1SDA072778R1 ABB E1.2C 1000 Ekip Hi-Touch LSI 4P Air Circuit Breaker

1SDA072778R1 ABB E1.2C 1000 Ekip Hi-Touch LSI 4P Air Circuit Breaker

ABB 1SDA072778R1 SACE Emax 2 E1.2C 1000 four-pole withdrawable air circuit breaker moving part with Ekip Hi-Touch LSI electronic protection, 1000 A rated current and 50 kA breaking capacity at 380–440 V AC.

SKU: 1SDA072778R1MPN: 1SDA072778R1
Price
List Price £8,546.80 ex VAT
Your Price (ex VAT) Save 25%
£6,410.10 25% OFF
You save £2,136.70 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £6,410.10
Trade pricing is personalised to your account

Manufacturer Lead Time

£6,410.10

Why Choose the ABB 1SDA072778R1 Emax 2 Air Circuit Breaker?

The ABB 1SDA072778R1 is a high-performance SACE Emax 2 E1.2C air circuit breaker designed for advanced protection, measurement and control of low-voltage electrical distribution systems. Configured as an E1.2C 1000 Ekip Hi-Touch LSI 4p WMP, this four-pole withdrawable moving part combines a 1000 A rated uninterrupted current with ABB's advanced Ekip Hi-Touch LSI electronic protection release.

As part of the ABB SACE Emax 2 air circuit breaker series, the E1.2C is engineered for demanding industrial, commercial and infrastructure power distribution applications. The Ekip Hi-Touch LSI trip unit provides adjustable long-time, short-time and instantaneous protection together with advanced measurement capabilities, including integrated Ekip Measuring Pro and Network Analyzer functionality.

The E1.2C performance level provides a rated ultimate short-circuit breaking capacity of 50 kA at 380–440 V AC and 42 kA at 500–690 V AC, together with a rated short-time withstand current of 42 kA for 1 s. Its four-pole withdrawable construction allows the moving portion to be isolated and removed from the corresponding fixed part, supporting efficient inspection, servicing and maintenance in critical switchboard installations.

Key Advantages

  • Advanced ABB SACE Emax 2 air circuit breaker for demanding low-voltage power distribution.
  • 1000 A rated uninterrupted current for substantial industrial and commercial electrical loads.
  • 50 kA ultimate short-circuit breaking capacity at 380–440 V AC.
  • 42 kA short-time withstand current for 1 s.
  • Advanced Ekip Hi-Touch LSI electronic protection release.
  • Integrated long-time, short-time and instantaneous protection functions.
  • Integrated Ekip Measuring Pro and Network Analyzer functionality.
  • Four-pole withdrawable moving-part construction supports convenient isolation and maintenance.

Key Features

  • ABB SACE Emax 2 E1.2C series.
  • 1000 A rated uninterrupted current.
  • 4-pole configuration.
  • Ekip Hi-Touch LSI electronic trip unit.
  • 50 kA Icu at 380–440 V AC.
  • 42 kA Icu at 500–690 V AC.
  • 42 kA Icw for 1 s.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • Adjustable long-time overload protection.
  • Adjustable short-time selective short-circuit protection.
  • Adjustable instantaneous short-circuit protection.
  • Integrated Ekip Measuring Pro measurement module.
  • Integrated Network Analyzer functionality.
  • Touch-sensitive display for protection configuration and monitoring.
  • Four auxiliary contacts with circuit-breaker open/closed position indication.
  • Withdrawable moving-part design for use with the corresponding Emax 2 fixed part.

Advanced Circuit Protection and Power Monitoring

Air circuit breakers such as the ABB SACE Emax 2 E1.2C protect low-voltage electrical distribution systems against overloads and short circuits while providing dependable switching and isolation. With a 50 kA breaking capacity at 380–440 V AC, this E1.2C configuration provides robust fault interruption for demanding switchboards, feeders and connected electrical equipment.

The Ekip Hi-Touch LSI electronic trip unit extends protection with sophisticated measurement and analysis capabilities. Integrated Ekip Measuring Pro and Network Analyzer functionality enables detailed supervision of electrical parameters and power quality, while adjustable long-time, short-time and instantaneous protection supports effective coordination and selectivity within modern low-voltage distribution systems.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Commercial building electrical distribution.
  • Manufacturing and process facilities.
  • Data centres and critical infrastructure.
  • Incoming and outgoing high-current switchboard feeders.
  • Power monitoring and electrical network analysis systems.
  • Switchboards requiring four-pole withdrawable circuit breaker assemblies.

Technical Specifications

Series SACE Emax 2
Frame E1.2C
Order code / MPN 1SDA072778R1
EAN 8015644766283
Product type Air circuit breaker
Construction Withdrawable moving part
Number of poles 4
Rated uninterrupted current (Iu) 1000 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Frequency 50 / 60 Hz
Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC 50 kA
Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC 50 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 50 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC 42 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 42 kA
Rated short-time withstand current (Icw) 42 kA for 1 s
Protection release Ekip Hi-Touch LSI
Release type Solid-state electronic
Protection functions Long-time, short-time and instantaneous (LSI)
Overload protection setting 0.4–1 × In
Short-time selective protection setting 0.6–10 × In
Instantaneous protection setting 1.5–15 × In
Measurement module Ekip Measuring Pro
Network analysis Integrated Network Analyzer
Configuration interface Touch-sensitive display
Auxiliary contacts 4
Position indication Circuit breaker open / closed
Product dimensions 348 × 363.5 × 271 mm
Product net weight 20 kg
Standard IEC 60947-2
Product family Emax 2 Air Circuit Breakers

Frequently Asked Questions

What is the ABB 1SDA072778R1 used for?

The ABB 1SDA072778R1 is an Emax 2 air circuit breaker moving part designed to protect, monitor and control low-voltage electrical distribution systems against overloads and short circuits.

What is the current rating of the ABB E1.2C 1SDA072778R1?

The breaker has a rated uninterrupted current of 1000 A, making it suitable for substantial industrial, commercial and infrastructure power distribution loads.

What breaking capacity does the E1.2C 1000 provide?

The E1.2C 1000 provides a rated ultimate short-circuit breaking capacity of 50 kA at 380–440 V AC and 42 kA at 500–690 V AC, together with a rated short-time withstand current of 42 kA for 1 s.

What protection release is fitted to 1SDA072778R1?

This model is fitted with the advanced ABB Ekip Hi-Touch LSI electronic release, providing adjustable long-time overload, short-time selective short-circuit and instantaneous short-circuit protection together with advanced measurement and network analysis functionality.

Is the ABB 1SDA072778R1 a fixed or withdrawable circuit breaker?

The 1SDA072778R1 is a four-pole withdrawable moving part for the Emax 2 E1.2C circuit breaker system and is designed for use with the corresponding fixed part in a low-voltage switchboard.

Trusted for Advanced Power Distribution

ABB SACE Emax 2 air circuit breakers combine high fault interruption performance with advanced electronic protection, electrical measurement and network analysis capabilities for demanding industrial, commercial and infrastructure low-voltage distribution systems.