1SDA072855R1 ABB Emax 2 E1.2C 1600 Ekip Touch LSI 4-Pole Air Circuit Breaker

1SDA072855R1 ABB Emax 2 E1.2C 1600 Ekip Touch LSI 4-Pole Air Circuit Breaker

ABB 1SDA072855R1 is an Emax 2 E1.2C 1600 A four-pole withdrawable air circuit breaker moving part with an Ekip Touch LSI electronic trip unit for low-voltage power distribution protection.

SKU: 1SDA072855R1MPN: 1SDA072855R1
Price
List Price £6,660.89 ex VAT
Your Price (ex VAT) Save 25%
£4,995.67 25% OFF
You save £1,665.22 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £4,995.67
Trade pricing is personalised to your account

Manufacturer Lead Time

£4,995.67

Why Choose the ABB 1SDA072855R1 Emax 2 Air Circuit Breaker?

The ABB 1SDA072855R1 is a high-performance Emax 2 E1.2C 1600 A four-pole air circuit breaker moving part designed for protection and control in low-voltage electrical distribution systems. As part of the advanced ABB SACE Emax 2 air circuit breaker series, it combines a withdrawable construction with the intelligent Ekip Touch LSI electronic trip unit for comprehensive circuit protection.

This E1.2C circuit breaker is engineered for demanding industrial, commercial and infrastructure power distribution applications. The Ekip Touch LSI release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection, while its touchscreen interface supports straightforward configuration and monitoring of protection settings.

With a rated current of 1600 A, a four-pole configuration and a rated ultimate short-circuit breaking capacity of 50 kA at 400–440 V AC, the 1SDA072855R1 provides dependable protection for high-current distribution circuits. Its withdrawable moving-part design enables integration with the appropriate Emax 2 E1.2 fixed part and facilitates efficient inspection, servicing and replacement within switchgear assemblies.

Key Advantages

  • High-performance ABB Emax 2 air circuit breaker moving part for low-voltage power distribution.
  • 1600 A rated current for demanding high-current installations.
  • Four-pole configuration for three-phase and neutral circuit protection.
  • 50 kA ultimate short-circuit breaking capacity at 400–440 V AC.
  • Advanced Ekip Touch LSI electronic trip unit.
  • LSI protection provides overload, short-time and instantaneous short-circuit protection.
  • Withdrawable construction supports efficient switchboard maintenance and servicing.
  • Designed for integration into ABB Emax 2 low-voltage switchgear and power distribution systems.

Key Features

  • ABB SACE Emax 2 E1.2C series.
  • 1600 A rated current.
  • Four-pole air circuit breaker moving part.
  • Ekip Touch LSI solid-state electronic protection release.
  • Long-time overload (L) protection.
  • Short-time short-circuit (S) protection.
  • Instantaneous short-circuit (I) protection.
  • 50 kA Icu at 400–440 V AC.
  • 42 kA rated short-time withstand current for 1 s.
  • 690 V AC rated operational voltage.
  • Withdrawable moving-part configuration for Emax 2 switchgear.
  • Fitted with four auxiliary changeover contacts and circuit-breaker open/closed position indication.

Advanced Protection for Low-Voltage Power Distribution

Air circuit breakers such as the ABB Emax 2 E1.2C provide switching, isolation and protection for high-current low-voltage distribution circuits. They are suited to main switchboards, industrial distribution systems and other installations where dependable interruption of overload and short-circuit currents is essential for equipment and system protection.

The Ekip Touch LSI trip unit combines long-time overload, short-time short-circuit and instantaneous protection with an intuitive touchscreen interface. The withdrawable Emax 2 architecture allows the circuit breaker moving part to be separated from its fixed chassis, helping simplify inspection, maintenance and replacement in critical electrical distribution systems.

Typical Applications

  • Main low-voltage electrical distribution switchboards.
  • Industrial power distribution systems.
  • Commercial and infrastructure electrical installations.
  • Manufacturing and process plants.
  • Power distribution and switchgear assemblies.
  • Generator and transformer distribution systems.
  • Building services and critical power installations.

Technical Specifications

Series SACE Emax 2
Frame E1.2
Performance level C
ABB order code / MPN 1SDA072855R1
Product type Air circuit breaker moving part
Rated current 1600 A
Rated operational voltage 690 V AC
Rated insulation voltage 1000 V AC
Rated impulse withstand voltage 12 kV
Number of poles 4
Neutral pole current 100% of rated current
Trip unit Ekip Touch LSI
Protection functions LSI – overload, short-time and instantaneous short-circuit protection
Ultimate short-circuit breaking capacity (Icu) at 400–440 V AC 50 kA
Rated short-time withstand current (Icw, 1 s) 42 kA
Current type AC
Execution Withdrawable moving part (WMP)
Auxiliary contacts 4 changeover contacts
Protection rating IP30
Power loss 400 W
Mechanical durability 20,000 operating cycles
Dimensions (H × W × D) 363.5 × 348 × 271 mm
Weight 20 kg
EAN 8015644767051
Product group Emax2 Air Circuit Breaker

Frequently Asked Questions

What is the ABB 1SDA072855R1 used for?

The ABB 1SDA072855R1 is an Emax 2 air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution circuits in industrial, commercial and infrastructure applications.

What is the current rating of the ABB 1SDA072855R1?

The E1.2C 1600 has a rated current of 1600 A and is supplied in a four-pole configuration.

What protection functions does the Ekip Touch LSI trip unit provide?

The Ekip Touch LSI electronic trip unit provides long-time overload protection (L), short-time short-circuit protection (S) and instantaneous short-circuit protection (I).

What is the breaking capacity of the E1.2C 1600?

The E1.2C performance level provides an ultimate short-circuit breaking capacity of 50 kA at 400–440 V AC and a rated short-time withstand current of 42 kA for 1 s.

Is the ABB 1SDA072855R1 a fixed or withdrawable circuit breaker?

The 1SDA072855R1 is the withdrawable moving part (WMP) of an ABB Emax 2 circuit-breaker system and is designed for use with the appropriate E1.2 fixed part.

Trusted Low-Voltage Protection from ABB

ABB SACE Emax 2 air circuit breakers provide advanced protection and control for modern low-voltage power distribution systems, combining high breaking performance, intelligent electronic trip units and flexible switchgear integration.