1SDA072803R1 ABB Emax 2 E1.2B 1250 Ekip Dip LSIG 4-Pole Air Circuit Breaker

1SDA072803R1 ABB Emax 2 E1.2B 1250 Ekip Dip LSIG 4-Pole Air Circuit Breaker

ABB 1SDA072803R1 is a SACE Emax 2 E1.2B 1250 four-pole withdrawable air circuit breaker moving part rated at 1250 A and equipped with an Ekip Dip LSIG solid-state electronic protection release.

SKU: 1SDA072803R1MPN: 1SDA072803R1
Price
List Price £5,898.48 ex VAT
Your Price (ex VAT) Save 25%
£4,423.86 25% OFF
You save £1,474.62 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £4,423.86
Trade pricing is personalised to your account

Manufacturer Lead Time

£4,423.86

Why Choose the ABB 1SDA072803R1 Emax 2 E1.2B 1250 Air Circuit Breaker?

The ABB 1SDA072803R1 is a SACE Emax 2 E1.2B air circuit breaker designed for protection and switching in low-voltage electrical distribution systems. Configured as the E1.2B 1250 Ekip Dip LSIG 4p WMP, this four-pole withdrawable moving part combines a 1250 A rated uninterrupted current with ABB's Ekip Dip LSIG solid-state electronic protection release.

The Ekip Dip LSIG release provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection. This comprehensive protection combination helps safeguard distribution equipment against overloads, high short-circuit currents and ground-fault conditions while supporting coordinated protection within low-voltage installations.

The E1.2B performance level provides an ultimate short-circuit breaking capacity of 42 kA at 400–690 V AC and a rated short-time withstand current of 42 kA for 1 s. Its four-pole withdrawable construction, four auxiliary change-over contacts and open/closed position indication make it well suited to serviceable switchboard installations where the corresponding Emax 2 fixed part is installed separately.

Key Advantages

  • Rated uninterrupted current of 1250 A for substantial low-voltage distribution loads.
  • Four-pole configuration for four-pole switching and protection applications.
  • Reliable Ekip Dip LSIG solid-state electronic protection release.
  • Long-time, short-time, instantaneous and ground-fault protection in one trip unit.
  • 42 kA ultimate short-circuit breaking capacity at 400–690 V AC.
  • 42 kA short-time withstand current for 1 s supports selective distribution-system design.
  • Withdrawable moving-part construction supports convenient inspection, maintenance and replacement.

Key Features

  • ABB SACE Emax 2 E1.2 air circuit breaker platform.
  • 1250 A rated uninterrupted current.
  • Four-pole configuration.
  • B short-circuit performance level.
  • Ekip Dip LSIG solid-state electronic protection release.
  • Long-time (L) overload protection.
  • Short-time (S) short-circuit protection.
  • Instantaneous (I) short-circuit protection.
  • Ground-fault (G) protection.
  • 42 kA Icu at 400–690 V AC.
  • 42 kA Ics across the specified operational-voltage range.
  • 42 kA Icw for 1 s and 24 kA for 3 s.
  • Rated operational voltage of 690 V AC.
  • Rated insulation voltage of 1000 V AC.
  • Rated impulse withstand voltage of 12 kV.
  • Four auxiliary contacts and circuit-breaker open/closed position indication.
  • Withdrawable moving part (WMP) configuration.

Comprehensive LSIG Protection for Low-Voltage Distribution

The ABB SACE Emax 2 E1.2B provides switching and electronic protection for low-voltage power distribution systems. Its Ekip Dip release monitors circuit current and initiates interruption when configured protection thresholds are exceeded, helping protect conductors, switchgear and connected equipment against overload, short-circuit and ground-fault conditions.

The Ekip Dip LSIG release combines long-time overload, short-time delayed short-circuit, instantaneous short-circuit and ground-fault protection. Together with the 1250 A E1.2B frame, 42 kA breaking capacity and withdrawable architecture, the ABB 1SDA072803R1 provides a robust solution for distribution switchboards requiring comprehensive electronic protection and service-friendly circuit-breaker construction.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial electrical distribution systems.
  • Transformer and feeder protection.
  • Manufacturing and process facilities.
  • Commercial and institutional building power distribution.
  • Infrastructure systems requiring integrated ground-fault protection.

Technical Specifications

Series SACE Emax 2
ABB order code 1SDA072803R1
EAN 8015644766535
Product type Air circuit breaker moving part
Product group Emax2 Air Circuit Breaker
Frame E1.2
Short-circuit performance level B
Rated current (In) 1250 A
Rated uninterrupted current (Iu) 1250 A
Number of poles 4
Neutral pole current 100% of Iu
Current type AC
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Protection release Ekip Dip LSIG
Release type Solid-state electronic
Protection functions L, S, I and G
Long-time overload protection Yes
Short-time short-circuit protection Yes
Instantaneous short-circuit protection Yes
Ground-fault protection Yes
Ultimate short-circuit breaking capacity (Icu) at 400 V AC 42 kA
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 42 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 42 kA
Ultimate short-circuit breaking capacity (Icu) at 500 V AC 42 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 42 kA
Rated service short-circuit breaking capacity (Ics) 100% of Icu
Short-time withstand current (Icw) 42 kA for 1 s; 24 kA for 3 s
Construction Withdrawable moving part
Configuration WMP
Main circuit connection Corresponding fixed part required
Auxiliary contacts 4
Open / closed position indication Yes
Mechanical durability 20,000 cycles
Electrical durability at Ue ≤ 440 V 8,000 cycles
Electrical durability at Ue 500–690 V 6,500 cycles
Product net width 348 mm
Product net height 363.5 mm
Product net depth 271 mm
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA072803R1?

The ABB 1SDA072803R1 is an Emax 2 E1.2B 1250 four-pole withdrawable air circuit breaker moving part equipped with an Ekip Dip LSIG solid-state electronic protection release.

What is the rated current of the ABB E1.2B 1250?

The ABB 1SDA072803R1 has a rated uninterrupted current of 1250 A.

What protection functions does the Ekip Dip LSIG release provide?

The LSIG configuration provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection.

Does the ABB 1SDA072803R1 include ground-fault protection?

Yes. The Ekip Dip LSIG release includes ground-fault protection in addition to its long-time, short-time and instantaneous overcurrent protection functions.

What is the breaking capacity of the ABB 1SDA072803R1?

The E1.2B 1250 configuration has an ultimate short-circuit breaking capacity of 42 kA at 400–690 V AC.

What is the short-time withstand current of the ABB E1.2B 1250?

The ABB 1SDA072803R1 has a rated short-time withstand current of 42 kA for 1 s and 24 kA for 3 s.

Is the ABB 1SDA072803R1 fixed or withdrawable?

It is a withdrawable moving-part (WMP) configuration designed for installation with the corresponding Emax 2 fixed part in a compatible switchboard assembly.

Trusted by Electrical Engineers Worldwide

ABB SACE Emax 2 air circuit breakers are engineered for the protection, control and management of low-voltage power distribution systems, combining configurable electronic protection, dependable short-circuit performance and flexible withdrawable construction for industrial, commercial and infrastructure applications.