1SDA072783R1 ABB E1.2N 1000 Ekip Dip LSIG 4P WMP Air Circuit Breaker

1SDA072783R1 ABB E1.2N 1000 Ekip Dip LSIG 4P WMP Air Circuit Breaker

ABB 1SDA072783R1 SACE Emax 2 E1.2N 1000 A four-pole withdrawable air circuit breaker with Ekip Dip LSIG electronic overload, short-circuit and ground-fault protection.

SKU: 1SDA072783R1MPN: 1SDA072783R1
Price
List Price £8,185.63 ex VAT
Your Price (ex VAT) Save 25%
£6,139.22 25% OFF
You save £2,046.41 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £6,139.22
Trade pricing is personalised to your account

Manufacturer Lead Time

£6,139.22

Why Choose the ABB E1.2N 1000 Ekip Dip LSIG 4p WMP Air Circuit Breaker?

The ABB 1SDA072783R1 is a high-performance SACE Emax 2 E1.2N air circuit breaker designed for protection and switching in demanding low-voltage electrical distribution systems. Rated at 1000 A, this four-pole withdrawable breaker combines ABB's compact E1.2N frame with an Ekip Dip LSIG electronic trip unit, providing Long-time, Short-time, Instantaneous and Ground-fault protection.

The E1.2N performance level delivers a rated ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and 50 kA at 500–690 V AC. Its rated service short-circuit breaking capacity is 100% of Icu, while short-time withstand capability reaches 50 kA for 1 s, supporting dependable protection and selective coordination in industrial, commercial and infrastructure distribution networks.

This model is supplied as a four-pole withdrawable moving part (WMP) for connection to the appropriate separate Emax 2 chassis. The solid-state Ekip Dip LSIG release provides comprehensive electronic protection, while four change-over auxiliary contacts and open/closed circuit-breaker position indication support effective switchboard monitoring and control.

Key Advantages

  • High-performance 1000 A air circuit breaker for low-voltage power distribution.
  • Four-pole configuration provides switching and protection across four-conductor systems.
  • Ekip Dip LSIG electronic trip unit provides overload, selective short-circuit, instantaneous and earth-fault protection.
  • 66 kA ultimate breaking capacity at 400–440 V AC for demanding fault-current conditions.
  • 50 kA Icu at 500–690 V AC maintains robust protection at higher operating voltages.
  • Ics equal to 100% of Icu provides strong service short-circuit performance.
  • 50 kA short-time withstand current for 1 s supports selective protection schemes.
  • Integrated Ground-fault (G) protection provides protection against earth-fault conditions.
  • Withdrawable construction supports efficient switchboard inspection, servicing and replacement.

Key Features

  • ABB SACE Emax 2 E1.2N air circuit breaker.
  • 1000 A rated current.
  • 4-pole configuration with neutral pole rated at 100% of Iu.
  • Ekip Dip LSIG solid-state electronic protection release.
  • Long-time (L) overload protection.
  • Short-time (S) selective short-circuit protection.
  • Instantaneous (I) short-circuit protection.
  • Ground-fault (G) protection.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 66 kA Icu at 400–440 V AC.
  • 50 kA Icu at 500–690 V AC.
  • 50 kA Icw for 1 s and 30 kA for 3 s.
  • Four change-over auxiliary contacts for signalling and control.
  • Withdrawable moving-part configuration for maintainable switchboard installations.

Comprehensive LSIG Protection for Power Distribution

The ABB SACE Emax 2 E1.2N provides a robust switching and protection point within low-voltage power-distribution systems. Its Ekip Dip LSIG release combines Long-time overload, Short-time selective, Instantaneous short-circuit and Ground-fault protection, enabling comprehensive protection against the principal overcurrent and earth-fault conditions encountered in industrial and commercial networks.

With a 1000 A current rating, up to 66 kA ultimate short-circuit breaking capacity and 50 kA short-time withstand capability for 1 s, the E1.2N is well suited to demanding distribution systems requiring strong fault performance and selectivity. Its withdrawable construction allows the moving breaker portion to be separated from the fixed chassis, supporting efficient maintenance and replacement where system availability is important.

Typical Applications

  • Main and distribution switchboards.
  • Industrial low-voltage power distribution systems.
  • Commercial building electrical distribution.
  • Manufacturing and process-control facilities.
  • Data centres and critical-power installations.
  • Infrastructure and utility distribution systems.
  • Transformer secondary and generator distribution.
  • Four-pole distribution circuits requiring comprehensive LSIG protection and selective coordination.

Technical Specifications

Series SACE Emax 2
Frame / subtype E1.2N
ABB order code 1SDA072783R1
Product group Emax2 Air Circuit Breaker
Product type Air circuit breaker
Short-circuit performance level N
Rated current (In) 1000 A
Rated uninterrupted current (Iu) 1000 A
Number of poles 4P
Neutral pole current 100% of Iu
Current type AC
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 66 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC 50 kA
Rated ultimate short-circuit breaking capacity (Icu) at 525 V AC 50 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 50 kA
Rated service short-circuit breaking capacity (Ics) 100% of Icu
Rated short-time withstand current (Icw) 50 kA for 1 s; 30 kA for 3 s
Trip unit Ekip Dip LSIG
Release type Solid-state electronic
Protection functions Long-time (L), Short-time (S), Instantaneous (I), Ground-fault (G)
Integrated earth-fault protection Yes
Version Withdrawable moving part (WMP)
Main-circuit connection Connection at separate chassis part
Auxiliary contacts 4 change-over contacts
Breaker position indication Open / closed
Control element Push button
Motor drive Optional
Degree of protection IP30
Electrical durability 8000 cycles
Mechanical durability 20000 cycles
Power loss 156 W
Dimensions (W × H × D) 348 × 363.5 × 271 mm
EAN / GTIN 8015644766337
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA072783R1 used for?

The ABB 1SDA072783R1 is a 1000 A four-pole air circuit breaker designed for switching and protecting demanding low-voltage electrical power-distribution systems.

What protection release is fitted to the ABB 1SDA072783R1?

This breaker is fitted with an Ekip Dip LSIG solid-state electronic trip unit, providing Long-time, Short-time, Instantaneous and Ground-fault protection.

What does LSIG mean on the Ekip Dip trip unit?

LSIG denotes Long-time, Short-time, Instantaneous and Ground-fault protection, providing comprehensive protection against overload, short-circuit and earth-fault conditions.

What is the breaking capacity of the ABB E1.2N 1000?

The E1.2N 1000 has a rated ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and 50 kA at 500–690 V AC, with Ics rated at 100% of Icu.

Is the ABB 1SDA072783R1 a fixed or withdrawable circuit breaker?

The 1SDA072783R1 is a withdrawable moving-part (WMP) circuit breaker designed for connection to the appropriate separate chassis in an ABB SACE Emax 2 switchboard installation.

Trusted Protection for Low-Voltage Distribution

ABB SACE Emax 2 air circuit breakers combine high short-circuit performance, comprehensive electronic protection and flexible withdrawable construction to provide dependable switching, selectivity and fault protection for demanding industrial, commercial and infrastructure power-distribution systems.