1SDA072773R1 ABB Emax 2 E1.2C 1000 Ekip Dip LSIG 4-Pole Air Circuit Breaker

1SDA072773R1 ABB Emax 2 E1.2C 1000 Ekip Dip LSIG 4-Pole Air Circuit Breaker

ABB 1SDA072773R1 is a SACE Emax 2 E1.2C 1000 four-pole withdrawable air circuit breaker moving part rated at 1000 A and equipped with an Ekip Dip LSIG electronic protection release.

SKU: 1SDA072773R1MPN: 1SDA072773R1
Price
List Price £5,637.69 ex VAT
Your Price (ex VAT) Save 25%
£4,228.27 25% OFF
You save £1,409.42 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £4,228.27
Trade pricing is personalised to your account

Manufacturer Lead Time

£4,228.27

Why Choose the ABB 1SDA072773R1 Emax 2 E1.2C 1000 Air Circuit Breaker?

The ABB 1SDA072773R1 is a SACE Emax 2 E1.2C air circuit breaker designed for protection and switching in low-voltage electrical distribution systems. Configured as the E1.2C 1000 Ekip Dip LSIG 4p WMP, this four-pole withdrawable moving part combines a 1000 A rated current with ABB's Ekip Dip LSIG electronic protection release.

The Ekip Dip LSIG release provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection. This combination provides comprehensive electronic protection against the principal overcurrent and earth-fault conditions encountered in low-voltage distribution networks.

The E1.2C performance level combines a compact E1.2 frame with enhanced short-circuit performance, including an ultimate short-circuit breaking capacity of 50 kA at 400–440 V AC and a rated short-time withstand current of 42 kA for 1 s. Its four-pole withdrawable moving-part construction is designed for use with the corresponding Emax 2 fixed part, supporting convenient inspection and maintenance.

Key Advantages

  • Rated current of 1000 A for substantial low-voltage distribution loads.
  • Four-pole configuration for applications requiring four-pole switching and protection.
  • Reliable Ekip Dip LSIG electronic protection release.
  • Long-time, short-time, instantaneous and ground-fault protection in one trip unit.
  • 50 kA ultimate short-circuit breaking capacity at 400–440 V AC.
  • 42 kA short-time withstand current for 1 s supports selective protection strategies.
  • Withdrawable moving-part construction supports convenient switchboard inspection and maintenance.

Key Features

  • ABB SACE Emax 2 E1.2 air circuit breaker platform.
  • 1000 A current rating.
  • Four-pole configuration.
  • C short-circuit performance level.
  • Ekip Dip LSIG electronic protection release.
  • Long-time (L) overload protection.
  • Short-time (S) short-circuit protection.
  • Instantaneous (I) short-circuit protection.
  • Ground-fault (G) protection.
  • 50 kA Icu at 400–440 V AC.
  • 42 kA Icw for 1 s.
  • Rated operational voltage up to 690 V AC.
  • Withdrawable moving part (WMP) configuration.
  • Designed for use with the corresponding Emax 2 fixed part in a compatible switchboard.

Comprehensive LSIG Protection for Low-Voltage Distribution

The ABB SACE Emax 2 E1.2C provides switching and overcurrent protection for low-voltage electrical distribution systems. Its electronic trip unit monitors circuit conditions and initiates interruption when configured protection thresholds are exceeded, helping protect conductors, switchgear and connected equipment against overload, short-circuit and ground-fault conditions.

The Ekip Dip LSIG release combines long-time overload, short-time delayed short-circuit, instantaneous short-circuit and ground-fault protection. Together with the 1000 A E1.2C frame, 50 kA short-circuit breaking performance and withdrawable architecture, the ABB 1SDA072773R1 provides a robust solution for distribution systems requiring comprehensive electronic protection and service-friendly switchgear construction.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial electrical distribution systems.
  • Manufacturing and process facilities.
  • Commercial and institutional building power distribution.
  • Infrastructure electrical installations.
  • Distribution systems requiring integrated ground-fault protection.

Technical Specifications

Series SACE Emax 2
ABB order code 1SDA072773R1
Product type Air circuit breaker moving part
Product group Emax 2 Air Circuit Breaker
Frame E1.2
Short-circuit performance level C
Rated current 1000 A
Number of poles 4
Current type AC
Rated operational voltage Up to 690 V AC
Protection release Ekip Dip LSIG
Release type Electronic
Protection functions L, S, I and G
Long-time overload protection Yes
Short-time short-circuit protection Yes
Instantaneous short-circuit protection Yes
Ground-fault protection Yes
Ultimate short-circuit breaking capacity (Icu) at 400–440 V AC 50 kA
Short-time withstand current (Icw) 42 kA for 1 s
Construction Withdrawable moving part
Configuration WMP
Installation Compatible Emax 2 fixed part required
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA072773R1?

The ABB 1SDA072773R1 is an Emax 2 E1.2C 1000 four-pole withdrawable air circuit breaker moving part equipped with an Ekip Dip LSIG electronic protection release.

What is the rated current of the ABB E1.2C 1000?

The ABB 1SDA072773R1 is configured for a rated current of 1000 A.

What protection functions does the Ekip Dip LSIG release provide?

The LSIG configuration provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection.

Does the ABB 1SDA072773R1 include ground-fault protection?

Yes. The Ekip Dip LSIG release includes ground-fault protection in addition to its long-time, short-time and instantaneous overcurrent protection functions.

What is the breaking capacity of the ABB 1SDA072773R1?

The E1.2C configuration provides an ultimate short-circuit breaking capacity of 50 kA at 400–440 V AC.

What is the short-time withstand current of the ABB E1.2C 1000?

The E1.2C configuration provides a rated short-time withstand current of 42 kA for 1 s.

Is the ABB 1SDA072773R1 fixed or withdrawable?

It is a withdrawable moving-part (WMP) configuration designed for installation with the corresponding Emax 2 fixed part in a compatible switchboard assembly.

Trusted by Electrical Engineers Worldwide

ABB SACE Emax 2 air circuit breakers are engineered for the protection, control and management of low-voltage power distribution systems, combining configurable electronic protection, robust short-circuit performance and flexible withdrawable construction for industrial, commercial and infrastructure applications.