Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072937R1 E2.2N 1250 Ekip G Touch LSIG 4p WMP is a 1250 A four-pole withdrawable Emax 2 air circuit breaker moving part with advanced electronic LSIG and generator protection for low-voltage power distribution systems.
£8,901.89
The ABB E2.2N 1250 Ekip G Touch LSIG 4p WMP, order code 1SDA072937R1, is a high-performance four-pole air circuit breaker (ACB) moving part designed for advanced protection, switching and isolation in low-voltage electrical distribution systems. As part of the ABB SACE Emax 2 series, it combines a 1250 A rated current with generator-focused protection and comprehensive electronic trip functionality for demanding industrial, commercial and infrastructure installations.
This Emax 2 circuit breaker is equipped with the Ekip G Touch LSIG electronic trip unit, providing long-time, short-time, instantaneous and ground-fault protection together with functions specifically intended for generator applications. The touchscreen interface enables convenient configuration of protection parameters, while integrated measurement capabilities support monitoring and management of the electrical system.
The E2.2N 1250 provides a rated ultimate short-circuit breaking capacity of 66 kA at 380–690 V AC, with a rated operational voltage of 690 V AC. Its four-pole withdrawable moving-part (WMP) construction is designed for use with a compatible Emax 2 fixed part, supporting convenient isolation, inspection, servicing and replacement in critical power distribution and generator protection systems.
Air circuit breakers such as the ABB Emax 2 E2.2N provide switching, isolation and electronic overcurrent protection for high-current low-voltage distribution circuits. The E2.2N performance level delivers a 66 kA ultimate short-circuit breaking capacity across a broad range of operating voltages, helping protect switchboards, conductors, generators and downstream electrical equipment during fault conditions.
The Ekip G Touch LSIG trip unit extends conventional LSIG protection with functions designed specifically for generator applications. Long-time, short-time, instantaneous and ground-fault protection are combined with integrated measurement and touchscreen configuration, making this breaker particularly suitable for installations where generator protection, selective coordination, electrical monitoring, system availability and maintainability are important.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA072937R1 |
| EAN | 8015644767877 |
| Product type | Air circuit breaker moving part |
| Product group | Emax2 Air Circuit Breaker |
| Frame | E2.2 |
| Performance level | N |
| Rated current (In) | 1250 A |
| Number of poles | 4 |
| Trip unit | Ekip G Touch LSIG |
| Release type | Electronic |
| Protection functions | Long-time (L), short-time (S), instantaneous (I), ground-fault (G) |
| Long-time protection adjustment | 0.4–1 × In |
| Short-time protection adjustment | 0.6–10 × In |
| Instantaneous protection adjustment | 1.5–15 × In |
| Ground-fault protection adjustment | 0.1–1 × In |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V AC |
| Frequency | 50 / 60 Hz |
| Current type | AC |
| Measurement functionality | Ekip Measuring Pro integrated |
| Configuration interface | Touchscreen display |
| Execution | Withdrawable |
| Configuration | Moving part of withdrawable circuit breaker (WMP) |
| Weight | approx. 60 kg |
The ABB 1SDA072937R1 is a 1250 A four-pole air circuit breaker moving part designed for advanced protection, switching and isolation in low-voltage power distribution and generator applications.
The E2.2N 1250 has a rated current of 1250 A.
The Ekip G Touch LSIG trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection, together with protection functionality specifically intended for generator applications.
The E2.2N provides a rated ultimate short-circuit breaking capacity of 66 kA at operating voltages from 380 V AC to 690 V AC.
Yes. The 1SDA072937R1 is the four-pole withdrawable moving part (WMP) of an ABB SACE Emax 2 E2.2N 1250 air circuit breaker and is designed for use with the corresponding withdrawable fixed part.
ABB SACE Emax 2 air circuit breakers combine dependable low-voltage circuit protection with advanced electronic trip technology, while Ekip G protection functions provide additional capabilities for demanding generator and power distribution applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.