ABB 1SDA072946R1 Emax 2 E2.2S 1250 Ekip Touch LSIG four-pole withdrawable air circuit breaker moving part rated at 1250 A with adjustable long-time, selective short-time, instantaneous and earth-fault protection.
£7,045.52
The ABB E2.2S 1250 Ekip Touch LSIG 4p WMP, order code 1SDA072946R1, is a high-performance four-pole withdrawable air circuit breaker moving part from the ABB SACE Emax 2 range. Designed for demanding low-voltage power distribution systems, it combines a 1250 A rated uninterrupted current with the advanced Ekip Touch LSIG electronic trip unit.
The Ekip Touch LSIG release provides comprehensive long-time (L), selective short-time (S), instantaneous (I) and earth-fault (G) protection. This combination protects against overloads, short circuits and earth faults while supporting selective coordination between upstream and downstream protective devices, helping maintain continuity of supply and protect critical distribution equipment.
The E2.2S performance level provides an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC. Its withdrawable moving-part construction facilitates inspection, servicing and replacement within compatible Emax 2 switchgear, making it well suited to high-performance industrial and commercial distribution systems.
Air circuit breakers such as the ABB SACE Emax 2 protect high-current low-voltage distribution systems against potentially damaging overloads, short circuits and earth faults. The Ekip Touch LSIG release combines adjustable long-time overload, selective short-time, instantaneous and earth-fault protection, enabling coordinated protection of conductors, transformers, switchgear and connected electrical equipment.
The selective short-time function supports coordinated fault clearing between different levels of protective devices, while the integrated earth-fault function extends protection to ground-fault conditions. Combined with the E2.2S frame's 85 kA breaking capacity at 400–440 V AC and service-friendly withdrawable construction, the 1SDA072946R1 provides dependable protection for demanding modern switchboards.
| Series | SACE Emax 2 |
|---|---|
| Order code | 1SDA072946R1 |
| EAN | 8015644767969 |
| Product type | Air circuit breaker moving part |
| Frame / sub-type | E2.2 |
| Short-circuit performance level | S |
| Rated uninterrupted current (Iu) | 1250 A |
| Number of poles | 4P |
| Current type | AC |
| Installation | Withdrawable, moving part |
| Main-circuit connection | Separate fixed chassis |
| Trip unit | Ekip Touch LSIG |
| Release type | Electronic (EL) |
| Protection functions | L, S, I and G |
| Overload release current setting | 500–1250 A |
| Short-time delayed short-circuit release setting | 750–12500 A |
| Instantaneous short-circuit release setting | 1875–18750 A |
| Rated voltage (Ur) | 690 V |
| Ultimate breaking capacity (Icu) at 400 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 415 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 500 V AC | 66 kA |
| Ultimate breaking capacity (Icu) at 525 V AC | 66 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 66 kA |
| Service breaking capacity (Ics) | 100% of Icu |
| Short-time withstand current (Icw) | 66 kA for 1 s; 50 kA for 3 s |
| Integrated earth-fault protection | Yes |
| Auxiliary contacts | 4 change-over contacts |
| Breaker trip indication | Yes |
| Motor drive integrated | No |
| Motor drive | Optional |
| Degree of protection | IP30 |
| Power loss | 176 W |
| Suitable for IT networks | Yes, up to 690 V |
| Standard | IEC |
| Dimensions (W × H × D) | 407 × 425 × 383 mm |
| Country of origin | Italy |
The ABB 1SDA072946R1 is an Emax 2 E2.2S four-pole withdrawable air circuit breaker moving part rated at 1250 A and equipped with an Ekip Touch LSIG electronic trip unit.
The Ekip Touch LSIG provides long-time overload (L), selective short-time (S), instantaneous short-circuit (I) and earth-fault (G) protection for comprehensive low-voltage distribution protection.
The overload release is adjustable from 500–1250 A, the short-time delayed short-circuit release from 750–12500 A, and the instantaneous short-circuit release from 1875–18750 A.
The E2.2S provides an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC, with service breaking capacity equal to 100% of Icu.
Yes. The G function of the Ekip Touch LSIG electronic trip unit provides integrated earth-fault protection in addition to long-time, selective short-time and instantaneous short-circuit protection.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, high short-circuit performance and service-friendly withdrawable construction for dependable low-voltage power distribution in demanding industrial and commercial installations.