Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072812R1 SACE Emax 2 E1.2C 1250 four-pole withdrawable air circuit breaker moving part with Ekip Dip LSI electronic protection, 1250 A rated current and 50 kA breaking capacity at 380–440 V AC.
£4,092.84
The ABB 1SDA072812R1 is a high-performance SACE Emax 2 E1.2C air circuit breaker designed for reliable protection and control of low-voltage electrical distribution systems. Configured as an E1.2C 1250 Ekip Dip LSI 4p WMP, this four-pole withdrawable moving part combines a 1250 A rated current with ABB's Ekip Dip LSI electronic protection release.
As part of the ABB SACE Emax 2 air circuit breaker series, the E1.2C is engineered for demanding industrial, commercial and infrastructure power distribution applications. The Ekip Dip LSI trip unit provides adjustable long-time overload, short-time selective short-circuit and instantaneous short-circuit protection, with settings configured through straightforward DIP switches.
The E1.2C performance level provides a rated ultimate short-circuit breaking capacity of 50 kA at 380–440 V AC and 42 kA at 500–690 V AC. Its 1250 A rating, four-pole configuration and withdrawable construction make the 1SDA072812R1 well suited to substantial switchboard applications where dependable fault interruption, protection selectivity and convenient maintenance are required.
Air circuit breakers such as the ABB SACE Emax 2 E1.2C protect low-voltage electrical distribution systems against potentially damaging overload and short-circuit conditions while providing dependable switching and isolation. With a 50 kA breaking capacity at 380–440 V AC, this E1.2C configuration provides robust fault interruption for substantial switchboards, feeders and connected electrical equipment.
The Ekip Dip LSI electronic trip unit adds adjustable short-time protection between the long-time overload and instantaneous protection stages. This enables improved coordination and selectivity between protective devices, while the DIP-switch interface and Emax 2 withdrawable architecture provide a practical combination of straightforward configuration, dependable protection and convenient maintenance.
| Series | SACE Emax 2 |
|---|---|
| Frame | E1.2C |
| Order code / MPN | 1SDA072812R1 |
| EAN | 8015644766627 |
| Product group | Emax2 Air Circuit Breaker |
| Product type | Air circuit breaker |
| Construction | Withdrawable moving part |
| Number of poles | 4 |
| Rated current | 1250 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50 / 60 Hz |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 50 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC | 50 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 50 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC | 42 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 42 kA |
| Protection release | Ekip Dip LSI |
| Release type | Solid-state electronic |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Overload protection setting | 0.4–1 × In |
| Overload release current setting | 500–1250 A |
| Short-time selective protection setting | 0.6–10 × In |
| Short-time delayed short-circuit setting | 750–12500 A |
| Instantaneous protection setting | 1.5–15 × In |
| Instantaneous short-circuit setting | 1875–18750 A |
| Protection adjustment | DIP switches |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Product net width | 348 mm |
| Product net height | 363.5 mm |
| Product net depth | 271 mm |
| Product net weight | 14 kg |
| Mechanical durability | 20,000 cycles |
| Electrical durability up to 440 V | 8,000 cycles |
| Electrical durability at 500–690 V | 6,500 cycles |
| Standard | IEC 60947-2 |
| Product family | Emax 2 Air Circuit Breakers |
The ABB 1SDA072812R1 is an Emax 2 air circuit breaker moving part designed to protect and control low-voltage electrical distribution systems against overloads and short circuits.
The breaker has a rated current of 1250 A, making it suitable for substantial industrial, commercial and infrastructure power distribution loads.
The E1.2C 1250 provides a rated ultimate short-circuit breaking capacity of 50 kA at 380–440 V AC and 42 kA at 500–690 V AC, supporting dependable fault interruption across demanding low-voltage distribution applications.
This model is fitted with the ABB Ekip Dip LSI electronic release, providing adjustable long-time overload, short-time selective short-circuit and instantaneous short-circuit protection with DIP-switch configuration.
The 1SDA072812R1 is a four-pole withdrawable moving part for the Emax 2 E1.2C circuit breaker system and is designed for use with the corresponding fixed part in a low-voltage switchboard.
ABB SACE Emax 2 air circuit breakers combine dependable high-current fault interruption with configurable electronic protection and maintainable withdrawable construction for demanding industrial, commercial and infrastructure low-voltage distribution systems.
We use cookies