Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072622R1 E6.2V 5000 Ekip Dip LSI 3p WMP is a 5000 A three-pole withdrawable SACE Emax 2 air circuit breaker with long-time, short-time and instantaneous electronic protection and up to 150 kA short-circuit breaking capacity for demanding low-voltage power distribution systems.
£31,602.44
The ABB E6.2V 5000 Ekip Dip LSI 3p WMP, order code 1SDA072622R1, is a high-capacity three-pole air circuit breaker (ACB) from the ABB SACE Emax 2 range, designed for protection and switching in demanding low-voltage power distribution systems. With a 5000 A rated uninterrupted current and ABB's Ekip Dip LSI electronic trip unit, it provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.
The E6.2V is engineered for electrical installations with exceptionally high prospective fault currents. Its V-performance level provides a rated ultimate short-circuit breaking capacity of 150 kA at 415 V AC and 100 kA at 690 V AC, making this breaker suitable for major industrial, infrastructure and high-power distribution systems where dependable interruption of severe fault currents is essential.
The 1SDA072622R1 is the moving part of a withdrawable circuit breaker, designed for installation with the appropriate fixed part in compatible ABB SACE Emax 2 switchgear. The Ekip Dip LSI release adds short-time protection to the long-time and instantaneous functions, supporting improved selectivity and coordination between upstream and downstream protective devices.
Air circuit breakers such as the ABB SACE Emax 2 provide switching, isolation and circuit protection for high-current low-voltage electrical networks. The E6.2V combines a substantial 5000 A current rating with an exceptional 150 kA breaking capacity at 415 V AC and 100 kA at 690 V AC, making it particularly suitable for major incoming and distribution circuits where very high prospective fault currents must be safely interrupted.
The Ekip Dip LSI electronic trip unit provides long-time overload (L), short-time delayed short-circuit (S) and instantaneous short-circuit (I) protection. The addition of adjustable short-time protection allows improved selectivity between protective devices compared with an LI-only configuration, helping isolate faults closer to their source while supporting continuity elsewhere in a properly coordinated distribution system.
| Series | SACE Emax 2 |
|---|---|
| Product group | Emax2 Air Circuit Breaker |
| Order code / MPN | 1SDA072622R1 |
| Product type | Air circuit breaker |
| Frame | E6.2 |
| Performance level | V |
| Rated uninterrupted current (Iu) | 5000 A |
| Number of poles | 3 |
| Current type | AC |
| Rated voltage | 690 V AC |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 150 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 150 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 100 kA |
| Protection release | Ekip Dip LSI |
| Release type | Electronic |
| Protection functions | L (long-time), S (short-time), I (instantaneous) |
| Overload release setting | from 2000 A |
| Short-time delayed short-circuit release setting | from 3000 A |
| Instantaneous short-circuit release setting | from 7500 A |
| Integrated earth-fault protection | No |
| Version | Withdrawable |
| Configuration | Moving part |
| Main-circuit connection | Connection at separate chassis part |
| Auxiliary contacts | 4 change-over contacts |
| Switched-off indication | Yes |
| Control element | Push button |
| Motor operator | Optional |
| Integrated motor operator | No |
| Integrated undervoltage release | No |
| Degree of protection | IP30 |
| Electrical durability at Ue ≤ 440 V | 3000 operating cycles |
| Electrical durability at Ue 500–690 V | 2000 operating cycles |
| Operating frequency | 10 cycles per hour |
| DIN rail mounting | No |
The ABB 1SDA072622R1 is a 5000 A three-pole air circuit breaker designed for switching and protecting high-current low-voltage power distribution systems against overload and short-circuit conditions.
The E6.2V 5000 1SDA072622R1 has a rated uninterrupted current of 5000 A, with its Ekip Dip overload protection setting starting from 2000 A.
The Ekip Dip LSI electronic trip unit provides long-time overload (L), short-time delayed short-circuit (S) and instantaneous short-circuit (I) protection. This LSI configuration does not include integrated earth-fault protection.
The E6.2V breaker provides a rated ultimate short-circuit breaking capacity of 150 kA at 400–415 V AC and 100 kA at 690 V AC, making it suitable for demanding installations with exceptionally high prospective fault currents.
Yes. The 1SDA072622R1 is the three-pole moving part of a withdrawable SACE Emax 2 circuit breaker, designed for installation with the appropriate fixed part in a compatible switchgear assembly.
ABB SACE Emax 2 air circuit breakers provide dependable high-current protection and switching for low-voltage power distribution systems, combining high short-circuit performance, advanced electronic protection and flexible withdrawable switchgear integration.
We use cookies