ABB 1SDA072863R1 SACE Emax 2 E1.2N 1600 A four-pole withdrawable air circuit breaker with Ekip Dip LSIG electronic overload, short-circuit and ground-fault protection.
£7,403.21
The ABB 1SDA072863R1 is a SACE Emax 2 E1.2N air circuit breaker designed for protection and switching in demanding low-voltage electrical distribution systems. Rated at 1600 A, this four-pole withdrawable breaker combines ABB's compact E1.2N frame with an Ekip Dip LSIG electronic trip unit, providing Long-time, Short-time, Instantaneous and Ground-fault protection.
The E1.2N performance level provides a rated ultimate short-circuit breaking capacity of 66 kA at 380–440 V AC and 50 kA at 500–690 V AC. With a rated operational voltage of 690 V AC, rated insulation voltage of 1000 V AC and a frequency rating of 50/60 Hz, it is engineered for robust industrial, commercial and infrastructure power-distribution systems.
This model is supplied as a four-pole withdrawable moving part (WMP) for installation with the appropriate Emax 2 fixed part. The Ekip Dip LSIG R 1600 solid-state AC release uses DIP switches for protection adjustment, while four change-over auxiliary contacts and circuit-breaker open/closed indication support integration into switchboards and control systems.
The ABB SACE Emax 2 E1.2N combines strong short-circuit performance with the practical configuration of the Ekip Dip LSIG electronic release. Long-time protection responds to sustained overloads, Short-time protection supports selective coordination, Instantaneous protection responds rapidly to high-level short circuits, and Ground-fault protection addresses earth-fault conditions. Protection thresholds are configured locally using DIP switches.
With a 1600 A current rating and up to 66 kA ultimate short-circuit breaking capacity, the E1.2N is suited to demanding power-distribution networks where dependable fault interruption and coordination are required. Its withdrawable moving-part construction enables the breaker to be separated from the corresponding fixed chassis, supporting inspection, servicing and replacement in maintainable switchboard systems.
| Series | SACE Emax 2 |
|---|---|
| Frame / subtype | E1.2N |
| ABB order code | 1SDA072863R1 |
| EAN / GTIN | 8015644767136 |
| Product group | Emax2 Air Circuit Breaker |
| Product type | Air circuit breaker |
| Performance level | N |
| Rated current (In) | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Number of poles | 4P |
| Current type | AC |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated frequency | 50/60 Hz |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 50 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 50 kA |
| Trip unit | Ekip Dip LSIG |
| Release designation | Ekip Dip LSIG R 1600 |
| Release type | Solid-state electronic AC release |
| Protection functions | Long-time (L), Short-time (S), Instantaneous (I), Ground-fault (G) |
| Overload protection adjustment | 0.4–1 × In |
| Overload release current setting | 640–1600 A |
| Short-time protection adjustment | 0.6–10 × In |
| Short-time delayed short-circuit setting | 960–16000 A |
| Instantaneous protection adjustment | 1.5–15 × In |
| Instantaneous short-circuit setting | 2400–24000 A |
| Ground-fault protection adjustment | 0.1–1 × In |
| Integrated earth-fault protection | Yes |
| Protection setting method | DIP switches |
| Version | Withdrawable moving part (WMP) |
| Main-circuit connection | Through separate fixed part / chassis |
| Auxiliary contacts | 4 change-over contacts |
| Breaker position indication | Open / closed |
| Integrated motor drive | No |
| Optional motor drive | Yes |
| DIN-rail mounting | No |
| Standard | IEC 60947-2 |
The ABB 1SDA072863R1 is a 1600 A four-pole withdrawable air circuit breaker designed for switching and protecting demanding low-voltage electrical distribution systems.
The breaker is fitted with an Ekip Dip LSIG R 1600 solid-state electronic release, providing Long-time, Short-time, Instantaneous and Ground-fault protection with settings configured through DIP switches.
LSIG denotes Long-time, Short-time, Instantaneous and Ground-fault protection. Together these functions protect against sustained overloads, short-circuit faults and earth-fault conditions.
The E1.2N 1600 has a rated ultimate short-circuit breaking capacity of 66 kA at 380–440 V AC and 50 kA at 500–690 V AC.
The 1SDA072863R1 is a withdrawable moving-part (WMP) circuit breaker designed for use with the appropriate separate fixed part in an ABB SACE Emax 2 switchboard installation.
ABB SACE Emax 2 air circuit breakers combine high short-circuit performance, configurable electronic protection and flexible withdrawable construction to provide dependable switching, selective coordination and fault protection for demanding industrial, commercial and infrastructure power-distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.