1SDA072863R1 ABB E1.2N 1600 Ekip Dip LSIG 4P WMP Air Circuit Breaker

1SDA072863R1 ABB E1.2N 1600 Ekip Dip LSIG 4P WMP Air Circuit Breaker

ABB 1SDA072863R1 SACE Emax 2 E1.2N 1600 A four-pole withdrawable air circuit breaker with Ekip Dip LSIG electronic overload, short-circuit and ground-fault protection.

SKU: 1SDA072863R1MPN: 1SDA072863R1
Price
List Price £9,870.95 ex VAT
Your Price (ex VAT) Save 25%
£7,403.21 25% OFF
You save £2,467.74 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £7,403.21
Trade pricing is personalised to your account

Manufacturer Lead Time

£7,403.21

Why Choose the ABB E1.2N 1600 Ekip Dip LSIG 4p WMP Air Circuit Breaker?

The ABB 1SDA072863R1 is a SACE Emax 2 E1.2N air circuit breaker designed for protection and switching in demanding low-voltage electrical distribution systems. Rated at 1600 A, this four-pole withdrawable breaker combines ABB's compact E1.2N frame with an Ekip Dip LSIG electronic trip unit, providing Long-time, Short-time, Instantaneous and Ground-fault protection.

The E1.2N performance level provides a rated ultimate short-circuit breaking capacity of 66 kA at 380–440 V AC and 50 kA at 500–690 V AC. With a rated operational voltage of 690 V AC, rated insulation voltage of 1000 V AC and a frequency rating of 50/60 Hz, it is engineered for robust industrial, commercial and infrastructure power-distribution systems.

This model is supplied as a four-pole withdrawable moving part (WMP) for installation with the appropriate Emax 2 fixed part. The Ekip Dip LSIG R 1600 solid-state AC release uses DIP switches for protection adjustment, while four change-over auxiliary contacts and circuit-breaker open/closed indication support integration into switchboards and control systems.

Key Advantages

  • High-current 1600 A air circuit breaker for demanding low-voltage distribution systems.
  • Four-pole configuration for switching and protecting four-conductor systems.
  • Ekip Dip LSIG electronic trip unit provides overload, selective short-circuit, instantaneous and earth-fault protection.
  • 66 kA ultimate short-circuit breaking capacity at 380–440 V AC.
  • 50 kA ultimate short-circuit breaking capacity at 500–690 V AC.
  • Adjustable Short-time protection supports selective coordination with downstream protective devices.
  • Integrated Ground-fault (G) protection provides protection against earth-fault conditions.
  • DIP-switch adjustment provides straightforward local configuration of protection settings.
  • Withdrawable construction supports efficient inspection, servicing and replacement.
  • Four change-over auxiliary contacts support switchboard signalling and control-system integration.

Key Features

  • ABB SACE Emax 2 E1.2N air circuit breaker.
  • 1600 A rated uninterrupted current.
  • 4-pole configuration.
  • Ekip Dip LSIG R 1600 solid-state electronic AC release.
  • Long-time (L) overload protection.
  • Short-time (S) selective short-circuit protection.
  • Instantaneous (I) short-circuit protection.
  • Ground-fault (G) protection.
  • Overload protection adjustable from 0.4–1 × In.
  • Short-time protection adjustable from 0.6–10 × In.
  • Instantaneous protection adjustable from 1.5–15 × In.
  • Ground-fault protection adjustable from 0.1–1 × In.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 50/60 Hz rated frequency.
  • 66 kA Icu at 380–440 V AC.
  • 50 kA Icu at 500–690 V AC.
  • Four change-over auxiliary contacts.
  • Withdrawable moving-part construction for maintainable switchboard installations.

Selective LSIG Electronic Protection for Power Distribution

The ABB SACE Emax 2 E1.2N combines strong short-circuit performance with the practical configuration of the Ekip Dip LSIG electronic release. Long-time protection responds to sustained overloads, Short-time protection supports selective coordination, Instantaneous protection responds rapidly to high-level short circuits, and Ground-fault protection addresses earth-fault conditions. Protection thresholds are configured locally using DIP switches.

With a 1600 A current rating and up to 66 kA ultimate short-circuit breaking capacity, the E1.2N is suited to demanding power-distribution networks where dependable fault interruption and coordination are required. Its withdrawable moving-part construction enables the breaker to be separated from the corresponding fixed chassis, supporting inspection, servicing and replacement in maintainable switchboard systems.

Typical Applications

  • Main and distribution switchboards.
  • Industrial low-voltage power distribution systems.
  • Commercial building electrical distribution.
  • Manufacturing and process-control facilities.
  • Data centres and critical-power installations.
  • Infrastructure and utility distribution systems.
  • Transformer secondary distribution.
  • High-current feeders requiring selective short-circuit protection.
  • Four-pole circuits requiring comprehensive LSIG electronic protection.

Technical Specifications

Series SACE Emax 2
Frame / subtype E1.2N
ABB order code 1SDA072863R1
EAN / GTIN 8015644767136
Product group Emax2 Air Circuit Breaker
Product type Air circuit breaker
Performance level N
Rated current (In) 1600 A
Rated uninterrupted current (Iu) 1600 A
Number of poles 4P
Current type AC
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated frequency 50/60 Hz
Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500/525 V AC 50 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 50 kA
Trip unit Ekip Dip LSIG
Release designation Ekip Dip LSIG R 1600
Release type Solid-state electronic AC release
Protection functions Long-time (L), Short-time (S), Instantaneous (I), Ground-fault (G)
Overload protection adjustment 0.4–1 × In
Overload release current setting 640–1600 A
Short-time protection adjustment 0.6–10 × In
Short-time delayed short-circuit setting 960–16000 A
Instantaneous protection adjustment 1.5–15 × In
Instantaneous short-circuit setting 2400–24000 A
Ground-fault protection adjustment 0.1–1 × In
Integrated earth-fault protection Yes
Protection setting method DIP switches
Version Withdrawable moving part (WMP)
Main-circuit connection Through separate fixed part / chassis
Auxiliary contacts 4 change-over contacts
Breaker position indication Open / closed
Integrated motor drive No
Optional motor drive Yes
DIN-rail mounting No
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA072863R1 used for?

The ABB 1SDA072863R1 is a 1600 A four-pole withdrawable air circuit breaker designed for switching and protecting demanding low-voltage electrical distribution systems.

What protection release is fitted to the ABB 1SDA072863R1?

The breaker is fitted with an Ekip Dip LSIG R 1600 solid-state electronic release, providing Long-time, Short-time, Instantaneous and Ground-fault protection with settings configured through DIP switches.

What does LSIG mean on the Ekip Dip trip unit?

LSIG denotes Long-time, Short-time, Instantaneous and Ground-fault protection. Together these functions protect against sustained overloads, short-circuit faults and earth-fault conditions.

What is the breaking capacity of the ABB E1.2N 1600?

The E1.2N 1600 has a rated ultimate short-circuit breaking capacity of 66 kA at 380–440 V AC and 50 kA at 500–690 V AC.

Is the ABB 1SDA072863R1 a fixed or withdrawable circuit breaker?

The 1SDA072863R1 is a withdrawable moving-part (WMP) circuit breaker designed for use with the appropriate separate fixed part in an ABB SACE Emax 2 switchboard installation.

Trusted Protection for Low-Voltage Distribution

ABB SACE Emax 2 air circuit breakers combine high short-circuit performance, configurable electronic protection and flexible withdrawable construction to provide dependable switching, selective coordination and fault protection for demanding industrial, commercial and infrastructure power-distribution systems.