ABB 1SDA072860R1 SACE Emax 2 E1.2C 1600 four-pole withdrawable air circuit breaker moving part with Ekip G Hi-Touch LSIG electronic protection, 1600 A rated current and 50 kA breaking capacity at 380–440 V AC.
£8,456.50
The ABB 1SDA072860R1 is a high-performance SACE Emax 2 E1.2C air circuit breaker designed for advanced generator protection, measurement and control in demanding low-voltage electrical systems. Configured as an E1.2C 1600 Ekip G Hi-Touch LSIG 4p WMP, this four-pole withdrawable moving part combines a 1600 A rated current with ABB's advanced Ekip G Hi-Touch LSIG electronic protection release.
The Ekip G Hi-Touch LSIG release combines long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection with additional functions developed for generator applications. Integrated Ekip Measuring Pro and Network Analyzer functionality provides advanced electrical measurement and power-quality analysis, while the touch-sensitive display provides an intuitive interface for configuration and monitoring.
The E1.2C performance level provides a rated ultimate short-circuit breaking capacity of 50 kA at 380–440 V AC and 42 kA at 500–690 V AC. With a rated operational voltage of 690 V AC, rated insulation voltage of 1000 V AC and four-pole withdrawable construction, the 1SDA072860R1 is suited to generator switchboards and other critical power-distribution applications requiring comprehensive protection and advanced monitoring.
The ABB SACE Emax 2 E1.2C provides comprehensive protection for low-voltage generator and distribution systems against overloads, short circuits and earth faults. With a 1600 A rated current and breaking capacity of 50 kA at 380–440 V AC, this configuration combines substantial fault interruption performance with the specialised protection capabilities required in demanding generator applications.
The Ekip G Hi-Touch LSIG release extends conventional LSIG protection with generator-specific functions, advanced electrical measurement and real-time network analysis. Integrated Ekip Measuring Pro and Network Analyzer functionality supports detailed supervision of electrical parameters and power quality, while the touchscreen interface provides convenient access to protection configuration, measurements and operating information.
| Series | SACE Emax 2 |
|---|---|
| Frame | E1.2C |
| Order code / MPN | 1SDA072860R1 |
| EAN | 8015644767105 |
| Product group | Emax2 Air Circuit Breaker |
| Product type | Air circuit breaker |
| Construction | Withdrawable moving part |
| Number of poles | 4 |
| Neutral pole current | 100% of Iu |
| Rated current | 1600 A |
| Current type | AC |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Frequency | 50 / 60 Hz |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 50 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC | 50 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 50 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 42 kA |
| Protection release | Ekip G Hi-Touch LSIG |
| Release type | Electronic |
| Protection functions | Long-time, short-time, instantaneous and earth-fault (LSIG) |
| Overload protection setting | 0.4–1 × In |
| Overload release current setting | 640–1600 A |
| Short-time selective protection setting | 0.6–10 × In |
| Short-time delayed short-circuit setting | 960–16000 A |
| Instantaneous protection setting | 1.5–15 × In |
| Instantaneous short-circuit setting | 2400–24000 A |
| Earth-fault protection setting | 0.1–1 × In |
| Earth-fault protection | Integrated |
| Generator-specific protection | Integrated |
| Measurement module | Ekip Measuring Pro |
| Network analysis | Integrated Network Analyzer |
| User interface | Touch-sensitive display |
| Mechanical durability | 20,000 cycles |
| Power loss | 400 W |
| Product net width | 348 mm |
| Product net height | 363.5 mm |
| Product net depth | 271 mm |
| Product net weight | 20 kg |
| Standard | IEC 60947-2 |
| Product family | Emax 2 Air Circuit Breakers |
The ABB 1SDA072860R1 is an Emax 2 air circuit breaker moving part designed for advanced protection, monitoring and control of low-voltage generator and power-distribution systems against overloads, short circuits and earth faults.
The breaker has a rated current of 1600 A, making it suitable for substantial generator, industrial, commercial and infrastructure power-system loads.
The E1.2C 1600 provides a rated ultimate short-circuit breaking capacity of 50 kA at 380–440 V AC and 42 kA at 500–690 V AC, providing robust fault interruption across demanding low-voltage applications.
This model is fitted with the advanced ABB Ekip G Hi-Touch LSIG electronic release, providing long-time, short-time, instantaneous and earth-fault protection together with generator-specific protection, Ekip Measuring Pro and Network Analyzer functionality.
The 1SDA072860R1 is a four-pole withdrawable moving part for the Emax 2 E1.2C circuit breaker system and is designed for use with the corresponding fixed part in a low-voltage switchboard.
ABB SACE Emax 2 air circuit breakers combine high fault interruption performance with generator-specific electronic protection, advanced electrical measurement, power-quality analysis and maintainable withdrawable construction for demanding low-voltage power systems.