1SDA072931R1 ABB E2.2N 1250 Ekip Dip LI 4p WMP Air Circuit Breaker 1250 A

1SDA072931R1 ABB E2.2N 1250 Ekip Dip LI 4p WMP Air Circuit Breaker 1250 A

ABB 1SDA072931R1 E2.2N 1250 Ekip Dip LI 4p WMP is a 1250 A four-pole withdrawable SACE Emax 2 air circuit breaker with Ekip Dip LI electronic protection and 66 kA breaking capacity for low-voltage power distribution systems.

SKU: 1SDA072931R1MPN: 1SDA072931R1
Price
List Price £7,522.99 ex VAT
Your Price (ex VAT) Save 25%
£5,642.24 25% OFF
You save £1,880.75 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £5,642.24
Trade pricing is personalised to your account

Manufacturer Lead Time

£5,642.24

Why Choose the ABB E2.2N 1250 Ekip Dip LI 4p WMP Air Circuit Breaker?

The ABB E2.2N 1250 Ekip Dip LI 4p WMP, order code 1SDA072931R1, is a high-performance four-pole air circuit breaker (ACB) from the ABB SACE Emax 2 range, designed for protection and switching in low-voltage power distribution systems. With a rated uninterrupted current of 1250 A, it combines the E2.2 frame with an Ekip Dip LI electronic protection release.

The Ekip Dip LI release provides adjustable long-time overload and instantaneous short-circuit protection. Protection settings are configured using DIP switches, providing straightforward adjustment for the requirements of the electrical installation while helping protect cables, busbars and connected equipment against damaging overcurrents.

The E2.2N 1250 offers a rated ultimate short-circuit breaking capacity of 66 kA across 380–690 V AC, together with a rated operational voltage of 690 V AC and rated insulation voltage of 1000 V AC. This four-pole model is supplied as a withdrawable moving part, supporting efficient inspection and maintenance within compatible ABB SACE Emax 2 switchgear assemblies.

Key Advantages

  • High-performance 1250 A four-pole air circuit breaker for low-voltage power distribution.
  • Ekip Dip LI electronic trip unit provides adjustable overload and instantaneous short-circuit protection.
  • Rated ultimate short-circuit breaking capacity of 66 kA at 400/415 V AC.
  • Maintains 66 kA Icu at 690 V AC for demanding distribution systems.
  • 690 V AC rated operational voltage for industrial and commercial installations.
  • Withdrawable moving-part construction supports efficient switchgear servicing and maintenance.

Key Features

  • ABB SACE Emax 2 E2.2 air circuit breaker platform.
  • 1250 A rated uninterrupted current.
  • Four-pole configuration.
  • Ekip Dip LI electronic release.
  • Adjustable long-time overload protection from 0.4–1 × In.
  • Adjustable instantaneous protection from 1.5–15 × In.
  • Protection settings configured through DIP switches.
  • 66 kA Icu at 380–690 V AC.
  • Rated operational voltage up to 690 V AC.
  • Withdrawable moving-part design with rear terminals for compatible Emax 2 switchgear.

Reliable Circuit Protection for High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax 2 protect low-voltage electrical installations against overloads and short circuits while providing controlled switching and isolation of high-current circuits. The E2.2 platform combines substantial current-carrying capability with high short-circuit breaking performance for use in main switchboards and demanding industrial power distribution systems.

The Ekip Dip LI electronic trip unit provides adjustable long-time overload and instantaneous short-circuit protection, with settings made through accessible DIP switches. Combined with the breaker’s 1250 A current rating, four-pole configuration and 66 kA breaking capacity, the E2.2N provides dependable protection for critical low-voltage distribution applications.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Commercial and infrastructure electrical installations.
  • Transformer and generator distribution applications.
  • Incoming and outgoing switchgear feeders.
  • High-current electrical systems requiring adjustable electronic overload and short-circuit protection.

Technical Specifications

Series SACE Emax 2
Order code / MPN 1SDA072931R1
Product type Air circuit breaker
Frame / sub-type E2.2
Short-circuit performance level N
Rated current (In) 1250 A
Rated uninterrupted current (Iu) 1250 A
Number of poles 4
Release Ekip Dip LI
Release type Electronic
Protection functions Long-time overload and instantaneous short-circuit protection (LI)
Long-time protection adjustment 0.4–1 × In
Instantaneous protection adjustment 1.5–15 × In
Protection adjustment method DIP switches
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Frequency 50 / 60 Hz
Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500/525 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 66 kA
Version Withdrawable moving part
Terminal arrangement Rear terminals
Current type AC
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA072931R1 used for?

The ABB 1SDA072931R1 is a 1250 A four-pole air circuit breaker designed for switching and protection in low-voltage industrial, commercial and infrastructure power distribution systems.

What protection functions does the Ekip Dip LI release provide?

The Ekip Dip LI electronic release provides adjustable long-time overload and instantaneous short-circuit protection, with long-time adjustment from 0.4–1 × In and instantaneous adjustment from 1.5–15 × In.

What is the breaking capacity of the E2.2N 1250?

The E2.2N 1250 has a rated ultimate short-circuit breaking capacity of 66 kA across operating voltages from 380–690 V AC.

How are the protection settings adjusted?

The protection thresholds of the Ekip Dip LI electronic release are configured using DIP switches, providing straightforward adjustment of the overload and instantaneous protection functions.

Is the ABB 1SDA072931R1 a fixed or withdrawable circuit breaker?

The E2.2N 1250 Ekip Dip LI 4p WMP is supplied as a withdrawable moving part with rear terminals for use within compatible ABB SACE Emax 2 switchgear assemblies.

Trusted ABB Protection for Critical Power Systems

ABB SACE Emax 2 air circuit breakers are designed for dependable protection, switching and control in low-voltage power distribution systems, combining high short-circuit performance with advanced electronic protection technology.