1SDA072817R1 ABB Emax 2 E1.2C 1250 Ekip G Touch LSIG 4-Pole Air Circuit Breaker

1SDA072817R1 ABB Emax 2 E1.2C 1250 Ekip G Touch LSIG 4-Pole Air Circuit Breaker

ABB 1SDA072817R1 is a SACE Emax 2 E1.2C 1250 four-pole withdrawable air circuit breaker moving part rated at 1250 A and equipped with an Ekip G Touch LSIG solid-state electronic protection release for generator and low-voltage distribution applications.

SKU: 1SDA072817R1MPN: 1SDA072817R1
Price
List Price £9,329.23 ex VAT
Your Price (ex VAT) Save 25%
£6,996.92 25% OFF
You save £2,332.31 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £6,996.92
Trade pricing is personalised to your account

Manufacturer Lead Time

£6,996.92

Why Choose the ABB 1SDA072817R1 Emax 2 E1.2C 1250 Air Circuit Breaker?

The ABB 1SDA072817R1 is a SACE Emax 2 E1.2C air circuit breaker engineered for generator and low-voltage power distribution protection. Configured as the E1.2C 1250 Ekip G Touch LSIG 4p WMP, this four-pole withdrawable moving part combines a 1250 A rated uninterrupted current with ABB's advanced Ekip G Touch LSIG solid-state electronic protection release.

The Ekip G Touch LSIG release provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection, with the Ekip G platform specifically developed to support generator protection applications. Adjustable electronic protection functions allow the breaker to be coordinated with the electrical system while providing comprehensive protection against overload, short-circuit and earth-fault conditions.

The E1.2C performance level provides an ultimate short-circuit breaking capacity of 50 kA at 400 V AC and a rated short-time withstand current of 42 kA for 1 s. The breaker is rated at 690 V AC and uses a four-pole withdrawable moving-part construction with main-circuit connection through a separate chassis part, supporting convenient inspection and maintenance.

Key Advantages

  • 1250 A rated uninterrupted current for substantial generator and distribution loads.
  • Four-pole configuration for switching and protection across four conductors.
  • Advanced Ekip G Touch LSIG electronic protection release for generator-oriented applications.
  • Long-time, short-time, instantaneous and ground-fault protection in one electronic trip unit.
  • 50 kA ultimate short-circuit breaking capacity at 400 V AC.
  • 42 kA short-time withstand current for 1 s supports selective protection strategies.
  • Withdrawable moving-part construction supports efficient switchboard inspection, servicing and replacement.

Key Features

  • ABB SACE Emax 2 E1.2 air circuit breaker platform.
  • 1250 A rated uninterrupted current.
  • Four-pole configuration.
  • C short-circuit performance level.
  • Ekip G Touch LSIG solid-state electronic protection release.
  • Long-time (L) overload protection.
  • Short-time (S) short-circuit protection.
  • Instantaneous (I) short-circuit protection.
  • Integrated ground-fault (G) protection.
  • 50 kA Icu at 400 V AC.
  • 42 kA Icw for 1 s.
  • Rated voltage of 690 V AC.
  • Overload release adjustment range of 500–1250 A.
  • Short-time delayed short-circuit adjustment range of 750–12500 A.
  • Instantaneous short-circuit adjustment range of 1875–18750 A.
  • Four auxiliary change-over contacts.
  • IP30 degree of protection.
  • Withdrawable moving part (WMP) configuration.

Generator-Focused LSIG Protection for Low-Voltage Power Systems

The ABB SACE Emax 2 E1.2C provides switching and electronic protection for low-voltage generator and distribution systems. Its Ekip G Touch release monitors electrical conditions and initiates circuit interruption when configured protection thresholds are exceeded, helping protect generators, conductors, switchgear and connected equipment against overload, short-circuit and ground-fault conditions.

The Ekip G Touch LSIG release combines long-time overload, short-time delayed short-circuit, instantaneous short-circuit and ground-fault protection within ABB's generator-oriented Ekip G platform. Together with the 1250 A E1.2C frame, 50 kA breaking capacity at 400 V AC and withdrawable architecture, the ABB 1SDA072817R1 provides a robust solution for generator switchboards and demanding low-voltage distribution applications.

Typical Applications

  • Generator protection and generator switchboards.
  • Low-voltage main distribution switchboards.
  • Industrial power generation and distribution systems.
  • Manufacturing and process facilities.
  • Commercial and infrastructure standby power systems.
  • Distribution systems requiring integrated ground-fault protection.

Technical Specifications

Series SACE Emax 2
ABB order code 1SDA072817R1
EAN 8015644766672
Product type Air circuit breaker moving part
Product group Emax2 Air Circuit Breaker
Frame E1.2
Short-circuit performance level C
Rated uninterrupted current (Iu) 1250 A
Number of poles 4
Rated voltage 690 V AC
Protection release Ekip G Touch LSIG
Release type Solid-state electronic
Protection functions L, S, I and G
Long-time overload protection Yes
Short-time short-circuit protection Yes
Instantaneous short-circuit protection Yes
Integrated ground-fault protection Yes
Overload release current setting 500–1250 A
Short-time delayed short-circuit release setting 750–12500 A
Instantaneous short-circuit release setting 1875–18750 A
Ultimate short-circuit breaking capacity (Icu) at 400 V AC 50 kA
Short-time withstand current (Icw) 42 kA for 1 s
Construction Withdrawable moving part
Configuration WMP
Main circuit connection Connection through separate chassis part
Auxiliary contacts 4 change-over contacts
Open / closed indication Yes
Trip indication Yes
Degree of protection IP30
Motor drive integrated No
Motor drive optional Yes
Integrated undervoltage release No
Product net weight 20 kg
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA072817R1?

The ABB 1SDA072817R1 is an Emax 2 E1.2C 1250 four-pole withdrawable air circuit breaker moving part equipped with an Ekip G Touch LSIG solid-state electronic protection release.

What is the rated current of the ABB E1.2C 1250?

The ABB 1SDA072817R1 has a rated uninterrupted current of 1250 A.

What protection functions does the Ekip G Touch LSIG release provide?

The LSIG configuration provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection, with the Ekip G Touch platform designed to support generator protection applications.

Does the ABB 1SDA072817R1 include ground-fault protection?

Yes. The Ekip G Touch LSIG release includes integrated ground-fault protection in addition to its long-time, short-time and instantaneous overcurrent protection functions.

What is the breaking capacity of the ABB 1SDA072817R1?

The E1.2C configuration has an ultimate short-circuit breaking capacity of 50 kA at 400 V AC.

What is the short-time withstand current of the ABB E1.2C 1250?

The E1.2C 1250 configuration has a rated short-time withstand current of 42 kA for 1 s.

Is the ABB 1SDA072817R1 fixed or withdrawable?

It is a withdrawable moving-part (WMP) configuration with its main circuit connected through the corresponding separate Emax 2 chassis part.

Trusted by Electrical Engineers Worldwide

ABB SACE Emax 2 air circuit breakers are engineered for the protection, control and management of low-voltage power systems, combining advanced electronic protection, robust short-circuit performance and flexible withdrawable construction for generator, industrial, commercial and infrastructure applications.