ABB 1SDA072625R1 SACE Emax 2 E6.2V 5000 A three-pole withdrawable air circuit breaker mobile part with Ekip Touch LSI protection, 690 V AC rated operational voltage and 150 kA short-circuit breaking capacity at 400–415 V AC.
£31,660.93
The ABB 1SDA072625R1 is a high-performance SACE Emax 2 E6.2V air circuit breaker (ACB) designed for advanced protection and control of demanding low-voltage electrical distribution systems. Rated at 5000 A, this three-pole breaker combines ABB’s high-breaking-capacity E6.2V frame with an Ekip Touch LSI electronic trip unit for adjustable overload and short-circuit protection.
As part of the advanced ABB SACE Emax 2 air circuit breaker series, the E6.2V is designed for high-current industrial switchboards, critical infrastructure, data centres, large commercial installations and major power distribution systems. The Ekip Touch trip unit combines electronic protection with an intuitive touchscreen interface and supports the wider monitoring, connectivity and power-management capabilities available within the Emax 2 platform.
The 1SDA072625R1 is a three-pole withdrawable mobile part (WMP) with a rated uninterrupted current of 5000 A and rated operational voltage of 690 V AC. Its E6.2V performance level provides an ultimate short-circuit breaking capacity of 150 kA at 400–415 V AC and a rated short-time withstand current of 100 kA for 1 second, making it suitable for electrical networks with exceptionally high prospective fault currents.
Air circuit breakers such as the ABB SACE Emax 2 protect high-current low-voltage electrical systems against damaging overload and short-circuit conditions. The E6.2V frame combines a substantial 5000 A current rating with extremely high short-circuit interruption capability, making this breaker suitable for large electrical networks where fault levels, selectivity and continuity of supply are critical considerations.
The Ekip Touch electronic trip unit provides adjustable long-time overload, short-time delayed and instantaneous short-circuit protection through its LSI functions. Its touchscreen interface simplifies protection configuration and system monitoring, while the wider Emax 2 architecture supports communication and integration with modern automation, supervision and intelligent power-management systems.
| Series | SACE Emax 2 |
|---|---|
| Frame | E6.2 |
| Order code / SKU | 1SDA072625R1 |
| EAN | 8015644764753 |
| Product type | Air circuit breaker |
| Rated uninterrupted current (Iu) | 5000 A |
| Rated operational voltage | 690 V AC |
| Number of poles | 3 |
| Current type | AC |
| Performance level | V |
| Trip unit | Ekip Touch |
| Release type | Electronic / solid-state |
| Protection functions | LSI |
| Overload release adjustment range | 2000–5000 A |
| Short-time delayed short-circuit adjustment range | 3000–50000 A |
| Instantaneous short-circuit adjustment range | 7500–75000 A |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 150 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 150 kA |
| Rated short-time withstand current (Icw, 1 s) | 100 kA |
| Integrated earth-fault protection | No |
| Execution | Withdrawable mobile part |
| Main circuit connection | Connection through separate fixed part |
| Auxiliary change-over contacts | 4 |
| Motor operator | Optional |
| DIN rail mounting | No |
| Standard | IEC 60947-2 |
The ABB 1SDA072625R1 is a three-pole SACE Emax 2 E6.2V withdrawable air circuit breaker mobile part rated at 5000 A and equipped with an Ekip Touch LSI electronic trip unit.
The breaker has a rated uninterrupted current of 5000 A and a rated operational voltage of 690 V AC.
The E6.2V provides an ultimate short-circuit breaking capacity of 150 kA at 400–415 V AC and a rated short-time withstand current of 100 kA for 1 second.
Ekip Touch is ABB’s electronic trip unit with touchscreen-based protection and monitoring functionality, while LSI denotes long-time, short-time and instantaneous protection against overload and short-circuit conditions.
The 1SDA072625R1 is a withdrawable mobile part designed for connection through the appropriate Emax 2 fixed part, allowing the breaker to be isolated and withdrawn from the switchboard for inspection, servicing and maintenance.
ABB SACE Emax 2 air circuit breakers combine high-current capability, exceptional short-circuit performance and advanced electronic protection for demanding industrial, infrastructure, data-centre and critical low-voltage power distribution systems.