1SDA072678R1 ABB Emax 2 E1.2N 250 Ekip Hi-Touch LSI 4-Pole Air Circuit Breaker

1SDA072678R1 ABB Emax 2 E1.2N 250 Ekip Hi-Touch LSI 4-Pole Air Circuit Breaker

ABB 1SDA072678R1 is a SACE Emax 2 E1.2N 250 four-pole withdrawable air circuit breaker moving part rated at 250 A and equipped with an Ekip Hi-Touch LSI electronic protection release.

SKU: 1SDA072678R1MPN: 1SDA072678R1
Price
List Price £10,934.25 ex VAT
Your Price (ex VAT) Save 25%
£8,200.69 25% OFF
You save £2,733.56 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,200.69
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,200.69

Why Choose the ABB 1SDA072678R1 Emax 2 E1.2N 250 Air Circuit Breaker?

The ABB 1SDA072678R1 is a high-performance SACE Emax 2 E1.2N air circuit breaker designed for protection, control and management of low-voltage electrical distribution systems. Configured as the E1.2N 250 Ekip Hi-Touch LSI 4p WMP, this four-pole withdrawable moving part combines a 250 A rated current with ABB's advanced Ekip Hi-Touch electronic protection release.

As part of the ABB SACE Emax 2 range, this circuit breaker provides LSI protection functions covering long-time overload, short-time short-circuit and instantaneous short-circuit protection. The Ekip Hi-Touch release provides advanced protection, measurement and power-management capabilities for sophisticated industrial, commercial and infrastructure power-distribution systems.

The E1.2N 250 is rated for operation up to 690 V AC and provides an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and 50 kA at 500–690 V AC. Its four-pole withdrawable construction supports straightforward servicing and maintenance within compatible Emax 2 switchboards, while the neutral pole is rated at 100% of the rated uninterrupted current.

Key Advantages

  • Compact 250 A Emax 2 air circuit breaker for low-voltage power distribution.
  • Four-pole configuration with a 100% rated neutral pole.
  • Advanced Ekip Hi-Touch LSI electronic protection release.
  • LSI functions provide long-time, short-time and instantaneous circuit protection.
  • 66 kA ultimate short-circuit breaking capacity at 400–440 V AC.
  • 50 kA short-time withstand current for 1 s supports selective protection strategies.
  • Withdrawable moving-part construction supports efficient switchboard servicing and maintenance.

Key Features

  • ABB SACE Emax 2 E1.2 air circuit breaker platform.
  • 250 A rated uninterrupted current.
  • Four-pole configuration.
  • N short-circuit performance level.
  • Ekip Hi-Touch LSI electronic protection release.
  • Long-time (L) overload protection.
  • Short-time (S) short-circuit protection.
  • Instantaneous (I) short-circuit protection.
  • 66 kA Icu at 400–440 V AC.
  • 50 kA Icu at 500–690 V AC.
  • 50 kA Icw for 1 s and 30 kA for 3 s.
  • Rated insulation voltage of 1000 V AC.
  • Rated impulse withstand voltage of 12 kV.
  • Withdrawable moving-part format for compatible Emax 2 switchboards.

Advanced Protection for Low-Voltage Power Distribution

Air circuit breakers such as the ABB SACE Emax 2 E1.2N provide switching and protection for low-voltage electrical distribution systems. The electronic protection release monitors circuit conditions and initiates interruption when configured thresholds are exceeded, helping protect conductors, switchgear and connected equipment against overload and short-circuit conditions.

The Ekip Hi-Touch LSI release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. Combined with the compact E1.2 frame, four-pole configuration and withdrawable architecture, this model provides a flexible solution for switchboards requiring advanced electronic protection, high system availability and straightforward maintenance.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution installations.
  • Manufacturing and process facilities.
  • Commercial building electrical distribution.
  • Infrastructure and utility power systems.
  • Critical-power and energy-management switchboards.

Technical Specifications

Series SACE Emax 2
ABB order code 1SDA072678R1
Product type Air circuit breaker
Product group Emax 2 Air Circuit Breaker
Frame / sub-type E1.2
Short-circuit performance level N
Rated current (In) 250 A
Rated uninterrupted current (Iu) 250 A
Number of poles 4
Neutral pole current 100% of Iu
Current type AC
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Ultimate short-circuit breaking capacity (Icu) at 400–440 V AC 66 kA
Ultimate short-circuit breaking capacity (Icu) at 500–690 V AC 50 kA
Service short-circuit breaking capacity (Ics) 50 kA
Short-time withstand current (Icw) 50 kA for 1 s / 30 kA for 3 s
Protection release Ekip Hi-Touch LSI
Release type Electronic
Protection functions L, S and I
Integrated earth-fault protection No
Construction Withdrawable moving part
Version W
Main circuit connection Connection at separate chassis part
Auxiliary change-over contacts 4
Degree of protection IP30
Power loss 62 W
Mechanical durability 20,000 operating cycles
Electrical durability 8000 operating cycles
Product net height 363.5 mm
Product net depth / length 271 mm
Product net weight 20 kg
Suitable for IT networks Yes, 690 V
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA072678R1?

The ABB 1SDA072678R1 is an Emax 2 E1.2N 250 four-pole withdrawable air circuit breaker moving part equipped with an Ekip Hi-Touch LSI electronic protection release.

What is the rated current of the ABB E1.2N 250?

The ABB 1SDA072678R1 has a rated uninterrupted current of 250 A.

What protection functions does the Ekip Hi-Touch LSI release provide?

The LSI configuration provides long-time overload, short-time short-circuit and instantaneous short-circuit protection functions.

Does the ABB 1SDA072678R1 include integrated earth-fault protection?

No. This model uses an LSI protection configuration and does not include integrated earth-fault protection.

What is the breaking capacity of the ABB 1SDA072678R1?

The E1.2N configuration provides an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and 50 kA at 500–690 V AC.

Is the ABB 1SDA072678R1 a fixed or withdrawable circuit breaker?

It is a withdrawable moving-part configuration designed for connection to the appropriate Emax 2 fixed part within a compatible switchboard assembly.

Trusted by Electrical Engineers Worldwide

ABB SACE Emax 2 air circuit breakers are engineered for the protection, control and management of low-voltage power distribution systems, combining advanced electronic protection, high short-circuit performance and flexible integration for demanding industrial, commercial, infrastructure and critical-power applications.