ABB 1SDA072943R1 is an Emax 2 E2.2S 1250 A four-pole withdrawable air circuit breaker moving part with an Ekip Dip LSIG electronic trip unit providing overload, short-circuit and earth-fault protection for demanding low-voltage power distribution systems.
£6,972.41
The ABB 1SDA072943R1 is a high-performance Emax 2 E2.2S 1250 A four-pole air circuit breaker moving part designed for protection, switching and control in demanding low-voltage electrical distribution systems. Part of the ABB SACE Emax 2 air circuit breaker series, it combines robust withdrawable construction with the dependable Ekip Dip LSIG electronic trip unit.
The Ekip Dip LSIG release provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection. Protection parameters are configured using DIP switches, providing straightforward adjustment for distribution applications requiring comprehensive electronic protection without a touchscreen interface.
With a rated current of 1250 A, a four-pole configuration, an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC, the 1SDA072943R1 provides dependable fault-interruption capability for high-current distribution circuits. Its withdrawable moving-part design enables integration with the appropriate Emax 2 E2.2 fixed part and supports efficient inspection, maintenance and replacement within switchgear assemblies.
Air circuit breakers such as the ABB Emax 2 E2.2S provide switching, isolation and protection for high-current low-voltage distribution circuits. The E2.2S performance level combines an 85 kA breaking capacity at 400–440 V AC with a 66 kA short-time withstand rating for 1 s, making it suitable for main switchboards and demanding distribution systems where high fault levels, protection selectivity and continuity of service must be considered.
The Ekip Dip LSIG trip unit provides comprehensive protection against long-time overloads, short-time and instantaneous short circuits, and earth faults. Combined with the E2.2S frame's high breaking capacity and withdrawable architecture, the 1SDA072943R1 provides a robust protection solution for industrial and commercial distribution systems while allowing straightforward protection adjustment through DIP switches.
| Series | SACE Emax 2 |
|---|---|
| Frame | E2.2 |
| Performance level | S |
| ABB order code / MPN | 1SDA072943R1 |
| Product type | Air circuit breaker moving part |
| Rated current | 1250 A |
| Rated uninterrupted current | 1250 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V AC |
| Rated impulse withstand voltage | 12 kV |
| Frequency | 50/60 Hz |
| Number of poles | 4 |
| Neutral pole current | 100% of rated current |
| Trip unit | Ekip Dip LSIG |
| Trip unit type | Electronic protection release |
| Protection functions | LSIG – long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection |
| Overload protection adjustment | 0.4–1 × In |
| Instantaneous protection adjustment | 1.5–15 × In |
| Earth-fault protection adjustment | 0.1–1 × In |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 525 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw, 1 s) | 66 kA |
| Rated short-time withstand current (Icw, 3 s) | 50 kA |
| Current type | AC |
| Execution | Withdrawable moving part (WMP) |
| Connecting capacity | 1200 mm² |
| Power loss | 176 W |
| Mechanical durability | 25,000 operating cycles |
| Electrical durability | 15,000 operating cycles |
| Dimensions (H × W × D) | 425 × 407 × 383 mm |
| Weight | 55 kg |
| Standard | IEC 60947-2 |
| EAN | 8015644767938 |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA072943R1 is an Emax 2 air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution circuits in industrial, commercial and infrastructure applications.
The E2.2S 1250 has a rated current of 1250 A and is supplied in a four-pole configuration with the neutral pole rated at 100% of the rated current.
The Ekip Dip LSIG electronic trip unit provides long-time overload protection (L), short-time short-circuit protection (S), instantaneous short-circuit protection (I) and earth-fault protection (G), with protection parameters configured using DIP switches.
The E2.2S 1250 has an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC. Its rated short-time withstand current is 66 kA for 1 s and 50 kA for 3 s.
The 1SDA072943R1 is the withdrawable moving part (WMP) of an ABB Emax 2 circuit-breaker system and is designed for installation with the appropriate E2.2 fixed part, allowing the breaker to be withdrawn for inspection, maintenance or replacement.
ABB SACE Emax 2 air circuit breakers provide advanced protection and control for modern low-voltage power distribution systems, combining high short-circuit performance, comprehensive electronic protection and flexible withdrawable switchgear integration.