ABB 1SDA072804R1 is a SACE Emax 2 E1.2B 1250 four-pole withdrawable air circuit breaker moving part rated at 1250 A and equipped with an Ekip Touch LI solid-state electronic protection release.
£3,716.66
The ABB 1SDA072804R1 is a SACE Emax 2 E1.2B air circuit breaker designed for protection and switching in low-voltage electrical distribution systems. Configured as the E1.2B 1250 Ekip Touch LI 4p WMP, this four-pole withdrawable moving part combines a 1250 A rated uninterrupted current with ABB's advanced Ekip Touch LI solid-state electronic protection release.
The Ekip Touch LI release provides long-time overload and instantaneous short-circuit protection. This electronic protection combination safeguards distribution circuits against sustained overloads and high-current short circuits, while the Ekip Touch platform provides advanced protection configuration, measurement and monitoring capabilities.
The E1.2B performance level provides an ultimate short-circuit breaking capacity of 42 kA at 400–690 V AC and a rated short-time withstand current of 42 kA for 1 s. Its four-pole withdrawable construction is designed for use with the corresponding Emax 2 fixed part and includes four auxiliary contacts plus circuit-breaker open/closed position indication.
The ABB SACE Emax 2 E1.2B provides switching and electronic overcurrent protection for low-voltage electrical distribution systems. Its Ekip Touch release monitors circuit conditions and initiates interruption when configured protection thresholds are exceeded, helping protect conductors, switchgear and connected equipment against overload and high-current short-circuit conditions.
The Ekip Touch LI release combines long-time overload and instantaneous short-circuit protection in an advanced electronic trip-unit platform. Together with the 1250 A E1.2B frame, 42 kA breaking capacity and withdrawable architecture, the ABB 1SDA072804R1 provides a capable solution for distribution switchboards requiring dependable electronic protection and service-friendly circuit-breaker construction.
| Series | SACE Emax 2 |
|---|---|
| ABB order code | 1SDA072804R1 |
| EAN | 8015644766542 |
| Product type | Air circuit breaker moving part |
| Product group | Emax2 Air Circuit Breaker |
| Frame | E1.2 |
| Short-circuit performance level | B |
| Rated uninterrupted current (Iu) | 1250 A |
| Number of poles | 4 |
| Current type | AC |
| Rated operational voltage | Up to 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Protection release | Ekip Touch LI |
| Release type | Solid-state electronic |
| Protection functions | L and I |
| Long-time overload protection | Yes |
| Instantaneous short-circuit protection | Yes |
| Short-time protection function | No |
| Integrated ground-fault protection | No |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 42 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 42 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 42 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 42 kA |
| Ultimate short-circuit breaking capacity (Icu) at 525 V AC | 42 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 42 kA |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Short-time withstand current (Icw) | 42 kA for 1 s; 24 kA for 3 s |
| Construction | Withdrawable moving part |
| Configuration | WMP |
| Main circuit connection | Corresponding Emax 2 fixed part required |
| Auxiliary contacts | 4 |
| Open / closed position indication | Yes |
| Suitable for IT networks | Yes, up to 690 V |
| Standard | IEC 60947-2 |
The ABB 1SDA072804R1 is an Emax 2 E1.2B 1250 four-pole withdrawable air circuit breaker moving part equipped with an Ekip Touch LI solid-state electronic protection release.
The ABB 1SDA072804R1 has a rated uninterrupted current of 1250 A.
The LI configuration provides long-time overload protection and instantaneous short-circuit protection.
No. The Ekip Touch LI release provides long-time and instantaneous overcurrent protection and does not include the integrated ground-fault protection function provided by appropriate LSIG configurations.
The E1.2B 1250 configuration has an ultimate short-circuit breaking capacity of 42 kA at 400–690 V AC.
The ABB 1SDA072804R1 has a rated short-time withstand current of 42 kA for 1 s and 24 kA for 3 s.
It is a withdrawable moving-part (WMP) configuration designed for installation with the corresponding Emax 2 fixed part in a compatible switchboard assembly.
ABB SACE Emax 2 air circuit breakers are engineered for the protection, control and management of low-voltage power distribution systems, combining configurable electronic protection, dependable short-circuit performance and flexible withdrawable construction for industrial, commercial and infrastructure applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.