1SDA072732R1 ABB E1.2C 800 Ekip Dip LSI 4p WMP Air Circuit Breaker

1SDA072732R1 ABB E1.2C 800 Ekip Dip LSI 4p WMP Air Circuit Breaker

ABB 1SDA072732R1 SACE Emax 2 E1.2C 800 A four-pole withdrawable air circuit breaker mobile part with Ekip Dip LSI electronic protection, 690 V rated voltage, 50 kA short-circuit breaking capacity at 400 V AC and 42 kA short-time withstand capability.

SKU: 1SDA072732R1MPN: 1SDA072732R1
Price
List Price £4,795.03 ex VAT
Your Price (ex VAT) Save 25%
£3,596.27 25% OFF
You save £1,198.76 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £3,596.27
Trade pricing is personalised to your account

Manufacturer Lead Time

£3,596.27

Why Choose the ABB E1.2C 800 Ekip Dip LSI 4p WMP Air Circuit Breaker?

The ABB 1SDA072732R1 is a SACE Emax 2 E1.2C air circuit breaker (ACB) designed for reliable protection and switching in low-voltage electrical distribution systems. Rated at 800 A, this four-pole breaker combines ABB’s compact E1.2C frame with an Ekip Dip LSI solid-state electronic trip unit providing long-time overload, short-time delayed and instantaneous short-circuit protection.

As part of the ABB SACE Emax 2 air circuit breaker series, the E1.2C combines compact construction with dependable short-circuit performance and flexible switchboard integration. The LSI protection configuration adds short-time delayed protection to the standard long-time and instantaneous functions, supporting improved selectivity and coordination between protective devices in multi-level distribution networks.

The 1SDA072732R1 is a four-pole withdrawable mobile part (WMP) with a rated uninterrupted current of 800 A and rated voltage of 690 V. The E1.2C performance level provides an ultimate short-circuit breaking capacity of 50 kA at 400 V AC and a rated short-time withstand current of 42 kA for 1 second, making it suitable for commercial, industrial and infrastructure power distribution systems.

Key Advantages

  • 800 A rated uninterrupted current for low-voltage main and feeder protection.
  • 50 kA ultimate short-circuit breaking capacity at 400 V AC for dependable fault interruption.
  • 42 kA short-time withstand current for 1 second supports selective protection strategies.
  • Ekip Dip LSI solid-state electronic trip unit provides configurable overload and short-circuit protection.
  • Long-time, short-time and instantaneous protection supports effective coordination with upstream and downstream protective devices.
  • Four-pole configuration with 100% neutral-pole current capability suits three-phase four-wire distribution networks.
  • Withdrawable mobile-part construction facilitates isolation, inspection, servicing and switchboard maintenance.

Key Features

  • ABB SACE Emax 2 E1.2C series.
  • 800 A rated uninterrupted current.
  • 690 V rated voltage.
  • Four-pole configuration.
  • 100% neutral-pole current rating.
  • C short-circuit performance level.
  • 50 kA Icu at 400 V AC.
  • 42 kA Icw for 1 second.
  • Ekip Dip LSI solid-state electronic trip unit.
  • LSI protection provides long-time overload, short-time delayed and instantaneous short-circuit protection.
  • 320 A minimum overload release setting.
  • 480 A minimum short-time delayed short-circuit setting.
  • 1200 A minimum instantaneous short-circuit setting.
  • No integrated earth-fault protection in the LSI configuration.
  • Withdrawable mobile part (WMP) configuration.
  • Four auxiliary change-over contacts for status and control applications.
  • IP30 degree of protection.

Selective LSI Four-Pole Circuit Protection

The ABB SACE Emax 2 E1.2C provides compact air circuit breaker protection for low-voltage networks requiring dependable interruption of overload and short-circuit currents. With a rated uninterrupted current of 800 A, an ultimate breaking capacity of 50 kA at 400 V AC and a short-time withstand capability of 42 kA for 1 second, this configuration combines space-efficient switchboard integration with robust fault-current performance.

The Ekip Dip LSI electronic trip unit provides long-time overload, short-time delayed and instantaneous short-circuit protection. The short-time function allows greater flexibility when coordinating multiple protective devices, helping downstream breakers clear localised faults before upstream protection operates. This LSI configuration does not include integrated earth-fault protection.

Typical Applications

  • Low-voltage main and sub-distribution switchboards.
  • Three-phase four-wire electrical distribution systems.
  • Commercial building power distribution.
  • Industrial feeder and distribution protection.
  • Transformer secondary distribution systems.
  • Infrastructure and utility installations.
  • Systems requiring selective short-circuit protection.
  • Switchboards requiring withdrawable four-pole circuit breaker construction.

Technical Specifications

Series SACE Emax 2
Frame E1.2
Order code / SKU 1SDA072732R1
EAN 8015644765828
Product type Air circuit breaker
Rated uninterrupted current (Iu) 800 A
Rated voltage 690 V
Rated impulse withstand voltage (Uimp) 12 kV
Number of poles 4
Neutral-pole current 100% of Iu
Current type AC
Performance level C
Trip unit Ekip Dip
Release type Solid-state electronic
Protection functions LSI
Overload release setting from 320 A
Short-time delayed short-circuit setting from 480 A
Instantaneous short-circuit setting from 1200 A
Long-time overload protection Yes
Short-time delayed short-circuit protection Yes
Instantaneous short-circuit protection Yes
Integrated earth-fault protection No
Ultimate short-circuit breaking capacity (Icu) at 400 V AC 50 kA
Rated short-time withstand current (Icw, 1 s) 42 kA
Execution Withdrawable mobile part
Main circuit connection Connection through separate fixed part
Auxiliary change-over contacts 4
Open / closed position indication Yes
Control element Push button
Integrated motor operator No
Motor operator Optional
DIN rail mounting No
Degree of protection IP30
Power loss 100 W
Electrical durability at ≤440 V AC 8000 operations
Electrical durability at 500–690 V AC 8000 operations
Mechanical durability 20000 operations
Dimensions (W × H × D) 348 × 363.5 × 271 mm
Net weight 20 kg
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA072732R1?

The ABB 1SDA072732R1 is a four-pole SACE Emax 2 E1.2C withdrawable air circuit breaker mobile part rated at 800 A and equipped with an Ekip Dip LSI solid-state electronic trip unit.

What are the current and voltage ratings of the ABB E1.2C 1SDA072732R1?

The breaker has a rated uninterrupted current of 800 A and a rated voltage of 690 V.

What is the breaking capacity of the ABB E1.2C 800?

The E1.2C 800 provides an ultimate short-circuit breaking capacity of 50 kA at 400 V AC and a rated short-time withstand current of 42 kA for 1 second.

What does Ekip Dip LSI mean?

Ekip Dip is ABB’s solid-state electronic trip unit, while LSI denotes long-time, short-time and instantaneous protection. The short-time function supports selective circuit coordination, while this configuration does not include integrated earth-fault protection.

Is the ABB 1SDA072732R1 fixed or withdrawable?

The 1SDA072732R1 is a four-pole withdrawable mobile part designed for connection through the corresponding Emax 2 E1.2 fixed part, allowing the breaker to be isolated and withdrawn from the switchboard for inspection, servicing and maintenance.

Trusted for Selective Low-Voltage Power Protection

ABB SACE Emax 2 air circuit breakers combine compact construction, dependable short-circuit performance and configurable electronic protection for commercial, industrial and infrastructure low-voltage power distribution systems requiring reliable selectivity and flexible withdrawable switchboard integration.