Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072747R1 SACE Emax 2 E1.2N 800 A four-pole withdrawable air circuit breaker mobile part with Ekip G Touch LSIG generator-oriented electronic protection, 690 V AC rated operational voltage and 66 kA short-circuit breaking capacity at 380–440 V AC.
£8,426.40
The ABB 1SDA072747R1 is a SACE Emax 2 E1.2N air circuit breaker (ACB) engineered for generator protection and advanced low-voltage power distribution. Rated at 800 A, this four-pole breaker combines ABB’s compact E1.2N frame with an Ekip G Touch LSIG solid-state electronic trip unit, providing long-time overload, short-time delayed, instantaneous short-circuit and earth-fault protection.
The Ekip G Touch release is specifically designed to extend Emax 2 protection capabilities for generator applications. In addition to LSIG circuit protection, it incorporates generator-specific protection functions and advanced electrical measurement capabilities, making the breaker suitable for generating sets, emergency power systems and installations where generator protection must be integrated with the main low-voltage distribution architecture.
The 1SDA072747R1 is a four-pole withdrawable mobile part (WMP) with a rated uninterrupted current of 800 A and rated operational voltage of 690 V AC. Its E1.2N performance level provides an ultimate short-circuit breaking capacity of 66 kA at 380–440 V AC and 50 kA at 500–690 V AC, together with a rated short-time withstand current of 50 kA for 1 second.
The ABB SACE Emax 2 E1.2N combines high-performance circuit interruption with generator-oriented electronic protection. Its 800 A current rating, 66 kA breaking capacity at 380–440 V AC and 50 kA short-time withstand capability for 1 second make it suitable for installations where robust fault-current performance must be combined with selective protection and generator supervision.
The Ekip G Touch LSIG trip unit provides adjustable long-time, short-time, instantaneous and earth-fault protection while adding generator-specific protection functions and integrated measurement capabilities. This makes the 1SDA072747R1 particularly suitable for generator incomers, standby generating systems, distributed generation installations and low-voltage power networks where generator operation and distribution protection must be coordinated.
| Series | SACE Emax 2 |
|---|---|
| Frame | E1.2 |
| Order code / SKU | 1SDA072747R1 |
| EAN | 8015644765972 |
| Product type | Air circuit breaker |
| Rated uninterrupted current (Iu) | 800 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50/60 Hz |
| Number of poles | 4 |
| Current type | AC |
| Performance level | N |
| Trip unit | Ekip G Touch |
| Release type | Solid-state electronic |
| Protection functions | LSIG |
| Long-time overload protection adjustment | 0.4–1 × In (320–800 A) |
| Short-time delayed protection adjustment | 0.6–10 × In (480–8000 A) |
| Instantaneous protection adjustment | 1.5–15 × In (1200–12000 A) |
| Earth-fault protection adjustment | 0.1–1 × In (80–800 A) |
| Ultimate short-circuit breaking capacity (Icu) at 380 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 50 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 50 kA |
| Rated short-time withstand current (Icw, 1 s) | 50 kA |
| Integrated earth-fault protection | Yes |
| Generator-specific protection | Yes |
| Measurement functionality | Ekip Measuring Pro |
| Execution | Withdrawable mobile part |
| Main circuit connection | Connection through corresponding fixed part |
| Auxiliary contacts | 4 |
| Open / closed position indication | Yes |
| Standard | IEC 60947-2 |
The ABB 1SDA072747R1 is a four-pole SACE Emax 2 E1.2N withdrawable air circuit breaker mobile part rated at 800 A and equipped with an Ekip G Touch LSIG electronic trip unit designed to provide comprehensive circuit and generator protection.
The breaker has a rated uninterrupted current of 800 A and a rated operational voltage of 690 V AC, with a rated insulation voltage of 1000 V AC.
The E1.2N 800 provides an ultimate short-circuit breaking capacity of 66 kA at 380–440 V AC and 50 kA at 500–690 V AC, together with a rated short-time withstand current of 50 kA for 1 second.
The Ekip G Touch LSIG is ABB’s electronic trip unit for applications including generator protection. It provides long-time, short-time, instantaneous and earth-fault protection together with generator-specific protection functions, measurement capabilities and touchscreen-based configuration.
The 1SDA072747R1 is a four-pole withdrawable mobile part designed for use with the corresponding Emax 2 E1.2 fixed part, allowing the breaker to be isolated and withdrawn from the switchboard for inspection, servicing and maintenance.
ABB SACE Emax 2 air circuit breakers combine robust short-circuit performance, advanced generator-oriented electronic protection and flexible withdrawable construction for generating systems, industrial installations, critical infrastructure and low-voltage power distribution networks.