Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072856R1 is an Emax 2 E1.2C 1600 A four-pole withdrawable air circuit breaker moving part with an Ekip Touch LSIG electronic trip unit providing overload, short-circuit and earth-fault protection for low-voltage power distribution.
£5,492.21
The ABB 1SDA072856R1 is a high-performance Emax 2 E1.2C 1600 A four-pole air circuit breaker moving part designed for protection and control in low-voltage electrical distribution systems. As part of the advanced ABB SACE Emax 2 air circuit breaker series, it combines withdrawable construction with the intelligent Ekip Touch LSIG electronic trip unit for comprehensive circuit protection.
This E1.2C circuit breaker is engineered for demanding industrial, commercial and infrastructure power distribution applications. The Ekip Touch LSIG release provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection, delivering comprehensive protection for electrical distribution networks while allowing protection parameters to be configured through its touchscreen interface.
With a rated current of 1600 A, a four-pole configuration and an ultimate short-circuit breaking capacity of 50 kA at 400–415 V AC, the 1SDA072856R1 provides dependable protection for high-current distribution circuits. Its withdrawable moving-part design enables integration with the appropriate Emax 2 E1.2 fixed part and facilitates inspection, servicing and replacement within switchgear assemblies.
Air circuit breakers such as the ABB Emax 2 E1.2C provide switching, isolation and protection for high-current low-voltage distribution circuits. They are suited to main switchboards, industrial distribution systems and other installations where dependable interruption of overload and short-circuit currents is essential for maintaining electrical safety and system availability.
The Ekip Touch LSIG trip unit provides four key protection functions: long-time overload protection, short-time selective short-circuit protection, instantaneous short-circuit protection and earth-fault protection. This comprehensive protection package makes the 1SDA072856R1 particularly suitable for distribution systems requiring protection against both phase faults and faults to earth, while its withdrawable architecture helps simplify maintenance and switchgear servicing.
| Series | SACE Emax 2 |
|---|---|
| Frame | E1.2 |
| Performance level | C |
| ABB order code / MPN | 1SDA072856R1 |
| Product type | Air circuit breaker moving part |
| Rated current | 1600 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V AC |
| Frequency | 50 / 60 Hz |
| Number of poles | 4 |
| Trip unit | Ekip Touch LSIG |
| Protection functions | LSIG – overload, selective short-circuit, instantaneous short-circuit and earth-fault protection |
| Overload protection adjustment | 0.4–1 × In |
| Instantaneous protection adjustment | 1.5–15 × In |
| Earth-fault protection adjustment | 0.1–1 × In |
| Ultimate short-circuit breaking capacity (Icu) at 380 V AC | 50 kA |
| Ultimate short-circuit breaking capacity (Icu) at 400–415 V AC | 50 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 50 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500–525 V AC | 42 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 42 kA |
| Current type | AC |
| Execution | Withdrawable moving part (WMP) |
| Installation | Withdrawable |
| Applicable standard | IEC 60947-2 |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA072856R1 is an Emax 2 air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution circuits in industrial, commercial and infrastructure applications.
The E1.2C 1600 has a rated current of 1600 A and is supplied in a four-pole configuration.
The Ekip Touch LSIG electronic trip unit provides long-time overload protection (L), short-time selective short-circuit protection (S), instantaneous short-circuit protection (I) and earth-fault protection (G).
The E1.2C has an ultimate short-circuit breaking capacity of 50 kA at 400–415 V AC. Its Icu rating is also 50 kA at 380 V AC and 440 V AC, reducing to 42 kA at 500–525 V AC and 690 V AC.
The 1SDA072856R1 is the withdrawable moving part (WMP) of an ABB Emax 2 circuit-breaker system and is designed for installation with the appropriate E1.2 fixed part.
ABB SACE Emax 2 air circuit breakers provide advanced protection and control for modern low-voltage power distribution systems, combining high breaking performance, intelligent electronic protection and flexible switchgear integration.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.