1SDA072873R1 ABB E2.2N 800 Ekip Dip LSIG 4p WMP Air Circuit Breaker

1SDA072873R1 ABB E2.2N 800 Ekip Dip LSIG 4p WMP Air Circuit Breaker

ABB 1SDA072873R1 is an Emax 2 E2.2N 800 A four-pole withdrawable air circuit breaker moving part with an Ekip Dip LSIG electronic trip unit for comprehensive overload, short-circuit and earth-fault protection.

SKU: 1SDA072873R1MPN: 1SDA072873R1
Price
List Price £8,263.61 ex VAT
Your Price (ex VAT) Save 25%
£6,197.71 25% OFF
You save £2,065.90 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £6,197.71
Trade pricing is personalised to your account

Manufacturer Lead Time

£6,197.71

Why Choose the ABB E2.2N 800 Ekip Dip LSIG 4p WMP Air Circuit Breaker?

The ABB E2.2N 800 Ekip Dip LSIG 4p WMP, order code 1SDA072873R1, is a four-pole withdrawable air circuit breaker moving part designed for protection and switching in demanding low-voltage power distribution systems. Part of the ABB SACE Emax 2 E2.2 series, it combines an 800 A rated current with an Ekip Dip LSIG electronic trip unit for comprehensive overload, selective short-circuit, instantaneous short-circuit and earth-fault protection.

The Ekip Dip LSIG trip unit provides long-time overload (L), short-time delayed short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection. Its electronic protection architecture and DIP-switch configuration provide straightforward adjustment while supporting selective coordination and comprehensive protection throughout industrial and commercial electrical distribution networks.

The E2.2N performance level provides an ultimate short-circuit breaking capacity of 66 kA at 440 V AC together with a rated short-time withstand current of 66 kA for 1 s. Its four-pole withdrawable construction supports switchboards where high fault-current capability, comprehensive LSIG protection and convenient servicing are required.

Key Advantages

  • 800 A rated current for substantial low-voltage distribution loads.
  • Four-pole configuration for comprehensive switching and circuit protection.
  • Ekip Dip LSIG electronic trip unit with adjustable protection settings.
  • Long-time, short-time, instantaneous and earth-fault protection.
  • 66 kA ultimate short-circuit breaking capacity at 440 V AC.
  • 66 kA rated short-time withstand current for 1 s.
  • Withdrawable moving-part design facilitates inspection, servicing and replacement.
  • Part of the modular ABB SACE Emax 2 air circuit breaker platform.

Key Features

  • ABB SACE Emax 2 E2.2N air circuit breaker moving part.
  • 800 A rated uninterrupted current.
  • 4-pole construction.
  • Ekip Dip LSIG electronic protection release.
  • Long-time overload protection.
  • Short-time delayed short-circuit protection.
  • Instantaneous short-circuit protection.
  • Integrated earth-fault protection.
  • Protection settings configured through DIP switches.
  • Short-time protection supports selective coordination.
  • 66 kA Icu at 440 V AC.
  • 66 kA Icw for 1 s.
  • Withdrawable execution for use with the corresponding Emax 2 fixed part.
  • Designed for demanding low-voltage power distribution applications.

Comprehensive LSIG Protection for Low-Voltage Distribution

The ABB Ekip Dip LSIG release combines four essential protection functions within a practical electronic trip unit. Long-time protection responds to sustained overloads, short-time protection supports selective coordination between upstream and downstream devices, instantaneous protection rapidly interrupts severe short circuits, and earth-fault protection helps detect potentially damaging fault currents to earth.

The E2.2N platform combines this comprehensive protection with substantial short-circuit withstand capability. Its withdrawable construction allows the moving breaker to be separated from the corresponding fixed part for inspection and servicing, making it particularly suitable for switchboards where maintainability, selective coordination and continuity of electrical service are important.

Typical Applications

  • Main low-voltage distribution switchboards.
  • Industrial power distribution systems.
  • Commercial building electrical distribution.
  • Manufacturing and process facilities.
  • Transformer and feeder protection.
  • Infrastructure and utility installations.
  • Critical power distribution systems.
  • Withdrawable switchgear requiring comprehensive LSIG protection.

Technical Specifications

Series SACE Emax 2 E2.2
Order code 1SDA072873R1
Product group Emax2 Air Circuit Breaker
Product type Air circuit breaker moving part
Rated uninterrupted current 800 A
Number of poles 4
Performance level N
Trip unit Ekip Dip LSIG
Release type Electronic
Protection functions L, S, I, G
Ultimate short-circuit breaking capacity at 440 V AC 66 kA
Rated short-time withstand current (1 s) 66 kA
Overload protection adjustment 0.4–1 × In
Integrated earth-fault protection Yes
Construction Withdrawable
Main-circuit connection Connection through corresponding fixed part
Breaker frame E2.2
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA072873R1?

The ABB 1SDA072873R1 is an Emax 2 E2.2N four-pole withdrawable air circuit breaker moving part rated at 800 A and equipped with an Ekip Dip LSIG electronic trip unit.

What protection functions does the Ekip Dip LSIG provide?

The Ekip Dip LSIG provides long-time (L), short-time (S), instantaneous (I) and earth-fault (G) protection for comprehensive low-voltage circuit protection.

What is the breaking capacity of the E2.2N 800?

The E2.2N 800 has an ultimate short-circuit breaking capacity of 66 kA at 440 V AC and a rated short-time withstand current of 66 kA for 1 s.

Is the ABB 1SDA072873R1 fixed or withdrawable?

This model is a withdrawable moving part designed for installation with the corresponding ABB SACE Emax 2 fixed part.

What is the rated current of the ABB 1SDA072873R1?

The ABB 1SDA072873R1 has a rated uninterrupted current of 800 A and combines this rating with comprehensive Ekip Dip LSIG electronic protection.

Trusted Power Protection from ABB

ABB SACE Emax 2 air circuit breakers combine comprehensive electronic protection, high short-circuit performance and service-friendly withdrawable construction for demanding low-voltage power distribution systems.