1SDA072814R1 ABB E1.2C 1250 Ekip Touch LI 4p WMP Air Circuit Breaker

1SDA072814R1 ABB E1.2C 1250 Ekip Touch LI 4p WMP Air Circuit Breaker

ABB 1SDA072814R1 is an Emax 2 E1.2C 1250 A four-pole withdrawable air circuit breaker moving part with an Ekip Touch LI electronic trip unit for advanced overload and instantaneous short-circuit protection.

SKU: 1SDA072814R1MPN: 1SDA072814R1
Price
List Price £5,116.06 ex VAT
Your Price (ex VAT) Save 25%
£3,837.05 25% OFF
You save £1,279.02 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £3,837.05
Trade pricing is personalised to your account

Manufacturer Lead Time

£3,837.05

Why Choose the ABB E1.2C 1250 Ekip Touch LI 4p WMP Air Circuit Breaker?

The ABB E1.2C 1250 Ekip Touch LI 4p WMP, order code 1SDA072814R1, is a high-performance four-pole withdrawable air circuit breaker moving part designed for protection and switching in low-voltage power distribution systems. Part of the ABB SACE Emax 2 E1.2 series, it combines a 1250 A rated current with an Ekip Touch LI electronic trip unit for advanced overload and instantaneous short-circuit protection.

The Ekip Touch LI solid-state electronic release provides long-time overload and instantaneous short-circuit protection. Protection thresholds can be configured through the touch-sensitive display, with overload protection adjustable from 0.4–1 × In and instantaneous protection from 1.5–15 × In, supporting precise coordination with the electrical distribution system.

The E1.2C performance level provides an ultimate short-circuit breaking capacity of 50 kA at 400/415 V AC and 42 kA at 690 V AC, with a rated short-time withstand current of 42 kA for 1 s. Its withdrawable moving-part construction enables convenient servicing and replacement when installed with the corresponding ABB Emax 2 fixed chassis.

Key Advantages

  • 1250 A rated current for demanding low-voltage power distribution.
  • Four-pole configuration for comprehensive switching and circuit protection.
  • Ekip Touch LI electronic trip unit with intuitive touch-sensitive display.
  • Adjustable long-time overload and instantaneous short-circuit protection.
  • 50 kA ultimate short-circuit breaking capacity at 400/415 V AC.
  • Protection settings adjustable to suit distribution-system requirements.
  • Withdrawable moving-part design facilitates inspection, servicing and replacement.
  • Part of the modular ABB SACE Emax 2 air circuit breaker platform.

Key Features

  • ABB SACE Emax 2 E1.2C air circuit breaker moving part.
  • 1250 A rated uninterrupted current.
  • 4-pole construction.
  • Ekip Touch LI solid-state electronic protection release.
  • Long-time overload protection.
  • Instantaneous short-circuit protection.
  • Overload release adjustable from 500–1250 A.
  • Instantaneous short-circuit release adjustable from 1875–18750 A.
  • Touch-sensitive display for protection configuration.
  • 690 V AC rated operational voltage.
  • Withdrawable execution for use with the corresponding Emax 2 fixed part.
  • Four auxiliary changeover contacts.
  • Circuit breaker open/closed position indication.
  • Optional motor operator capability.

Advanced Electronic Protection and Control

The ABB Ekip Touch platform combines electronic circuit protection with an intuitive touch-sensitive interface for straightforward configuration and supervision. On this LI version, long-time protection safeguards the circuit against sustained overloads while instantaneous protection provides rapid tripping when severe short-circuit currents occur.

The withdrawable E1.2 construction is particularly suitable for switchboards where maintainability and operational flexibility are important. The moving breaker can be separated from its corresponding fixed chassis for inspection or servicing, while auxiliary contacts and open/closed position indication support integration with switchboard signalling and control systems.

Typical Applications

  • Main low-voltage distribution switchboards.
  • Industrial power distribution systems.
  • Commercial building electrical distribution.
  • Manufacturing and process facilities.
  • Transformer and feeder protection.
  • Infrastructure and utility installations.
  • Critical power distribution systems.
  • Withdrawable switchgear requiring advanced electronic LI protection.

Technical Specifications

Series SACE Emax 2 E1.2
Order code 1SDA072814R1
Product type Air circuit breaker moving part
Rated current 1250 A
Rated operational voltage 690 V AC
Rated insulation voltage 1000 V AC
Frequency 50 / 60 Hz
Number of poles 4
Performance level C
Trip unit Ekip Touch LI
Release type Solid-state electronic
Protection functions L, I
Ultimate short-circuit breaking capacity at 380 V AC 50 kA
Ultimate short-circuit breaking capacity at 400/415 V AC 50 kA
Ultimate short-circuit breaking capacity at 440 V AC 50 kA
Ultimate short-circuit breaking capacity at 500/525 V AC 42 kA
Ultimate short-circuit breaking capacity at 690 V AC 42 kA
Rated short-time withstand current (1 s) 42 kA
Overload release adjustment range 500–1250 A
Instantaneous short-circuit release adjustment range 1875–18750 A
Integrated earth-fault protection No
Construction Withdrawable
Main-circuit connection Connection through separate fixed chassis
Auxiliary changeover contacts 4
Motor operator Optional
Standard IEC 60947-2
EAN 8015644766641

Frequently Asked Questions

What is the ABB 1SDA072814R1?

The ABB 1SDA072814R1 is an Emax 2 E1.2C four-pole withdrawable air circuit breaker moving part rated at 1250 A and equipped with an Ekip Touch LI solid-state electronic trip unit.

What protection functions does the Ekip Touch LI provide?

The Ekip Touch LI provides long-time overload (L) and instantaneous short-circuit (I) protection, with adjustable electronic protection settings configured through its touch-sensitive display.

What is the breaking capacity of the E1.2C 1250?

The E1.2C 1250 provides an ultimate short-circuit breaking capacity of 50 kA at 400/415 V AC and 42 kA at 690 V AC.

Is the ABB 1SDA072814R1 fixed or withdrawable?

This model is a withdrawable moving part designed for use with the corresponding ABB SACE Emax 2 fixed chassis.

What are the protection adjustment ranges of the ABB 1SDA072814R1?

The overload release is adjustable from 500–1250 A, while the instantaneous short-circuit release is adjustable from 1875–18750 A.

Trusted Power Protection from ABB

ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, intuitive control and service-friendly withdrawable construction for demanding low-voltage power distribution systems.