Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072810R1 SACE Emax 2 E1.2B 1250 A four-pole withdrawable air circuit breaker mobile part with Ekip G Hi-Touch LSIG electronic protection, 690 V AC rated operational voltage, 42 kA short-circuit breaking capacity and integrated earth-fault protection.
£7,358.03
The ABB 1SDA072810R1 is a SACE Emax 2 E1.2B air circuit breaker (ACB) designed for advanced generator and low-voltage power distribution protection. Rated at 1250 A, this four-pole breaker combines ABB’s compact E1.2B frame with an Ekip G Hi-Touch LSIG electronic trip unit, providing long-time overload, short-time delayed, instantaneous short-circuit and earth-fault protection.
The Ekip G Hi-Touch release extends ABB’s advanced Hi-Touch protection and monitoring platform with functions suited to generator applications. It combines comprehensive LSIG circuit protection with advanced measurement, monitoring and power-management capabilities, making this configuration particularly suitable for generator incomers, standby generation systems and installations where generator and distribution protection must be coordinated.
The 1SDA072810R1 is a four-pole withdrawable mobile part (WMP) with a rated uninterrupted current of 1250 A and rated operational voltage of 690 V AC. The E1.2B performance level provides an ultimate short-circuit breaking capacity of 42 kA at 400–690 V AC and a rated short-time withstand current of 42 kA for 1 second, supporting dependable protection across demanding low-voltage applications.
The ABB SACE Emax 2 E1.2B combines compact air circuit breaker construction with advanced electronic protection for generator and low-voltage distribution applications. With a rated uninterrupted current of 1250 A, an ultimate breaking capacity of 42 kA across 400–690 V AC and a short-time withstand capability of 42 kA for 1 second, this configuration provides robust and consistent fault-current performance within ABB’s compact E1.2 frame.
The Ekip G Hi-Touch LSIG electronic trip unit provides long-time overload, short-time delayed, instantaneous short-circuit and earth-fault protection while adding advanced functionality for generator applications. Combined with the monitoring and power-management capabilities of the Hi-Touch platform, it is well suited to installations where generator operation, electrical protection and system supervision must work together within a coordinated low-voltage network.
| Series | SACE Emax 2 |
|---|---|
| Frame | E1.2 |
| Order code / SKU | 1SDA072810R1 |
| EAN | 8015644766603 |
| Product type | Air circuit breaker |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 4 |
| Neutral-pole current | 100% of Iu |
| Current type | AC |
| Performance level | B |
| Trip unit | Ekip G Hi-Touch |
| Release type | Electronic |
| Protection functions | LSIG |
| Long-time overload protection | Yes |
| Short-time delayed short-circuit protection | Yes |
| Instantaneous short-circuit protection | Yes |
| Integrated earth-fault protection | Yes |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 42 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 42 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 42 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 42 kA |
| Ultimate short-circuit breaking capacity (Icu) at 525 V AC | 42 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 42 kA |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw, 1 s) | 42 kA |
| Rated short-time withstand current (Icw, 3 s) | 24 kA |
| Execution | Withdrawable mobile part |
| Main circuit connection | Connection through corresponding fixed part |
| Auxiliary contacts | 4 |
| Open / closed position indication | Yes |
| Power loss | 244 W |
| Electrical durability at ≤440 V AC | 8000 cycles |
| Electrical durability at 500–690 V AC | 6500 cycles |
| Mechanical durability | 20000 cycles |
| Dimensions (W × H × D) | 348 × 363.5 × 271 mm |
| Net weight | 20 kg |
| Standard | IEC 60947-2 |
The ABB 1SDA072810R1 is a four-pole SACE Emax 2 E1.2B withdrawable air circuit breaker mobile part rated at 1250 A and equipped with an Ekip G Hi-Touch LSIG electronic trip unit for advanced generator and distribution protection.
The breaker has a rated uninterrupted current of 1250 A and a rated operational voltage of 690 V AC, with a rated insulation voltage of 1000 V AC.
The E1.2B 1250 provides an ultimate short-circuit breaking capacity of 42 kA at 400–690 V AC. Its rated short-time withstand current is 42 kA for 1 second and 24 kA for 3 seconds.
Ekip G Hi-Touch is ABB’s advanced electronic trip unit with generator-oriented protection, measurement, monitoring and power-management capabilities. LSIG provides long-time, short-time, instantaneous and earth-fault protection, giving this configuration comprehensive circuit protection including integrated earth-fault functionality.
The 1SDA072810R1 is a four-pole withdrawable mobile part designed for use with the corresponding Emax 2 E1.2 fixed part, allowing the breaker to be isolated and withdrawn from the switchboard for inspection, servicing and maintenance.
ABB SACE Emax 2 air circuit breakers combine dependable short-circuit performance, advanced generator-oriented electronic protection and flexible withdrawable construction for generating systems, industrial facilities, critical infrastructure and low-voltage distribution networks requiring comprehensive LSIG protection and advanced system supervision.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.