Moving part |
| Main-circuit connection | Connection at separate chassis part |
| Auxiliary contacts | 4 change-over contacts |
| Integrated earth-fault protection | No |
| Degree of protection | IP30 |
| Power loss | 288 W |
| Electrical durability | 12,000 cycles at Ue ≤ 440 V; 10,000 cycles at 500–690 V |
| Mechanical durability | 25,000 cycles |
| Product net width | 407 mm |
| Product net height | 425 mm |
| Product net depth | 383 mm |
| Product net weight | 49 kg |
| Standard | IEC 60947-2 |
The ABB 1SDA072961R1 is a 1600 A air circuit breaker used for switching, isolation and protection of low-voltage electrical distribution systems against overloads and short circuits.
The breaker incorporates an Ekip Dip LI electronic trip unit, providing long-time overload and instantaneous short-circuit protection.
The E2.2B 1600 provides an ultimate short-circuit breaking capacity of 42 kA, including at 400/415 V AC and 690 V AC.
No. This version uses the Ekip Dip LI release, providing long-time and instantaneous protection; versions with LSIG releases are available where integrated ground-fault protection is required.
The 1SDA072961R1 is a withdrawable moving-part version of the SACE Emax 2 E2.2B, designed for connection to the corresponding separate chassis part and convenient withdrawal for inspection, servicing or replacement.
ABB SACE Emax 2 air circuit breakers combine dependable electronic circuit protection, robust switching performance and maintainable withdrawable construction for modern low-voltage power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.