Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072788R1 SACE Emax 2 E1.2N 1000 four-pole withdrawable air circuit breaker moving part with Ekip Hi-Touch LSI electronic protection, 1000 A rated current and 66 kA breaking capacity at 380–440 V AC.
£8,275.96
The ABB 1SDA072788R1 is a high-performance SACE Emax 2 E1.2N air circuit breaker designed for advanced protection, measurement and control of low-voltage electrical distribution systems. Configured as an E1.2N 1000 Ekip Hi-Touch LSI 4p WMP, this four-pole withdrawable moving part combines a 1000 A rated uninterrupted current with ABB's advanced Ekip Hi-Touch LSI solid-state electronic protection release.
As part of the ABB SACE Emax 2 air circuit breaker series, the E1.2N is engineered for demanding industrial, commercial and infrastructure power distribution applications. The Ekip Hi-Touch LSI trip unit provides adjustable long-time, short-time and instantaneous overcurrent protection, complemented by integrated Ekip Measuring Pro and Network Analyzer functionality for advanced electrical measurement and power-quality monitoring.
The E1.2N performance level provides a rated ultimate short-circuit breaking capacity of 66 kA at 380–440 V AC and 50 kA at 500–690 V AC. With a rated operational voltage of 690 V AC, rated insulation voltage of 1000 V AC and four-pole withdrawable construction, the breaker is well suited to critical switchboards requiring high fault interruption performance, sophisticated protection and convenient maintenance.
Air circuit breakers such as the ABB SACE Emax 2 E1.2N protect low-voltage electrical distribution systems against overloads and short circuits while providing dependable switching and isolation. With a 66 kA breaking capacity at 380–440 V AC, this E1.2N configuration offers enhanced fault interruption performance for demanding switchboards, feeders and critical electrical distribution systems.
The Ekip Hi-Touch LSI electronic trip unit extends conventional overcurrent protection with advanced electrical measurement and analysis. Integrated Ekip Measuring Pro and Network Analyzer functionality supports detailed supervision of electrical parameters and power quality, while adjustable long-time, short-time and instantaneous protection enables effective coordination and selectivity within modern low-voltage distribution networks.
| Series | SACE Emax 2 |
|---|---|
| Frame | E1.2N |
| Order code / MPN | 1SDA072788R1 |
| EAN | 8015644766382 |
| Product group | Emax2 Air Circuit Breaker |
| Product type | Air circuit breaker |
| Construction | Withdrawable moving part |
| Number of poles | 4 |
| Rated uninterrupted current (Iu) | 1000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50 / 60 Hz |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC | 50 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 50 kA |
| Protection release | Ekip Hi-Touch LSI |
| Release type | Solid-state electronic |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Overload protection setting | 0.4–1 × In |
| Overload release current setting | 400–1000 A |
| Short-time selective protection setting | 0.6–10 × In |
| Short-time delayed short-circuit setting | 600–10000 A |
| Instantaneous protection setting | 1.5–15 × In |
| Instantaneous short-circuit setting | 1500–15000 A |
| Integrated earth-fault protection | No |
| Measurement module | Ekip Measuring Pro |
| Network analysis | Integrated Network Analyzer |
| Configuration interface | Touch-sensitive display |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open / closed |
| Integrated undervoltage release | No |
| Integrated motor drive | No |
| Optional motor drive | Yes |
| Mounting system | Withdrawable |
| Standard | IEC 60947-2 |
| Product family | Emax 2 Air Circuit Breakers |
The ABB 1SDA072788R1 is an Emax 2 air circuit breaker moving part designed to protect, monitor and control demanding low-voltage electrical distribution systems against overloads and short circuits.
The breaker has a rated uninterrupted current of 1000 A, making it suitable for substantial industrial, commercial and infrastructure power distribution loads.
The E1.2N 1000 provides a rated ultimate short-circuit breaking capacity of 66 kA at 380–440 V AC and 50 kA at 500–690 V AC, providing robust fault interruption across a wide range of low-voltage distribution applications.
This model is fitted with the advanced ABB Ekip Hi-Touch LSI electronic release, providing adjustable long-time overload, short-time selective short-circuit and instantaneous short-circuit protection together with Ekip Measuring Pro and Network Analyzer functionality.
The 1SDA072788R1 is a four-pole withdrawable moving part for the Emax 2 E1.2N circuit breaker system and is designed for use with the corresponding fixed part in a low-voltage switchboard.
ABB SACE Emax 2 air circuit breakers combine high fault interruption performance with advanced electronic protection, electrical measurement and network analysis capabilities for demanding industrial, commercial and infrastructure low-voltage distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.